AXE MMX-AP Series User manual

AXE MICROPROCESS PANEL CONTROLLER METER (Pushwhell Switch)
MMX-AP series
■Features
◎
Measuring DCA/DCV/ACA/ACV/Potentiometer/Pt-100/
Transmitter/Load Cell/Resistor….etc
◎
3 Alarm function
◎
Display average can be modified(1~99)
◎
Accuracy 0.1% F.S.±1 digit
◎
0.4” LED highlight display
◎
Display range -19999~19999 can be modified
◎
Man-machine interface ,easy to operate
◎
Pushwheel digit switches alarm setting,0~99999 or ±9999
◎
EEPROM Saving, data safekeeping about 10 years
◎
Decimal point can be modified
◎
Modified inside parameter, must have pass code
◎
Display value can Max. hold function
■Name Of Parts
■Alarm Function Diagram
◎
ACT=HI
≧
˙Indication setting
(alarm lamp and relay on)
˙Indication<setting
(alarm lamp and relay off)
◎
ACT=LO
Indication<setting
(alarm lamp and relay on)
≧
˙Indication setting
(alarm lamp and relay off)
Key Introduce Operation Manual
Key Function
1.In normal display, The key function is call out setting group
2.In parameter setting page, The key function is data Enter , and goto next page
Key Function
Into parameter setting page, the parameter mark&data is alternate display, If need modify data can
press shift key into setting procedure, The display is lock parameter data, this time must let off key
about 0.2 sec, press again, the cursor(twinkle express)is cycle moving left. (Key Response about
0.2 sec)
8
8
8
8
8
8
8
8
8
8
HI SET
LO SET
HI
LO
GO
FUN
Alarm indicate
Function
indicate
(AZ/HOLD/MAX)
Display
Cursor shift
Parameter ENTER
(Function call out)
Set-value up(Display adjustment call out)
Set-value down
AL1 VALUE
AL2 VALUE
INPUT
HI set value
Lo set value
Hysteresis
(ACT=HI)
Hysteresis
(ACT=Lo)
HI
C
omparative
output
Lo comparative
output
’
(
-
+tar
t band)
-start band
Input=Zero
-
input limit
Lo
rela
output
’
(-start band)
+start band
Symmetrical
+start
band
Decided of DEL and SDT
Not active range
Not active range
ON
OFF

Key Function
1.In normal display, The key function is call out adjustment display value (DZERO&DSPAN)page
2.Into parameter setting page, the parameter mark&data is alternate display, If need modify data
can press up key into setting procedure, The display is lock parameter data, this time must let off
key about 0.2 sec, press again, the parameter data will increment. (Key Response about 0.2 sec)
Key Function
Into parameter setting page, the parameter mark&data is alternate display, If need modify data can
press down key into setting procedure, The display is lock parameter data, this time must let off
key about 0.2 sec, press again the parameter data will decrement. (Key Response about 0.2 sec)
& Key Function
In setting group or setting page press &
key return normal display,
but if in setting page the
modify data will be lost
No Key in anything In setting group or setting page no key in anything about 2 minutes, return normal display,
but if in
Setting page the modify data will be lost
Step
Parameter Mark Description
Parameter Mark
Operation Manual
1 Normal display
Press /FUNC key into P.COD setting page
2 P.COD(Pass code input page)
1.Key in 5 digit pass code with or or key
2.Press key,
the pass code is right into setting group , otherwise
return normal display
3 SYS(System setting group)
ROP(Alarm setting group)
1.Select setting group with key
2.Press key into setting page of selection setting group
Step
Parameter Mark Description
Parameter Mark
Operation Manual
4 SYS(System setting group)
Press key decide SYS setting group , press
key into
DP setting page
4-1
DP(Decimal Point)
Default=0
1.Decide decimal point position with or key (0 to 4)
2.Press key enter data and into DSPL setting page
4-2
DSPL(Display Low Scale)
Default=0
1.Decide display low scale with & & key (
-19999~19999)
2.Press key enter data and into DSPH setting page
4-3
DSPH(Display High Scale)
Default=19999
1.Decide display high scale with & & key (
-19999~19999)
2.Press key enter data and into AVG setting page
4-4
AVG (Average)
Default=1
1.Decide display Average times with & & key (1~99)
2.Press key enter data and into LCUT setting page
4-5
LCUT (Low Cut)
Default=0
1.Decide display low cut with & & key (0~99)
2.Press key enter data and into CODE setting page
4-6
CODE(Pass Code)
Default=0
1.Decide Pass code with & & key (0~19999)
2.Press key enter data and into LOCK setting page
4-7
LOCK(Panel Lock)
Default=NO
1.Decide panel lock with or key (NO or YES)
2.Press key enter data and return SYS setting group
Step
Parameter Mark Description
Parameter Mark
Operation Manual
5 ROP(Alarm setting group)
Press key decide ROP setting group
, press key into
ACT1 setting page
5-1
ACT1(Alarm Active 1 setting
page )Default=HI
1.Decide active 1 with or
key(HI or LO)
2.Press key enter data and into ACT2 setting page
5-2
ACT2(Alarm Active 2 setting
page )Default=HI
1.Decide active 2 with or
key(HI or LO)
2.Press key enter data and into
HYS1 setting page
5-3
HYS1(Alarm Hysteresis 1
setting page)Default=0
1.Decide Hysteresis 1 with or
or
key(0~999)
2.Press key enter data and into HYS2 setting page
5-4
HYS2(Alarm Hysteresis 2
setting page)Default=0
1.Decide Hysteresis 2 with or
or
key(0~999)
2.Press
key enter data and into DEL1 setting page
5-5
DEL1(Alarm Delay 1 setting
page)Default=0
1.Decide delay 1 with or
or
key(0~99.9 s
ec)
2.Press key enter data and into DEL2 setting page
5-6
DEL2(Alarm Delay 2 setting
page)Default=0
1.Decide delay 2 with or
or
key(0~99.9sec)
2.Press
key enter data and into SB setting page
5-7
SB(Start band)
Default=0
1.Decide start band with or
or
key(
-999~999)
2.Press key enter data and into SDT setting page

5-8
SDT(Start Delay Time)
Default=0
1.Decide start delay time with or
or
key(0~99.9sec)
2.Press key enter data and return ROP setting group
Step
Parameter Mark Description
Parameter Mark
Operation Manual
6 Normal display
Press /D
-ADJ key about 3 sec, into DZERO adjustment page
6-1
DZERO(Display Zero Adjust
)Default=0
1.Adjustment display zero with or
key
2.Press key e
nter data and into DSPAN adjustment page
6-2
DSPAN(Display Span Adjust
)Default=0
1.Adjustment display span with or
key
2.Press key enter data and return normal display
Appendix
Error Mark Description Error Mark Analyze & Description
1 Input over error detect
Input signal over range(120%)
2 Input under error detect
Input signal under range(-20%)
3
Display over error detect
Display over range(99999)
4
Display under error detect
Display under range(-19999)
5 A/D Converter error detect
1.Input signal over range (180%)
2.Inside circuit damage
Please moving input signal if still display ADER, please contact us
6 EEPROM error detect
1.External interference when EEPROM read/write
2.EEPROM write over 100 million times(guarantee 10 years)
Please power reset, if still display E-00,doing following step:
1.E-00 & No alternate display for inquire reset EEPROM
2.Decide Yes with or
key, press
key return normal display
3.EEPROM was reset ,Please follow step 1~6 set again