BAPI BAPI-Stat Quantum Series Manual

Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specications subject to change without notice.
rev. 04/23/1841012_ins_quantum_slider_temp_display
1 of 6
Product Identication and Overview
Fig. 1: BAPI-Stat
“Quantum” with slider
setpoint adjustment,
override button and
provided screw pack.
The BAPI-Stat “Quantum” style room temperature sensor features a
large format LCD and slider setpoint adjustment. Additional options
include button override and communication jack.
The setpoint is available as a resistance or voltage output. The
override is a momentary closure signal that can be congured in
parallel with the sensor or setpoint, or as a separate momentary
output.
Mounting
JUNCTION BOX
1. Pull the wire through the wall and out of the junction box, leaving about 6
inches free.
2. Pull the wire through the hole in the base plate.
3. Secure the base to the box using the #6-32 x 1/2 inch mounting screw
provided.
4. Terminate the unit according to the guidelines in the Termination section.
5. Attach Cover by latching it to the top of the base, rotating the cover down
and snapping it into place.
6. Secure the cover by backing out the lock-down screws using a 1/16” Allen
wrench until they are ush with the bottom of the cover.
DRYWALL MOUNTING
1. Place the base plate against the wall where you want to mount the sensor.
2. Using a pencil, mark out the two mounting holes and the area where the
wires will come through the wall.
3. Drill two 3/16” holes in the center of each marked mounting hole. Insert a
drywall anchor into each hole.
4. Drill one 1/2” hole in the middle of the marked wiring area.
5. Pull the wire through the wall and out the 1/2” hole, leaving about 6” free.
6. Pull the wire through the hole in the base plate.
7. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
8. Terminate the unit according to the guidelines in the Termination section.
9. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover
by backing out the lock-down screws using a 1/16” Allen wrench until they are ush with the bottom of the cover.
NOTE: In a wall-mount application, the mixing of room air and air from within the wall cavity can lead to erroneous
readings, condensation, and premature failure of the sensor. To prevent this condition, plug the conduit hole with
insulation in the junction box.
Fig. 2: Mounting hardware is provided
for both J-Box and drywall installation
(J-Box installation shown)

Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specications subject to change without notice.
rev. 04/23/1841012_ins_quantum_slider_temp_display
2 of 6
Termination
BAPI recommends using twisted pair of at least 22AWG and sealant lled connectors for all wire connections. Larger
gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes.
Do NOT run this device’s wiring in the same conduit as AC power wiring. BAPI’s tests show uctuating and inaccurate
signals are possible when AC power wiring is in the same conduit as the signal lines. If you are experiencing any of these
difculties, please contact your BAPI representative.
Fig. 3: BAPI-Stat “Quantum”
Circuit Board
BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring
connections are important to a successful installation. Not observing these recommendations may damage the
product and void the warranty.
TERMINAL DESCRIPTION
GND ........................... Power Supply Ground (Common to the controller)
V+ .............................. Power Supply Hot (See specs for voltage details)
W1 ............................. Not Used
OCCUPY ................... BAPI-Man Occ/Un-Occ indicator Input.
Ground terminal to ll in the BAPI-Man icon for
Occupied.
SEN1 & SEN2 ........... Sensor output per order (resistive). No polarity.
*If the unit is a common ground conguration, see
“Grounding Note” below.
SET1 & SET2 A) Setpoint output per order (resistive). *If the
unit is a common ground conguration, see
“Grounding Note” below.
B) Setpoint output per order (voltage). SET1 is
“+”, SET2 is “-”.
OVR1 & OVR2........... Override Output (Dry contact) if unit is ordered
with Override as a Separate Output (-J). The
override can also be ordered as a momentary
shunt across the sensor terminals SEN1 & SEN2
(-N) or as a momentary shunt across the setpoint
terminals SET1 & SET2 (-P). *If the unit is a
common ground conguration, see “Grounding
Note” below.
EXT-TEMP & EXT-GND
.. Remote sensor terminals. No polarity. *If the
unit is a common ground conguration, see
“Grounding Note” below. To use these terminals,
a 10K-2 thermistor sensor must be ordered
separately and the temperature value from this
sensor will be displayed on the LCD but will not
be sent to the controller. Max wire distance for the
external sensor is 25 feet.
*Grounding Note:
Common Ground or Differential Ground congurations are selected per order (Common Ground is default). The
Differential Ground conguration indicates that SEN2, SET2, OVR2 and EXT-GND must all be wired separately (No
internal common connection). The Common Ground conguration indicates that SEN2, SET2, OVR2 and EXT-GND are
connected to GND internally (All internally common).

Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specications subject to change without notice.
rev. 04/23/1841012_ins_quantum_slider_temp_display
3 of 6
Optional Test and Balance Switch (SW7)
Optional Communication Jack Wiring
Fig. 5: C35L Comm. Jack
(3.5mm plug shown for
clarity)
Fig. 6:
C11/C22
Comm. Jack
PIN # WIRE COLOR
1 Not Connected
2 Black
3 Red
4 Yellow
5 Green
6 Not Connected
C11L/C22L Comm. Jack Wiring
Location WIRE COLOR
Ground Black
Tip White
Ring Red
C35L Comm. Jack Wiring
Sensor Type Low Temp (40° F)
Resistance Value
High Temp (105°F)
Resistance Value
1000Ω RTD 1.02KΩ (41.20°F) 1.15KΩ (101.5°F)
3000Ω Thermistor 7.87KΩ (39.8°F) 1.5KΩ (106.8°F)
10K-2 Thermistor 30.1KΩ (34.9°F) 4.75Ω (109.1°F)
10K-3 Thermistor 26.7KΩ (35.9°F) 5.11KΩ (108.4°F)
10K-3(11K) Thermistor 7.32KΩ (43.7°F) 3.65Ω (105.2°F)
Test and Balance Switch (SW7)
NORM: Sensor operates normally
LOW: Sets the sensor value low
HIGH: Sets the sensor value high
On the Test and Balance Switch (SW7), the NORM position allows the
real sensor to be monitored. The HIGH position forces the output to a
very hot reading and the LOW position forces a very cold reading (see
Table below).
Fig. 4: Back Plate
Comm. Jack
Locations

Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specications subject to change without notice.
rev. 04/23/1841012_ins_quantum_slider_temp_display
4 of 6
BAPI-Stat Quantum sensor comes with a display, slider setpoint adjustment and optional override.
Temperature:
Displayed in Fahrenheit or Celsius in the major display. (Field adjustable via the “F/C” switch on DIP Switch SW5.)
Temperature Setpoint Slider:
Moving the slidepot enough to change the setpoint will display the setpoint in the major of the display. The setpoint
temperature display will ash the digits indicating that setpoint is being changed.
Override Button:
When the override button is pressed on display units, the BAPI-Man Icon will display (Fig
8). A dry resistance of less than 15 ohms appears across the override output.
Note: The unit must receive a conrmation (ground) signal on the “OCCUPY” terminal for
the BAPI-Man to remain visible on the screen. Pressing the Override button will light the
BAPI-Man icon; however, if no conrmation signal is received, then the BAPI-Man will go
blank (disappear) after 5 seconds.
Upon receiving a rst conrmation (ground) signal on the “OCCUPY” terminal, the
BAPI-Man will show occupied (Solid). The BAPI-Man will then show unoccupied (Hollow)
whenever the conrmation signal is removed and occupied when the signal is returned.
The only way to blank the BAPI-Man from the display after it has received a rst
conrmation signal is to cycle power.
Front Panel & Control Descriptions
Fig. 7: BAPI-Stat “Quantum” with
Display, Slider Setpoint and Override.
BAPI-Man Icon
Major Display
Hollow
equals
“Unoccupied”
Fig. 8: BAPI-Man Icon
Solid
equals
“Occupied”
Temperature
Setpoint Slider
Override
Button

Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specications subject to change without notice.
rev. 04/23/1841012_ins_quantum_slider_temp_display
5 of 6
Optional Technician Adjustments
The unit is shipped ready to install. The following Setup or Program Menu Changes are available if the installer decides to
change the factory settings.
ENTERING PROGRAM MODE TO ADJUST PARAMETERS (see Figs 9-11 for adjustment tools)
1. Power unit and set DIP Switch SW5 #2 (PROG) to ON (right). The LCD will show a page number
(P1-P9). P1-P9 will ash to indicate that display parameter can be adjusted.
2. Slide Potentiometer J1 is used to scroll up and down through pages and adjusting the page
parameters.
NOTE: For units with Temperature Setpoint, the Slide Potentiometer will extend outside the
enclosure. For units without Temperature Setpoint, the Slide Potentiometer will not be extended outside the enclosure.
3. Push Switch SW8 as “Enter” to switch between page number and adjusting the page parameter.
4. After a page parameter has been adjusted, push Switch SW8 to conrm the change.
5. To exit Program Mode, Set DIP Switch SW5 #2 (PROG) to OFF (left).
Note: DIP Switch SW5 #1 (°F/C) can be used to switch the display between °F and °C.
Parameter Page
Temperature Offset P1
Item Display Action
0 Setpoint Enabled
1Setpoint Disabled (pushbutton only): Display shows
setpoint when activated, but can't be changed
2Setpoint Display Only: Shows setpoint only, does not
display local temperature
3Setpoint Not Displayed: Setpoint can be changed, but
will not display
Item Display Action
0 Display in whole digits
1 Display in 0.5° increments, °F and °C
2 Display in 0.1° increments, °F and °C
Temperature Setpoint
Display Low P4
Temperature Setpoint
Display High P5
Temperature Setpoint
Output Low P6
Temperature Setpoint
Output High P7
Temperature Setpoint
Value P8
User Fan/Mode Setpoint P9
Programming Pages
±5° in 0.1° increments
Adjustment
Adjust the Low Temperature of the setpoint range
Shows Fan/Mode setpoint on units configured with Mode/
Setpoint (Ready Only. Pushbutton only. Major display shows 0)
Shows High Setpoint Output
(Read Only. Displayed in 10 ohm resolution)
P2
P3Temperature Display
Setpoint Lockout
Adjust the High Temperature of the setpoint range
Shows Low Setpoint Output
(Read Only. Displayed in 10 ohm resolution)
Shows temperature setpoint value (Ready Only)
Fig. 10: J1 Slide
Potentiometer
Fig. 11: Enter
Switch SW8
Fig. 9: DIP
Switch SW5

Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specications subject to change without notice.
rev. 04/23/1841012_ins_quantum_slider_temp_display
6 of 6
General Diagnostics
POSSIBLE PROBLEM: POSSIBLE SOLUTIONS:
Temperature reading is incorrect - Verify that the input is set up correctly in the controller’s and building automation
software.
- Check wiring for proper termination and check for opens or shorts.
- Check for corrosion at either the controller or the sensor. Clean off the corrosion,
re-strip the interconnecting wire and reapply the connection. In extreme cases,
replace the controller, interconnecting wire and/or sensor.
- Label the terminals at the sensor end and the controller end. Disconnect the
interconnecting wires from the controller and the sensor. With the wires separated
at both ends, measure the resistance from wire-to-wire with a multimeter. The
meter should read greater than 10 Meg-ohms, open or OL depending on the meter
you have. Short the interconnecting wires together at one end. Go to the other
end and measure the resistance from wire-to-wire with a multimeter. The meter
should read less than 10 ohms (22 gauge or larger, 250 feet or less). If either test
fails, replace the wire.
- Measure the physical temperature at the temperature sensor’s location using an
accurate temperature standard. Disconnect the temperature sensor wires and
measure the temperature sensor’s resistance across the sensor output pins with
an ohmmeter. Compare the temperature sensor’s resistance to the appropriate
temperature sensor table on the BAPI website. If the measured resistance
is different from the temperature table by more than 5% call BAPI technical
support. Find BAPI’s website at www.bapihvac.com; click on “Resource Library”
and “Sensor Specs” then click on the type of sensor you have. Don’t forget to
reconnect the wires.
- If the unit has a Test and Balance switch, make sure it is in the correct position.
Setpoint reading is incorrect - Make sure that the setpoint output is correct. Remove the setpoint output wire and
check the output for the correct resistance or voltage output. See the product label
for your specic range.
Override is not working correctly - Verify that the resistance across the override output is less than 15 ohms when the
override is pushed.
Specications
Power for 24VDC Power Units:
0 to 5 VDC Setpoint: ..... 9 to 40 VDC (24 VDC nominal)
0 to 10 VDC Setpoint: ... 15 to 40 VDC (24 VDC nominal)
Resistive Setpoint: ........ 9 to 40 VDC (24 VDC nominal)
Any Allowed Setpoint: ... 15 to 28 VAC (24 VAC nomimal)
Note: AC power requires a separate pair of shielded wires
Power Consumption: 13 mA max DC; .32 VA max AC
Wiring: 22 to 16AWG
Mounting: Standard 2x4” box or drywall (Screws provided)
Outputs:
Temperature: Thermistor or RTD
Temperature Setpoint: Resistive or Voltage
Fan/System Control: Resistive
Inputs: Dry contact (24V, <1mA)
Occupied: OCCUPY terminal “Grounded”
Unoccupied: OCCUPY terminal “Open to Ground”
External Sensor: 10K-2 thermistor,
Purchased separately,
Wired 25’ max from sensor
Enclosure Material: ABS Plastic, UL94V-0
Environmental Ambient:
Temperature: 32 to 122ºF (0 to 50ºC)
Humidity: 0 to 95% RH Non-condensing
Storage: 32 to 185°F (0 to 85°C)
Agency: RoHS
Table of contents
Other BAPI Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

S+S Regeltechnik
S+S Regeltechnik THERMASGARD RGTF1 Series Operating Instructions, Mounting & Installation

Ropex
Ropex CIRUS UPT-6010 operating instructions

Procool
Procool SF-104 quick start guide

Middleby Marshall
Middleby Marshall 75729 instructions

Autonics
Autonics TCN Series manual

Carrier
Carrier ComfortChoice EDGE Installation and start-up instructions