BAPI BA-H200 Series Manual

24595_ins_BAPI_4_room_humidity
Installation & Operating Instructions
BA/B4-H200 Series
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
rev.01/26/11
Specications subject to change without notice.
Overview
Figure 1: BAPI-Stat 4 Room Humidity w/Setpoint & Override
The BAPI-Stat 4 Style room unit is available as a humiditiy only sensor or as a combination temperature and humidity sensor
with optional LCD display, temperature setpoint adjustment and occupant override. It is available with the entire line of BAPI
termperature sensors.
1 of 5
Specications
Power:
15 to 35 VDC for 4 - 20 mA Output
10 to 40 VDC for 0 - 5 VDC Output
15 to 40 VDC for (0, 2) - 10 VDC Output
12 to 24 VAC for 0 - 5 VDC Output
(requires a separate pair of shielded wires)
15 to 28 VAC for (0, 2) - 10 VDC Output (requires a separate pair of shielded wires)
Power Consumption:
20 mA max. for 4 - 20 mA Output
4 mA max. for 0 - 5 VDC and (0, 2) - 10 VDC Output
0.1 VA max. for 0 - 5 VDC and (0, 2) - 10 VDC Output
Terminals:
Cage clamp, 16 to 22 AWG
Sensing Elements:
Temperature - Thermistor, RTD or Semiconductor
Humidity - Capacitive Polymer, ±1.8% RH Accuracy
Field Calibration:
Potentiometer (R34)
±5% in 0.1% increments
Note: Units are factory calibrated
Wiring: 2 to 6 pair of 16 to 22 AWG
Mounting:
Standard 2”x4” J-box or drywall mount - screws provided
Environmental Operation Range:
Temperature: 32 to 122 °F (0 to 50 °C)
Humidity: 0 to 95%, non-condensing
Material: ABS Plastic
Material Rating: UL 94, V-0, RoHS

24595_ins_BAPI_4_room_humidity
Installation & Operating Instructions
BA/B4-H200 Series
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
rev.01/26/11
Specications subject to change without notice.
Terminations
Note1: The termination screws should be turned fully Counter Clockwise (CCW) to open the jaws fully. Then insert the eld wire and turn
the screws Clock Wise (CW) to pinch the wire fully closed. If the jaws are left partially open, the inserted wire may be on bottom of, instead
of inside, the jaws causing a poor connection.
BAPI recommends using twisted pair of at least 22AWG and sealant lled connectors for all wire connections. Larger gauge wire may
be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes.
Do NOT run this device’s wiring in the same conduit as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used
to supply highly inductive loads such as motors, contactors and relays.
BAPI recommends against wiring the sensor with power applied as accidental arcing may damage the product and void the warranty.
Fig 3: Circuit Board
NOTE: Common Ground Option (CG) OVR2, SEN2, and SET2 are connected together internally.
Differential Ground Option (DF) All terminals are independent.
4 to 20 mA Termination
Terminal Function
OVR1 & OVR2 Override Output (Dry Contact Switch). If unit is in common ground
(-CG), OVR2 is internally connected to SET2 & SEN2.
SET1 & SET2 Setpoint output. If unit is common ground (-CG), SET2 is internally con-
nected to OVR2 & SET2.
SEN1 & SEN2 Sensor Output (Resistive Output). If common ground (-CG), SEN2 is in-
ternally connected to OVR2 & SET2. (Semiconductor SEN1=+, SEN2=-)
EXT-OVR Allows remote control of the LCD indicator for occupancy, and is acti-
vated by logic LOW or power supply ground at this terminal.
VOUT Not Used
V+ Power, see specications section for details
GND 4 to 20 mA Humidity Signal [to analog input of controller]
0 to 5 VDC or 0 to 10 VDC or 2-10 VDC Termination
Terminal Function
OVR1 & OVR2 Override Output (Dry Contact Switch). If unit is common ground (-CG),
OVR2 is internally connected to SET2 & SEN2.
SET1 & SET2 Setpoint output. If unit is common ground (-CG), SET2 is internally
connected to OVR2 & SEN2.
SEN1 & SEN2 Sensor Output (Resistive Output). If common ground (-CG), SEN2 is
internally connected to OVR2 & SET2. (Semiconductor SEN1=+,SEN2=-)
EXT-OVR Allows remote control of the LCD indicaor for occupancy, and is activated
by logic LOW or power supply ground at this terminal.
VOUT Voltage Humidity Signal [to analog input of controller]
V+ Power, see specications section for details
GND To controller power supply ground [GND or Common]
2 of 5
Mounting
Mounting hardware is provided for both junction box and drywall installation (junction box installation shown).
Junction Box
1. Pull the wire through the wall and out of the junction box, leaving about six inches free.
2. Pull the wire through the hole in the base plate.
3. Secure the plate to the box using the #6-32 x 1/2 inch mounting screws provided.
4. Terminate the unit according to the guidelines in the Termination section.
5. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place.
6. Secure the cover by backing out the lock-down screws using a 1/16” Allen wrench
until they are ush with the bottom of the cover.
Drywall Mounting
1. Place the base plate against the wall where you want to mount the sensor.
2. Using a pencil mark out the two mounting holes and the area where the wires will
come through the wall.
3. Drill two 3/16” holes in the center of each marked mounting hole. Insert a drywall
anchor into each hole.
4. Drill one 1/2” hole in the middle of the marked wiring area.
5. Pull the wire through the wall and out of the 1/2” hole, leaving about six inches free.
6. Pull the wire through the hole in the base plate.
7. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
8. Terminate the unit according to the guidelines in the Termination section.
9. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place.
10. Secure the cover by backing out the lock-down screws using a 1/16” Allen wrench until they are ush with the bottom of the cover.
Fig 2: Mounting to a Junction Box
NOTE: In any wall-mount application, the wall temperature and the temperature of the air within thewall cavity can cause erroneous readings. The
mixing of room air and air from within the wall cavity can lead to condensation, erroneous readings and premature failure of the sensor. To prevent these
conditions, seal the conduit leading to the junction box or ll the box with insulation.

24595_ins_BAPI_4_room_humidity
Installation & Operating Instructions
BA/B4-H200 Series
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
rev.01/26/11
Specications subject to change without notice.
3 of 5
Optional Test Ballance Switch
Low: Will set se nsor value low
Norm : Sensor will op erate norm ally
High: W iil se t sensor value High
Sensor Type Low Temp High Temp
1000 Ω RTD 1.02K Ω (41.2°F) 1.15K Ω (101.5°F)
3000 Ω Thermistor 7.87K Ω (39.8°F) 1.50K Ω (106.8°F)
10K-2 Thermistor 30.1K Ω (34.9°F) 4.75K Ω (109.1°F)
10K-3 Thermistor 26.7K Ω (35.9°F) 5.11K Ω (108.4°F)
10K-3(11K) Thermistor 7.32K Ω (43.7°F) 3.65K Ω (105.2°F)
Figure 4: Calibration Switch
Figure 5: R34
The optional technician adjustment procedure allows temperature and humidity offsets, °F or °C
display units or display information to be changed at any time. When the unit is powered up,
pressing the tact switch at SW1 will enter the user calibration adjustment mode (See Figure 4).
When pressed, the LCD will show page zero, P0. The page numbers auto-scroll to P5 and then
the unit returns to the normal run mode. Pressing SW1 when any page number is displayed will
show the calibration value that is associated with that page. The variable will auto-scroll and will
show all the allowed values for the selected page. Pressing SW1 when the variable value you
need is shown will record that value and return to showing page numbers.
* When active means when moving the setpoint slider.
** Display toggles through selections.
Optional Technician Adjustments
Display Units
Non-Display Units
Potentiometer R34 as shown in Fig 6 can be adjusted to change the output ±5%. A high accuracy reference is recommended.
Parameter Page Adjustment
Designator
Temperature Offset P0 ±5° in 0.1° increments. A high accuracy reference is recommended.
Humidity Offset P1 ±5% in 0.1% increments or R34
When R34 is selected, humidity offset is set by turning
potentiometer R34 situated just above the override switch.
See Figure 6. A high accuracy reference is recommended.
Display Units P2 °F or °C
Display RH to Temp Toggle Time P3 3 to 11 seconds
Display Resolution P4 0 = 0.5
1 = 0.1
Display Section P5 0 = Temperature, Humidity and Temperature Setpoint when active*
1 = Temperature and Temperature Setpoint when active*
2 = Humidity and Temperature Setpoint when active*
3 = Temperature, Humidity and Temperature Setpoint**
4 = Temperature and Temperature Setpoint**
5 = Humidity and Temperature Setpoint**
6 = Temperature Setpoint
7 = Temperature and Humidity**
8 = Temperature
9 = Humidity

24595_ins_BAPI_4_room_humidity
Installation & Operating Instructions
BA/B4-H200 Series
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
rev.01/26/11
Specications subject to change without notice.
4 of 5
Optional Communications Jack Wiring
Note: Male Jack shown for clarity
Figure 6: C35 Communications Jack 3.5mm Front 3.5mm Back
C11L Front C11L Back
Figure 7: C11 Communications Jack
C35 Wiring
Wire Color
Ground Black
Tip White
Ring Red
C11 Wiring
Comm Jack Pin Wire Color
1 Not Connected
2 Black
3 Red
4 Yellow
5 White or Green
6 Not Connected
The display indicates dry bulb temperature in degrees Fahrenheit or Celsius, dew point in degrees Fahrenheit or Celsius, relative hu-
midity in %RH, temperature setpoint in degrees Fahrenheit or Celsius. Temperatures and relative humidity can be displayed in a rotat-
ing manner, see the Optional Technicians Adjustments section. The BAPI Man icon indicates that the override button has been pushed.
Dry Bulb Temperature: When dry bulb temperature is displayed the INSIDE icon as well as the appropriate units icon are illuminated.
Dew Point Temperature: When dew point temperature is displayed the letters dP are displayed for 2 seconds just before the dew
point temperature is displayed. Then the dew point temperature is displayed with the appropriate units icon illuminated, the INSIDE
icon is off.
Relative Humidity: When relative humidity is displayed the INSIDE icon as well as %RH are illuminated.
Signies Space Temperature
or Humidity Being Displayed
Signies Temp Setpoint
Display or Setpoint Adjustment
Display Units
0.6 inch Display
BAPI Man Icon
Setpoint Slide-Pot: When the temperature setpoint is active (see technician adjustments), moving the slide pot enough to change the
setpoint by one degree will display the setpoint on display units.
Override Button: When pressed, the override icon will display on display units. A dry resistance of less than 15 ohms appears
across the override output (OVR1 to OVR2). Latching the Icon to show that the system is in override requires that a digital output on
your controller be used to connect terminal EXT-OVR to power supply ground.
Figure 8: Optional Dew Point Display
User Operation

24595_ins_BAPI_4_room_humidity
Installation & Operating Instructions
BA/B4-H200 Series
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
rev.01/26/11
Specications subject to change without notice.
Diagnostics
5 of 5
Possible Problems: Possible Solutions:
General troubleshooting • Determine that the input is set up correctly in the controller's and building automation
software.
• Check wiring at the sensor and controller for proper connections.
• Check for corrosion at either the controller or the sensor. Clean off the corrosion, re-
strip the interconnecting wire and reapply the connection. In extreme cases, replace
the controller, interconnecting wire and/or sensor.
• Label the terminals that the interconnecting wires are connected to at the sensor
end and the controller end. Disconnect the interconnecting wires from the controller
and the sensor. With the interconnecting wires separated at both ends measure the
resistance from wire-to-wire with a multimeter. The meter should read greater than 10
Meg-ohms, open or OL depending on the meter you have. Short the interconnecting
wires together at one end. Go to the other end and measure the resistance from
wire-to-wire with a multimeter. The meter should read less than 10 ohms (22 gauge or
larger, 250 feet or less). If either test fails, replace the wire.
Incorrect Humidity • Check power supply/controller voltage supply
• Disconnect sensor and check power wires for proper voltage (see specications below)
Check all software parameters
• If available, check the sensor against a calibrated instrument such as a hygrometer
• Determine if the sensor is exposed to an external environment different from the room
(conduit draft)
Incorrect Temperature • Determine that the temperature sensor's wires are connected to the correct controller
input terminals and are not loose.
• Check the wires at the sensor and controller for proper connections.
• Measure the physical temperature at the temperature sensor's location using an
accurate temperature standard.
Output to Controller
Disconnect the temperature sensor's wire (Terminals SEN1 & SEN2) and measure
the temperature sensor's resistance across the sensor output pins with an ohmmeter.
Put the ohmmeters black lead on Terminal SEN2 and the red lead on Terminal SEN1.
Compare the temperature sensor's resistance to the appropriate temperature sensor
table on the BAPI web site (See below). If the measured resistance is different from
the temperature table by more than 5% call BAPI technical support. Don't forget to
reconnect the wires.
How to Find Temperature Sensor Resistance
Find BAPI's web site at www.bapihvac.com; click on the button labeled SENSORS on
the left of the screen and then click on the sensor type you have.
• Make sure that the sensor leads are not touching one another.
• Determine if the sensor is exposed to an external environment different from the room
(conduit draft)
Humidity Output Selection
Figure 9: Output Jumpers
Moving the jumper on connector J4 will change the humidity output from 4 to 20mA,
0 to 5VDC or 0-10VDC. Figure 9 shows the jumper in the 4 to 20mA, position. The 0-10
VDC jumper is used for the 2-10 VDC signal if an H212 or H312 was ordered.
This manual suits for next models
1
Table of contents
Other BAPI Temperature Controllers manuals