Barcol-Air CERA NXOJOOB User manual

www.airselect.nl
TYPE NXOJOOB
TOTAL VENTILATION CONCEPT FOR STACKED HOUSING
TOTAL VENTILATION CONCEPT FOR STACKED HOUSING
CO2CONTROLLED FRESH OUTSIDE AIR VENTILATION SYSTEM
ONLINE SELECTION TOOL

2© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA | System features
•
CERA:
C
entral
E
nergy
R
ecovery
A
•
Total ventilation concept for stacked housing
•
CO
2
controlled fresh outside air ventilation system
•
CO
2
controlled fresh outside air ventilation system
•
Low energy consumption
•
Airtight class C & damper leakage class 2 accoriding to EN 1751
•
Pressure independent control
•
Low pressure loss
•
Individual room control (up to 6 nos. rooms)
•
®
®
®
•
Plug & Play including factory calibrated BACnet controller
•
•
Low noise system (no fan & internally insulated)
•
•
•
•
The CERA system has been developed by Barcol-Air and Hiensch Engineering
•
Low in energy consumption due to the central heat recovery system | Nominal fan power use very low
•
Low energy according to BENG, NTA8800 calculation

3
© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA | Fresh outside air ventilation control units
Index
TYPE
CERA-1 | CERA-2
Type designation
......................................................................................................................................................
4
Technical information
...............................................................................................................................................
5
Technical information & delivery format
...................................................................................................................
6
............................................................................................................................................................
7
Assembly and installation intructions
........................................................................................................................
8
CERA-1
Dimensions
..............................................................................................................................................................
9
Performance data
....................................................................................................................................................
10
Control sequence of operation (standard)
...............................................................................................................
11
CERA-2
Dimensions
..............................................................................................................................................................
13
Performance data
....................................................................................................................................................
14
Control sequence of operation (standard)
...............................................................................................................
15
CE Declaration of Conformity
..................................................................................................................................
17

4© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
Composition type designation:
N J BX O O O
Position 1:
Product group
N
N = air volume control units
Position 2:
Function
X
X = CERA control unit
1 = non standard, specify separately
Position 3:
Controls (manufacturer)
O
O = without controls, specify separately
J = circular outlets
1 = non standard, specify separately
Position 4:
Outlet
J
Position 5:
Reheat coil
O
O = without reheat coil
Position 6:
Controls (type and function)
O
O = without controls
P
osition
7:
S
ensor
B
O = not applicable
®
2 x 12 point averaging
®2 x 12 point averaging
®
1 = non standard, specify separately
Ordering information:
Standard units:
- quantity of units
- complete 7 digit code
- unit size / model
min
- V
min
- V
max increased
)
- handing (standard right side)
Non standard units:
and/or drawing are/is requested.
Ordering example:
N
X
O
J
O
O
B
1
2
5
R
C
E
R
A
1
Model
Type
CERA
type
1 or 2
Right
or
Left
CERA units | type NXOJOOB
Type designation
TYPE
CERA-1 | CERA-2

5
© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA units | type NXOJOOB
Technical information
Application
- CERA units are pressure-independent fresh outside air volume control
units (ventilation units) suitable for stacked housing. The units have
been designed particularly for systems with low noise criteria and for
the accurate measurement and control of air volumes courtesy of the
®
.
The CERA unit controls the amount of fresh air supplied to the room
based on the measured CO
2
level and features override options using
switches, all of which save energy. The CERA unit controls the amount
of fresh air supplied to the room based on the measured CO
2
levels
between a factory calibrated minimum and maximum set-point. It will
provide increased air volumes when the ‘cooking’ function or ‘bathroom’
function is activated. When the ‘night’ function is active it will provide
is a very energy conscious system, which will contribute to your green
The units take up very little space and are suitable for use in new or
refurbishment projects (renovations/transformation). The units are
BENG calculation
BENG stands for Nearly Zero Energy Buildings and is applicable since
01-01-2021 and did replace the EPC calculation. The BENG calculation
is required for applying for a new building environmental permit and
calculate the Energy Performance component.
The energy performance of a building is determined with the new
determination method NTA 8800.
Technical information
come into contact with the insulating material and the units do have
supply and return spigots. The supply and return air run synchronously
with each other and ensure air balance in the apartment. Two versions of
the CERA system are available: the one-zone system (CERA-1) and the
two-zone system (CERA-2).
a specially-designed servo-actuated 3-way valve that directs air to the
main zones & the sub zones depending on the need.
The CERA PLUS system can be connected to several CO
2
sensors for
several bedrooms and/or other rooms. The highest CO
2
value measured
will be used in the air volume calculation. The CERA PLUS system is
available for the CERA-1 (up to 5 sensors) and the CERA-2 (up to 6
sensors).
The units and the system are not suitable for direct connection to
a motorless or motorised kitchen hood.
TYPE
CERA-1 | CERA-2
CERA-1 | 1 zone system
CERA-2 | 2 zone system
CERA-1 | 1 zone system

6© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA units | type NXOJOOB
Technical information & delivery format
TYPE
CERA-1 | CERA-2
Technical information
Construction:
- Unit casing: single wall, air-thight construction made of galvanized
sheet steel (non spiral), internally insulated with 13 mm MS30UL
- Duct-sleeve connections suitable for DIN 24 145 or DIN 24 146.
- The units feature three mounting brackets with slotted holes.
Damper:
- Damper blade made of galvanized sheet steel, sandwich construction
of twin blade and neoprene gasket (low leakage).
- Damper shaft: aluminium, ø12 mm with self lubricating
Nylon bearings.
Motorised air side 3-way valve:
- The CERA-2 unit features a specially-designed 3-way air valve
made of steel, sandwich construction and neoprene gaskets for
low air leakage.
Flo-Cross
®
Flo-Cross®
Flo-Cross
:
®
®
®
made of extruded aluminium.
Controls:
- The units feature a DDC BACnet
®
controller.
The wiring to the switches and sensors in the apartment, which has
the controller.
- Internal wiring including power supply cable + plug (halogen free).
- The controller is supplied with dedicated CERA-1 or CERA-2
software.
- Upon request, the system can be set up and remotely controlled.
It is recommended to opt for the optional remote setup and monitoring,
please contact our Technical Advisors for additional information.
Delivery format
- The CERA unit will be supplied with dust caps over the spigots.
Applying these dust caps is done to prevent any construction waste in
the units or to prevent unnecessary draft in high-rise buildings as much
as possible.
- Plug & play units equipped with CERA software.
and pre-calibrated. The calibration data is mentioned on a
product sticker.
- This product sticker also features required housing information
(e.g. block, home and house numbers).
- All controls will be mounted, as standard, on the right hand side
requested. The unit cover is provided with a sticker indicating the
- Left-hand versions of the units available upon request.
- CERA-2 unit divides the air supply into 2 zones; the left connection
connects to the living zone by default.
- I/O connector for CERA plus variant: optional delivery possible
(surcharge) If you have any questions, please contact our technical
advisors.
CERA unit seal colour codes:
Orange seal:
Status: factory setting
CERA unit ready for installation
(The CERA unit is delivered with an orange seal)
Green seal:
Status: after commissioning
CERA unit ready for operation
(Green seal is in the CERA unit on delivery)
Blue seal:
Status: after service/maintenance
Maintenance has been performed
on the CERA unit

7
© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA units | type NXOJOOB
Specifi cation
TYPE
CERA-1 | CERA-2
Example CERA-1
:
CERA units for CO
2
controlled ventilation for stacked housing, made
of galvanized sheet steel. Casing leakage EN 1751 and duct-sleeve
connections suitable for DIN 24 145 or DIN 24 146.
Units provided with double skin, oval shaped damper blades with
neoprene gaskets and damper shafts made of aluminium with self
®
2x12 points
®2x12 points
®
accuracy even with irregular duct approach.
Units supplied with DDC controllers which correspond to BACnet
®
- Increased max. air volume: 253 m
3
/h
- Max. volume: 180 m
3
/h
- Minimum air volume: 65 m
3
/h
- Unit size: 125 mm / connections: 160 mm
-
s
: 42 Pa
- Max. discharge sound index: NC 25 at a pressure drop of 150 Pa
- Max. radiated sound index
: < NC 20
at a pressure drop of 150 Pa
Manufacturer: Barcol-Air
Ordering example:
type – model – connection = NXOJOOB-125R-CERA1
CERA-1
CERA-2
CERA-2

8© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
Installation drawing type NXOJOOB | CERA-1
Remark:
CERA units | type NXOJOOB
Assembly and installation intructions
The CERA units shall be installed with 3 no. bolts/screws according to
the following installation drawing.
Wall plugs and screws are not supplied. Good quality wall plugs and
screws must be used. The weights of the units are mentioned on
page 9 (CERA-1) and page 13 (CERA-2).
The required diagrams are available upon request.
Point of attention:
- High mechanical stresses in the CERA unit casing must be avoided
as these may cause damage to the structure.
- The CERA unit must never be twisted as this could have a negative
impact on the operation of the damper valves.
- Built-in controller components, electronics and measuring tubes
must be accessible at all times; control equipment is mounted on
- A power supply point, wall socket, must be present at the CERA unit.
The unit is standard equipped with a 1.5 meter power cable with
a plug.
- After installation and adjustment, the unit must be fused. (see page 6).
Recommendation:
should take into account the lowest possible resistance in the total duct
system. The system pressure for the operation of the CERA units
should be a minimum of 100-150 Pa. The secondary resistance
(after the CERA unit) should be as low as possible, preferably
<35 Pa.
side and at least 1.0 meter downstream.
units, it is recommended to have communication cable between the
CERA units. In this way, the CERA units can be accessed from
1 central point.
TYPE
CERA-1 | CERA-2
E
=
A
+
75
2x M6 bout
1x borgschroef
=
Return
Supply
2x M6 bolt
1x locking screw

9
© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
TYPE CERA-1
CERA-1 | type NXOJOOB
Dimensions
Dimensions and weight CERA-1
125 160 200
A 432 432 432
B 410 410 490
C 265 293 333
ØD 158 158 198
E 350 350 430
F 100 100 120
G 210 210 250
Kg 14,4 14,8 17,0
Model
CERA‐1
Remarks dimensions:
1. All dimensions are in mm.
2. Other dimensions available on request.
Home side
Shaft side
Type NXOJOOB-160
L
CERA-1
NXOJOOB-200
L
CERA-1
Type NXOJOOB-160
R
CERA-1
NXOJOOB-200
R
CERA-1
Type NXOJOOB-125
L
CERA-1
Type NXOJOOB-125
R
CERA-1
Shaft side
Shaft side
Shaft side
Home side
Home side
Home side

10 © 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
1. Sound data is determined in a reverberation
room at an independent sound laboratory,
according to ISO 3741 en ISO 5135
standards.
2. Lw/Oct. (re. 1pW) are sound power levels
for discharge and radiated sound. Values
< 17 dB are indicated by “-“.
3. The values for insertion loss L
w
do not
include end reflection.
4. dB(A), NC and NR index values are sound
pressure levels. Sound pressure levels
< 20 are indicated by “--“.
5. The sound pressure levels for discharge
sound include the values for an acoustic
hose in accordance with table 1.
6. Lp values are including a room absorption
of 10 dB/Oct.
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
m/s l/s CFM m³/h Pa
2 23 50 84 5 63 53 48 44 33 25 21 ‐‐57 49 43 35 29 18 ‐‐‐29 19 ‐‐‐‐‐‐‐
4 47 99 168 20 65 57 51 49 40 31 25 ‐‐63 55 48 42 36 27 22 ‐‐32 27 22 21 ‐‐‐‐‐
6 70 149 253 42 67 59 53 51 44 35 27 ‐20 67 58 51 46 40 32 26 ‐21 34 32 27 24 19 ‐‐‐‐
8 94 198 337 71 68 60 55 53 47 38 28 ‐22 70 61 53 49 43 36 29 22 24 35 35 30 27 22 17 22 ‐‐
10 117 248 421 108 X X X X X X X XXXXXXXXXXXXXXXXXXXX
2 39 82 139 2 62 49 45 39 30 20 ‐‐‐49 45 43 35 27 17 ‐‐‐27
‐‐‐‐‐‐‐‐
4 77 164 279 8 68 57 53 49 40 32 26 ‐22 58 54 50 44 37 29 20 ‐‐33 27 24 22
‐‐‐‐‐
6 116 246 418 18 71 62 58 54 46 39 30 24 26 64 59 55 49 43 36 26 ‐‐36 34 31 27 21 19 23
‐‐
8 155 328 558 30 74 65 61 58 50 44 33 27 28 68 63 58 53 47 41 29 20 23 38 39 36 31 25 23 27
‐‐
10 194 410 697 46 76 68 63 61 53 47 36 29 31 71 66 60 56 50 45 32 24 27 40 43 39 34 28 25 30
‐‐
2 61 129 219 1 54 48 44 39 31 21 ‐‐‐52 45 40 34 30 22 ‐‐‐21
‐‐‐‐‐‐‐‐
4 122 258 439 4 61 56 53 49 41 33 23 ‐‐56 51 45 39 34 27 ‐‐‐27 26 22 21
‐‐‐‐‐
6 183 388 658 9 66 61 58 54 48 40 28 ‐22 59 54 48 42 37 30 ‐‐‐30 32 30 27 21 19 22
‐‐
8 244 517 878 16 69 65 62 58 52 45 32 24 26 61 56 50 45 39 32 22 ‐‐33 37 35 31 25 22 26
‐‐
10 305 646 1097 25 71 67 64 62 55 48 35 27 30 62 58 52 46 40 33 23 ‐‐34 41 39 34 28 25 30
‐‐
dB(A)
NC
NR
125
160
Model
Data referring to inlet‐spigot
min.
ΔPs
Discharge sound (supply) Discharge sound (return)
200
Radiated sound
Velocity
Air Volume
Lw in dB/Oct. (re 1pW) Lp values
dB(A)
NC
NR
dB dB dB
Lw in dB/Oct. (re 1pW) Lp values Lw in dB/Oct. (re 1pW) Lp values
dB(A)
NC
NR
TYPE CERA-1
Sound data (pressure drop ∆ 100 Pa)
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
m/s l/s CFM m³/h Pa
2 23 50 84 5 64 56 51 47 38 31 24 ‐‐57 51 46 40 35 23 ‐‐‐30 20 ‐18 ‐‐‐‐‐
4 47 99 168 20 69 61 56 53 45 37 29 22 23 66 58 52 46 41 31 25 ‐‐35 29 24 24 19 ‐‐‐‐
6 70 149 253 42 72 64 58 56 49 41 32 25 27 71 62 55 50 44 36 29 23 25 37 34 29 27 23 19 22 ‐‐
8 94 198 337 71 74 66 60 59 52 44 34 28 29 74 65 57 52 47 40 33 27 29 39 37 33 30 25 22 25 ‐‐
10 117 248 421 108 76 68 61 61 54 46 36 30 31 77 67 59 54 49 42 35 31 32 41 40 36 32 28 23 28 ‐‐
2 39 82 139 2 63 52 48 42 35 26 22 ‐‐51 47 45 39 34 25 ‐‐‐29
‐‐‐‐‐‐‐‐
4 77 164 279 8 70 60 56 51 44 36 29 22 24 61 56 52 47 42 34 23 ‐‐34 27 25 23 19
‐‐‐‐
6 116 246 418 18 73 65 60 56 50 43 33 26 28 66 62 57 52 46 40 28 ‐21 37 34 31 28 24 21 24
‐‐
8 155 328 558 30 76 68 64 60 54 47 36 30 31 70 65 60 55 49 44 32 23 25 39 39 36 32 28 25 28
‐‐
10 194 410 697 46 78 71 66 63 57 50 38 32 33 73 68 63 57 52 47 34 26 28 40 42 40 35 30 28 31
‐‐
2 61 129 219 1 57 52 46 41 36 27 ‐‐‐52 46 43 38 35 28 ‐‐‐23
‐‐‐‐‐‐‐‐
4 122 258 439 4 64 59 55 51 46 37 26 ‐‐58 53 49 44 39 33 ‐‐‐29 26 23 22 19
‐‐‐‐
6 183 388 658 9 68 64 60 56 51 43 31 23 25 62 57 52 47 42 35 23 ‐‐32 32 30 27 24 21 23
‐‐
8 244 517 878 16 72 67 64 60 55 48 35 27 29 65 60 54 49 43 37 26 ‐‐34 36 35 31 28 24 27
‐‐
10 305 646 1097 25 74 69 66 63 58 51 37 30 32 67 62 56 50 45 39 28 ‐20 36 40 39 34 31 27 30
‐‐
Radiated sound
Lw in dB/Oct. (re 1pW) Lp values
NR
dB(A)
NC
NR
125
Model
Data referring to inlet‐spigot
min.
ΔPs
Discharge sound (supply) Discharge sound (return)
Velocity
Air Volume
Lw in dB/Oct. (re 1pW) Lp values Lw in dB/Oct. (re 1pW) Lp values
dB(A)
NC
160
200
dB(A)
NC
NR
dB dB dB
Sound data (pressure drop ∆ 150 Pa)
Additional sound absorption of Sonodec acoustic hose (1 meter)
Hz 125 250 500 1000 2000 4000
dB 17 22 22 27 19 14
7.
∆
p
s
is the static pressure loss in the CERA
sis the static pressure loss in the CERA
s
unit with the damper fully open.
8. Where an “X” is shown in the table,
the unit’s own resistance is > 100 Pa,
which means sound levels at 100 Pa
are not available.
9. For non standard applications and/or
selections please contact our technical staff .
CERA-1 | type NXOJOOB
Performance data

11
© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA-1 | type NXOJOOB
Controls sequence of operation (standard)
TYPE CERA-1
CERA - 1
CERA
Living room KitchenBathroom
10 10
Jung 534 EU
BACnet bus BACnet bus
sign al cable
sign al cable
sign al cable
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
10 10
Jung 534 EU
push-button switchCO₂sensorCERA-1 Unitpush-button switch
CERA1+
CERA - 1
10 10
Jung 534 EU
BACnet bus BACnet bus
10 10
Jung 534 EU
CERA-1 + Unit
+module
Living room KitchenBathroom
push-button switch
sign al cable
sign al cable
sign al cable
sign al cable
sign al cable
sign al cable
sign al cable
Power Outlet
230Vac
Power Outlet
230Vac
CO₂sensor
CO₂sensorCO₂sensorCO₂sensor
CO₂sensor
Bedroom - 2 Bedroom - 3 Bedroom - 4Master Bedroom
push-button switch
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
Remark:
Wiring between the CERA-1 unit and the sensor(s)/switch(es) by third party.
(wiring by third party)
(wiring by third party)
(
CERA-S-TCO2
)

12 © 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
Sequence of operation of the CERA-1 one-zone system (standard model):
•
®
®
®
•
A central AHU provides fresh air and ensures static pressure in the system. The distribution of air in the home will be determined by
The central AHU unit must function 24/7.
•
In normal operation, the measured CO
2
value (living room) will be used to calculate the required air volume between a minimum air volume
2
value
800 ppm, then the air volume will be equal
•
By actuating the pulse switches (kitchen/bathroom) with LED feedback, the air volume in the home can be temporarily set to an increased or
reduced mode (night/sleep mode).
•
automatically return to the demand-driven CO
2
control.
•
2
reading. After
13 hours (night/sleep setting), the control sequence will automatically return to normal operation.
•
•
CERA-1 is also suitable for integration with the bathroom light; the CERA-1 unit will automatically switch to the increased mode after a 5-minute
•
•
CERA-1 PLUS is available for monitoring CO
2
levels in multiple bedrooms. A
CERA-S-TCO2
CO
2
sensor can be installed in a total of 4 bedrooms
and the living room. The highest CO
2
value measured will be used in the calculation of the desired air volume.
•
Optionally a humidity sensor can be used in the bathroom/bedroom, which ensures that the CERA unit automatically switches to elevated
increased mode the moment the humidity rises above a preset percentage. As standard for this type CERA-KLH100-HD-R5V sensor a percentage
TYPE CERA-1
CERA-1 | type NXOJOOB
Control sequence of operation (standard)
CO2-sensor
Type: CERA-S-TCO2
Hygrostat
Type: CERA-KLH100-HD-R5V

13
© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
125 160 200
A432 432 432
B668 747 907
C265 301 341
ØD 158 158 198
E608 687 847
F100 100 120
G260 330 410
H208 208 248
I230 274 334
J338 373 453
Kx 109 129
Lx 118 138
Kg 21,2 23,4 29,2
Model
CERA‐2
Dimensions en weight CERA-2
CERA-2 | type NXOJOOB
Dimensions
TYPE CERA-2
Remarks dimensions:
1. All dimensions are in mm.
2. Other dimensions available on request.
Home side
Shaft side
Type NXOJOOB-125
L
CERA-2
Type NXOJOOB-125
R
CERA-2
Type NXOJOOB-160
L
CERA-2
NXOJOOB-200
L
CERA-2
Type NXOJOOB-160
R
CERA-2
NXOJOOB-200
R
CERA-2
Home side
Shaft side
Shaft side
Shaft side
Home side
Home side

14 © 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA-2 | type NXOJOOB
Performance data
TYPE CERA-2
1. Sound data is determined in a reverberation
room at an independent sound laboratory,
according to ISO 3741 en ISO 5135
standards.
2. Lw/Oct. (re. 1pW) are sound power levels
for discharge and radiated sound. Values
< 17 dB are indicated by “-“.
3. The values for insertion loss L
w
do not
include end reflection.
4. dB(A), NC and NR index values are sound
pressure levels. Sound pressure levels
< 20 are indicated by “--“.
5. The sound pressure levels for discharge
sound include the values for an acoustic
hose in accordance with table 1.
6. Lp values are including a room absorption
of 10 dB/Oct.
7.
∆
p
s
is the static pressure loss in the CERA
sis the static pressure loss in the CERA
s
unit with the damper fully open.
8. Where an “X” is shown in the table,
the unit’s own resistance is > 100 Pa,
which means sound levels at 100 Pa
are not available.
9. For non standard applications and/or
selections please contact our technical staff .
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
m/s l/s CFM m³/h Pa
2 23 50 84 10 63 57 52 41 29 26 23 ‐‐57 49 43 35 29 18 ‐‐‐29 19 ‐‐‐‐‐‐‐
4 47 99 168 29 66 60 55 46 35 31 26 ‐‐63 55 48 42 36 27 22 ‐‐32 27 22 21 ‐‐‐‐‐
6 70 149 253 56 68 61 56 49 39 34 28 20 22 67 58 51 46 40 32 26 ‐21 34 32 27 24 19 ‐‐‐‐
8 94 198 337 88 69 62 57 50 42 36 29 22 24 70 61 53 49 43 36 29 22 24 35 35 30 27 22 17 22 ‐‐
10 117 248 421 125 X X X X X X X XXXXXXXXXXXXXXXXXXXX
2 39 82 139 5 62 59 51 43 36 34 23 ‐‐49 45 43 35 27 17 ‐‐‐27 24 ‐‐‐17
‐‐‐
4 77 164 279 18 66 63 56 50 43 39 28 ‐21 58 54 50 44 37 29 20 ‐‐32 31 26 22 17 20
‐‐‐
6 116 246 418 41 69 65 58 53 47 43 30 22 24 64 59 55 49 43 36 26 ‐‐34 36 31 26 22 22 23
‐‐
8 155 328 558 74 71 66 60 56 50 45 32 24 26 68 63 58 53 47 41 29 20 23 36 40 35 29 25 24 27
‐‐
10 194 410 697 116 X X X X X X X XXXXXXXXXXXXXXXXXXXX
2 61 129 219 6 62 55 50 43 39 32 22 ‐‐52 45 40 34 30 22 ‐‐‐27 20
‐‐‐‐‐‐‐
4 122 258 439 22 67 61 54 49 45 39 27 ‐21 56 51 45 39 34 27 ‐‐‐32 30 24 21 19 19
‐‐‐
6 183 388 658 50 70 65 57 52 48 42 31 22 24 59 54 48 42 37 30 ‐‐‐34 36 29 24 22 21 22
‐‐
8 244 517 878 89 72 67 59 54 50 45 33 25 27 61 56 50 45 39 32 22 ‐‐36 39 33 27 24 22 25
‐‐
10 305 646 1097 139 XXXXXXXXXXXXXXXXXXXXXXXXXXX
Lw in dB/Oct. (re 1pW) Lw in dB/Oct. (re 1pW) Lw in dB/Oct. (re 1pW)
Model
Data referring to inlet‐spigot
min.
ΔPs
Discharge sound (supply) Discharge sound (return) Radiated sound
Velocity
Air Volume
Lp values Lp values Lp values
dB(A)
NC
NR
dB(A)
NC
NR
dB(A)
NC
NR
dB dB dB
125
200
160
Sound data (pressure drop ∆ 100 Pa)
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
m/s l/s CFM m³/h Pa
2 23 50 84 10 65 60 57 45 33 31 26 ‐20 57 51 46 40 35 23 ‐‐‐30 20 ‐18 ‐‐‐‐‐
4 47 99 168 29 70 64 60 50 40 36 30 22 24 66 58 52 46 41 31 25 ‐‐35 29 24 24 19 ‐‐‐‐
6 70 149 253 56 73 66 61 53 44 39 33 26 28 71 62 55 50 44 36 29 23 25 37 34 29 27 23 19 22 ‐‐
8 94 198 337 88 75 68 63 56 46 42 35 29 30 74 65 57 52 47 40 33 27 29 39 37 33 30 25 22 25 ‐‐
10 117 248 421 125 77 69 64 57 48 43 36 31 32 77 67 59 54 49 42 35 31 32 41 40 36 32 28 23 28 ‐‐
2 39 82 139 5 64 63 56 47 40 39 27 ‐20 51 47 45 39 34 25 ‐‐‐30 25 20 18 ‐18
‐‐‐
4 77 164 279 18 70 66 60 53 47 44 32 23 25 61 56 52 47 42 34 23 ‐‐35 32 28 24 21 22 21
‐‐
6 116 246 418 41 74 69 62 57 51 47 34 27 28 66 62 57 52 46 40 28 ‐21 37 37 33 28 24 24 25
‐‐
8 155 328 558 74 76 70 64 59 53 49 37 30 31 70 65 60 55 49 44 32 23 25 39 40 37 31 27 26 28
‐‐
10 194 410 697 116 78 71 65 61 55 50 38 32 33 73 68 63 57 52 47 34 26 28 40 43 39 33 29 28 30
‐‐
2 61 129 219 6 65 60 54 47 44 39 26 ‐20 52 46 43 38 35 28 ‐‐‐30 22 18 18 ‐18
‐‐‐
4 122 258 439 22 70 66 59 52 49 44 31 23 25 58 53 49 44 39 33 ‐‐‐34 31 26 23 22 22 20
‐‐
6 183 388 658 50 74 69 61 56 52 47 34 27 28 62 57 52 47 42 35 23 ‐‐37 37 31 26 25 24 24
‐‐
8 244 517 878 89 76 71 63 58 54 49 37 30 31 65 60 54 49 43 37 26 ‐‐38 40 35 29 27 26 27
‐‐
10 305 646 1097 139 78 73 64 59 56 51 38 32 33 67 62 56 50 45 39 28 ‐20 39 43 37 30 29 27 29
‐‐
160
Lp values
dB(A)
NC
NR
dB(A)
NC
NR
dB(A)
NC
NR
dB dB dB
200
125
Model
Data referring to inlet‐spigot
min.
ΔPs
Discharge sound (supply) Discharge sound (return) Radiated sound
Velocity
Air Volume
Lw in dB/Oct. (re 1pW) Lp values Lw in dB/Oct. (re 1pW) Lp values Lw in dB/Oct. (re 1pW)
Sound data (pressure drop ∆ 150 Pa)
Additional sound absorption of Sonodec acoustic hose (1 meter)
Hz 125 250 500 1000 2000 4000
dB 17 22 22 27 19 14

15
© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA-2 | type NXOJOOB
Controls sequence of operation (standard)
TYPE CERA-2
Remark:
Wiring between the CERA-2 unit and the sensor(s)/switch(es) by third party.
(wiring by third party)
(wiring by third party)
(
CERA-S-TCO2
)
(
CERA-S-TCO2
)
CERA2+
CERA - 2
10 10
Jung 534 EU
BACnet bus BACnet bus
10 10
Jung 534 EU
CERA2+ Unit
+module
Dining Room
CERA - 2
CERA - 2
Living room KitchenBathroom
10 10
Jung 534 EU
BACnet bus BACnet bus
sign al cable
sign al cable
sign al cable
2
2
2
2
-
-
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
CERA
10 10
Jung 534 EU
push-button switchCO
₂
sensorCERA-2 Unit
push-button switch
Bedroom
sign al cable
CO
₂
sensor
Master Bedroom
Bedroom - 2 Bedroom - 3 Bedroom - 4
sign al cable
sign al cable
sign al cable
sign al cable
sign al cable
sign al cable
sign al cable
sign al cable
push-button switch
CO₂sensor
CO₂sensor
push-button switch
CO₂sensor CO₂sensor CO₂sensor CO₂sensor
Bathroom Living room Kitchen
Power Outlet
230Vac
Power Outlet
230Vac
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)
24V
0V
OP1
OP2
OP3
0V
24 V ~
0-5 V = 0-2000 ppm
0 V
0-5 V = 0…+40° C
N.A.
CERA-S-TCO2
N.A. (Optie RV)

16 © 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
Sequence of operation of the CERA-2 two-zone system (standard model):
•
The CERA-2 unit features two supply connections on the home side and one return duct with built-in air valves to control the air volume.
®
®
®
Type CERA-2 measures the CO
2
content in two
zones (living room and bedroom). A specially-designed, motorised-sided 3-way air valve controls the supply air between the two zones.
•
A central AHU unit provides fresh air and ensures static pressure in the system. The distribution of air in the home will be determined by
•
In normal operation, the measured CO
2
value (living room) will be used to calculate the required air volume between a minimum air volume
2
value
800 ppm, then the air volume will be equal
zones.
•
By actuating the pulse switches (kitchen/bathroom) with LED feedback, the air volume in the home can be temporarily set to an increased or
reduced mode (night/sleep mode).
•
In increased mode, the required air volume will be maximum regardless of the measured CO
2
value; it will be equally (50/50) divided between the
two zones. After 60 minutes, the control sequence will automatically return to the demand-driven CO
2
control.
•
2
reading. After
13 hours (night/sleep setting), the control sequence will automatically return to normal operation.
•
•
CERA-2 is also suitable for integration with the bathroom light; the CERA-2 unit will automatically switch to the increased mode after a 5-minute
•
•
CERA-2 PLUS is available for monitoring CO
2
levels in multiple bedrooms
.
In total, a maximum of two sensors in the living room zone and four
CERA-S-TCO2
CO
2
value will be used in
calculating the required air volume and how it is divided.
•
Optionally a humidity sensor can be used in the bathroom/bedroom, which ensures that the CERA unit automatically switches to elevated
increased mode the moment the humidity rises above a preset percentage. As standard for this type CERA-KLH100-HD-R5V sensor a percentage
CERA-2 | type NXOJOOB
Control sequence of operation (standard)
TYPE CERA-2
CO2-sensor
Type: CERA-S-TCO2
Hygrostat
Type: CERA-KLH100-HD-R5V

17
© 01-2022 | Barcol-Air B.V. | T +31 (0)299 689 300 | www.barcol-air.nl | www.cera-systeem.nl | Changes w/o notice or obligation.
CERA units | type NXOJOOB
CE Declaration of Conformity
TYPE
CERA-1 | CERA-2

BARCOL-AIR |AIR DISTRIBUTION
Cantekoogweg 10-12 - 1442 LG Purmerend, The Netherlands
T+31 (0)299 689 300 | Eexport@barcol-air.nl
OUR TECHNOLOGY | YOUR WELLBEING
WWW.BARCOL-AIR.NL
Table of contents
Other Barcol-Air Fan manuals
Popular Fan manuals by other brands

Salda
Salda RIRS 3500VE-VW EKO 3.0 Technical manual

Westinghouse
Westinghouse ETL-ES-Alta Vista-WH22 owner's manual

Helios
Helios VDD T120 Series Installation and operating instructions

Titus
Titus DVCP Installation and operation manual

LUCCI
LUCCI AIRFUSION BREEZE installation instructions

ZIEHL-ABEGG
ZIEHL-ABEGG FB Series Translation of the original operating instructions