Beko BEKOMAT 33U User guide

EN - english
Instructions for installation and operation
Condensate drain
BEKOMAT®33U / 33U CO (BM33U / BM33UCO)
01-1619

2 BEKOMAT® 33U / 33U CO
Dear customer,
Thank you for deciding in favour of the BEKOMAT®33U / 33U CO condensate drain. Please read the instal-
lation and operating instructions carefully before mounting and starting up the BEKOMAT®33U / 33U CO ,
and follow our directions. Perfect functioning of the BEKOMAT®33U / 33U CO , and thus reliable conden-
sate discharge, can only be guaranteed when the provisions and notes stipulated here are strictly adhered
to.

BEKOMAT® 33U / 33U CO 3
1 Pictograms and symbols ...................................................................................................................4
2 Safety instructions.............................................................................................................................4
3 Proper use........................................................................................................................................6
4 Exclusion from the scope of application.............................................................................................6
5 Technical data ..................................................................................................................................7
6 Electrical data ...................................................................................................................................8
7 Dimension drawing............................................................................................................................9
8 Climate zones and performance data ..............................................................................................10
9 Function..........................................................................................................................................11
10 Installation ......................................................................................................................................14
11 Electrical installation........................................................................................................................17
12 Control and maintenance ................................................................................................................20
13 Troubleshooting and fault elimination ..............................................................................................26
14 Elements and components..............................................................................................................27
15 Recommended spare parts .............................................................................................................28
16 Accessories ....................................................................................................................................28
17 Declaration of conformity.................................................................................................................30

Pictograms and symbols
4 BEKOMAT® 33U / 33U CO
Pos: 1 /Beko Technische Dokume ntat ion/Überschriften/ 1/Piktogr amme und Symbole @ 1\ mod_1290773595840_ 2901.docx @ 20524 @ 1 @ 1
1Pictograms and symbols
Pos: 2 / Beko TechnischeDokume ntat ion/Pikt ogramme/ Anleitung beachten blau @ 0\ mod_12132 683002 55_2901. docx @ 8336 @ @ 1
Observe the installation and operating instructions
Pos: 3 /Beko Technische Dokume ntat ion/Piktogramm e/Anle itung beachten s/w Typenschild@ 1\m od_12907 7218014 2_2901.docx @ 20491 @ @ 1
Observe the installation and operating instructions
(on the type plate)
Pos: 4 /Beko Technische Dokume nt at ion/Pikt ogr amm e/ G efahr War nung Vorsicht s/ w @ 0\ m od_121326568517 4_2901.docx @ 8260 @ @ 1
General danger symbol (danger, warning, caution)
Pos: 5 /Beko Technische Dokume nt at ion/Pikt ogr amm e/ G +W+V Netzspannung s/w @ 0\m od_121326619370 1_2901.docx @ 8298 @ @ 1
General danger symbol (danger, warning, caution) for supply voltage and supply voltage-carry-
ing plant components
Pos: 6 /Beko Technische Dokume nt at ion/Überschrift en/ 1/ Sicherhe itshin weise @ 0\m od_118363760926 1_2901.docx @ 5367@ 1 @ 1
2 Safety instructions
Pos: 7 /Beko Technische Dokume ntat ion/G lobale Text e/A llgeme iner Hin weis BM @ 0\ mod_118361573731 3_2901.docx @ 4006 @ @ 1
Pos: 8 /Beko Technische Dokume ntat ion/Sicherhe it/HinweisAn le itung BEKO (männl. Name) @ 0\ mod_1184147787557_2901.docx @ 5760@ @ 1
Please check whether or not these instructions correspond to the device type.
Adhere to all advice given in these operating instructions. They include essential information
which must be observed during the installation, operation and maintenance. Therefore it is im-
perative for the service technician and the responsible operator / technical staff to read these
operating instructions prior to installation, start-up and maintenance.
The operating instructions must be accessible at any time at the place of application of the
BEKOMAT®33U / 33U CO .
In addition to these operating instructions, local or national regulations must be complied with,
if necessary.
Make sure that the BEKOMAT®33U / 33U CO is operated only within the permissible limit val-
ues indicated on the type plate. Any deviation involves a risk for persons and materials, and
may result in malfunction and service failures.
If you have any queries regarding these installation- and operating instructions, please contact
BEKO TECHNOLOGIES GMBH.
Pos: 9 /Beko Technische Dokume nt at ion/Sicher he it/ G ef ahr Druckluft @ 0\ m od_118414814385 4_2901.docx @ 5778@ @ 1
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping com-
pressed air or through bursting plant components or plant components which are not
secured.
Pos: 10 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Druckl uft BM @ 0\m od_1184148284291_290 1. docx @ 5814@ @ 1
Measures:
• Do not exceed the maximum operating pressure (see type plate).
• Only carry out service measures when the system is pressureless.
•Use pressure-resistant installation material only.
• The feed pipe must be tubed firmly. Discharge pipe: short, fixed pressure hose onto pressure-resistant
pipe.
• Make sure that persons or objects cannot be hit by condensate or escaping compressed air.
Pos: 11 /Beko Technische Dok um entat ion/Sich er heit/G ef ahr Net zspannung 1 s/w @ 0\m od_1184148186948 _2901.docx @ 5796@ @ 1

Safety instructions
BEKOMAT® 33U / 33U CO 5
Danger!
Supply voltage!
There is the risk of an electric shock involving injury or death when coming into contact
with non-insulated components carrying supply voltage.
Pos: 12 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Netzspann ung BM 31U/32U/33 U @ 7\m od_13904671 97804_2 901.docx @ 38043@ @ 1
Measures:
• During electric installations, all regulations in force need to be adhered to (e.g. VDE 0100 / IEC 60364).
•When the control unit is open, service and installation works must only be undertaken when the
system is deactivated.
• The removed control unit has no IP degree of protection.
• All types of electrical works must be carried out by authorised and qualified personnel only.
Pos: 13 /Beko Technische Dok um entat ion/Sich er heit/Sicherhe itshin weis e, weiter e BM (nicht Ex, nicht I F)@ 0\mod_1183616103 770_29 01.docx @ 4011 @ @ 1
Further safety instructions:
• For installation and operation, the national regulations and safety codes in force must also be adhered
to.
• Do not use the BEKOMAT®33U / 33U CO in hazardous areas.
• Regarding the inlet screw joints, excessive tightening forces must be avoided. This applies in particular
to conical screw joints.
• The BEKOMAT®33U / 33U CO will only function when voltage is applied.
• Do not use the test button for permanent drainage.
• Use genuine spare parts only. This is imperative to ensure perfect functioning.
Pos: 14 /Beko Technische Dok um entat ion/Sich er heit/Zusatz Sicherhe itshin weise BM3 3/ BM33U @ 0\m od_1231926 887620_2901.docx @ 12830 @ @ 1
Additional advice:
• During installation, use the spanner flat at the feed pipe (wrench size SW28 + 34) as a back rest.
• The service unit must not be dismantled.
Pos: 15 /Beko Technische Dok um entat ion/Sich er heit/Vorsicht Fehlfunkti on @ 0\m od_121437809 6290_2901. docx @ 9360 @ @ 1
Caution!
Malfunction during operation!
Through incorrect installation and poor maintenance, malfunction may occur at the
BEKOMAT .
Condensate which is not discharged may cause damage to plants and in production
processes.
Pos: 16 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Feh lfunkt ionen BM @ 0\ m od_12143784 34025_2901. docx @ 9379 @ @ 1
r
Measures:
• Condensate drainage which is reliable in performance directly optimises the compressed-air quality.
• To prevent damage and breakdowns, it is imperative to observe the following:
• Exact compliance with the specifications of use and with the performance parameters of the
BEKOMAT, in connection with the case of application (see "Proper use" section).
• Exact compliance with the installation- and operation instructions in this manual.
• Regular maintenance and control of the BEKOMAT in accordance with the instructions in this oper-
ating manual.
Pos: 17 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Proper use
6 BEKOMAT® 33U / 33U CO
Pos: 18 /Beko Technische Dok um entat ion/Überschr ift en/1/ Bestimmungsgemäße Ver wendung @ 0\ m od_1183637706293_29 01.docx @ 5385 @ 1 @ 1
3 Proper use
Pos: 19 /Beko Technische Dok um entat ion/Bestimmungsgemäß e Verwend ung/BE KOM AT/Bestimmung. Verwend. BM 31/ 32/33 +U @ 0\m od_1213345398718_290 1. docx @ 8818 @ @ 1
• The BEKOMAT®33U / 33U CO is an electronically level-controlled condensate drain for compressed-air
plants.
• The device is employed within the permissible performance parameters (see "Technical data").
• The BEKOMAT®33U / 33U CO is able to drain condensate under operating pressure from the plant
components virtually without compressed-air loss.
• For its function, the BEKOMAT®33U / 33U CO requires an supply voltage and an operating pressure
(see "Technical data").
• As far as the employment in plants with increased demands on compressed air is concerned (food in-
dustry, medical technology, laboratory equipment, special processes etc.), the operator must decide on
measures for the monitoring of the compressed-air quality. These have an effect on the safety of the
subsequent processes and may prevent damage to persons and plants.
• It is the task of the operator to ensure that the indicated conditions are met during the entire operating
time.
Pos: 20 /Beko TechnischeDok umentat ion/Bestimmungsgemäß e Verwend ung/BEKOM AT/Hinwe is Anwendung BM 33 für CO2- Anwendg. @ 0\ mod_1242828 875874_ 2901.docx @ 14910 @ @ 1
• For the employment in CO2plants, a BEKOMAT with a CO specification must be used.
Pos: 21 /Beko Technische Dok um entat ion/Überschr ift en/1/ Ausschluss vom Anwendu ngsbereich @ 0\ m od_1236003439359_29 01.docx @ 13710 @ 1 @ 1
4 Exclusion from the scope of application
Pos: 22 /Beko TechnischeDok umentat ion/Bestimmungsgemäß e Verwend ung/BEKOM AT/Aussch lußAn wendun g BM 31/ 32/33 +U@ 0\ mod_123600383751 1_2901.docx @ 13737 @ @ 1
• The BEKOMAT®33U / 33U CO as a condensate drain alone cannot guarantee a defined compressed-
air quality, for this purpose, other additional technical devices are required.
• BEKOMAT®33U / 33U CO is not suitable for use in plants carrying vacuum or atmospheric ambient
pressure or in ex-areas.
• The BEKOMAT®33U / 33U CO must not be exposed to permanent direct solar or thermal radiation.
• The BEKOMAT®33U / 33U CO must not be installed and operated in areas with an aggressive atmos-
phere.
Pos: 23 /Beko Technische Dok um entat ion/Bestimmungsgemäß e Verwend ung/BE KOM AT/Ausschluß An wendun g BM nicht f ür f r ostgef ährdet eBereiche ( Zusatz) @ 0\m od_1216106439206_ 2901.docx @ 11234@ @ 1
• The BEKOMAT®33U / 33U CO is not heatable and, therefore, not suitable for the use in areas where
frost is likely to occur.
Pos: 24 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Technical data
BEKOMAT® 33U / 33U CO 7
Pos: 25 /Beko Technische Dok um entat ion/Überschr ift en/1/ Technisc he Daten @ 0\ m od_11843295 70967_2901.docx @ 6058 @ 1 @ 1
5 Technical data
Pos: 26 /Beko Technische Dok um entat ion/Technische Daten/B EKOM AT/Techn. Daten BM 3xU + UC + G O ST ( o. Leistg.) @ 5\mod_1358843578945_290 1.docx @ 30450 @ @ 1
min./max. operating pressure
(see type plate)
0,8...16 bar (12...230 psi)
or
1,2...16 bar (17...230 psi)
min./max. temperature
(see type plate)
+1...+60 °C (+34...+140 °F)
or
+1...+70 °C (+34...+158 °F)
Condensate inflow 3 x G ½ (NPT ½) internal
Condensate outflow G ½ Ø 13 mm hose connector
Condensate oil-contaminated + oil-free
Housing aluminium + plastic, glass fibre-reinforced
Weight (empty) 1,65 kg (3.63 lbs)
This product has been tested to the requirements of CAN/CSA-C22.2 No. 61010-1-12, third edition, includ-
ing a later version of the same standard incorporating the same level of testing requirements.
Pos: 27 /Beko Technische Dok um entat ion/Technische Daten/B EKOM AT/Leistung BM Standard @ 0\m od_1184050 678383 _2901.docx @ 5720@ @ 1
Max. performance for the "blue" climate zone – see also Chapter "Climate zones and performance data"
max. compressor performance 10 m³/min (350 scfm)
max. refrig.-dryer performance 20 m³/min (700 scfm)
max. filter performance 100 m³/min (3500 scfm)
Pos: 28 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Electrical data
8 BEKOMAT® 33U / 33U CO
Pos: 29 /Beko Technische Dok um entat ion/Überschr ift en/1/ Elektr ische D at en @ 0\m od_1183638451371_290 1. docx @ 5601 @ 1 @ 1
6 Electrical data
Pos: 30 /Beko Technische Dok um entat ion/Elektr isch e Daten/BEKOMAT/E lektr ischeD at en BM 32U/33U @ 4\m od_13577374 05732_2901.docx @ 29582 @ @ 1
Supply voltage
(see type plate)
95…240 VAC ±10% (50…60 Hz) /100…125 VDC ±10%
or
24…48 VAC ±10% (50…60 Hz) / 18…72 VDC ±10%
Power consumption P = 0,6 ... 3 VA (W)
Recommended cable-jacket di-
ameter Ø 5,0…10 mm (0,20“…0,39“)
Recommended
wire cross-section
Spring-loaded terminal
(voltage supply/relay)
0,75...1,5 mm² (AWG 16...20)
Recommended
wire cross-section
Screw terminal
(voltage supply)
0,75...2,5 mm² (AWG 14...20)
Recommended
wire cross-section
Spring-loaded terminal
(external test)
0,75...1,5 mm² (AWG 16...20)
Recommended
wire cross-section
Screw terminal
(relay/external test)
0,75...1,5 mm² (AWG 16...20)
Recommended stripping of cable
jacket
(voltage supply/relay)
~ 30 mm (~ 1.18")
Recommended stripping of cable
jacket
(external test)
~ 90 mm (~ 3.54")
Recommended length of the wire
end tube
Spring-loaded terminal
~ 8 mm (~ 0.31 inch)
Recommended length of the wire
end tube
Screw terminal
~ 6 mm (~ 0.24 inch)
Connection data of the potential-
free contact
Switch to load *)
AC: max. 250V / 1A
DC: max. 30V / 1A
Connection data of the potential-
free contact
Switch to low signal *)
min. 5 VDC / 10 mA
Connection data of the external
test contact on the unit side 5 VDC; switching current ≥ 0,5 mA
Protection class IP 67
Overvoltage category
(IEC 61010-1) II
VAC = V alternating current
VDC = V direct current
*) The switching of loads means that the properties of the contact are no longer suitable
for the switching of low signals.
Pos: 31 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Dimension drawing
BEKOMAT® 33U / 33U CO 9
Pos: 32 /Beko Technische Dok um entat ion/Überschr ift en/1M aßzeic hnung @ 0\m od_1183638072605_2901.docx @ 5493 @ 1 @ 1
7 Dimension drawing
Pos: 33 /Beko TechnischeDok umentat ion/Techn ische Daten/ Masszeichnung @ 0\ mod_118456 981528 0_2901.docx @ 6140 @ @ 1
Pos: 34 /Beko TechnischeDok umentat ion/Techn ische Daten/ Masszeichnung Ergänz ungSW @ 1\m od_125015324 4115_2 901.docx @ 15481 @ @ 1
SW = wrench size
Pos: 35 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Climate zones and performance data
10 BEKOMAT® 33U / 33U CO
Pos: 36 /Beko Technische Dok um entat ion/Überschr ift en/1/ Klim az onen und Leistung sdat en @ 0\m od_118363838 5480_2 901.docx @ 5583 @ 1 @ 1
8 Climate zones and performance data
Pos: 37 /Beko TechnischeDok umentat ion/Klimazonen/K lim azon enBM @ 0\ mod_11845734627 96_290 1.docx @ 6180 @ @ 1
Climate zone
Max.
compressor perfor-
mance
m³/min.
Max.
dryer performance
m³/min.
Max. filter performance
m³/min.
green 12 24 120
blue 10 20 100
red 7 14 70
The indicated performance data are based on a moderate climate and apply to Europe, large parts of South-
east Asia, North and South Africa, parts of North and South America (climate zone: blue).
For dry and / or cool climate (climate zone: green) , the following factor applies: performance in the "blue"
climate zone approx. x 1.2
For warm and / or humid climate (tropics; climate zone: red), the following factor applies: performance in the
"blue" climate zone approx. x 0.7
Pos: 38 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Function
BEKOMAT® 33U / 33U CO 11
Pos: 39 /Beko Technische Dok um entat ion/Überschr ift en/1/ Funktion @ 0\ m od_1183637 775808 _2901.docx @ 5403 @ 1 @ 1
9 Function
Pos: 40 /Beko Technische Dok um entat ion/Funktion/B EKOM AT/BM Ableitf unkt ion@ 0\m od_11836180 31702_ 2901.docx @ 4032 @ @ 1
Via the inlet line (1) the condensate flows into the
BEKOMAT®33U / 33U CO and accumulates in the
housing (2).
A capacitively functioning sensor (3) continuously reg-
isters the filling level and relays a signal to the elec-
tronic control as soon as the container is filled.
The pilot valve (4) is activated and the membrane (5)
opens the outlet line to discharge the condensate (6).
When the BEKOMAT®33U / 33U CO is empty, the
outlet line is reclosed tightly in time before unneces-
sary compressed-air losses occur.
Pos: 41 /Beko Technische Dok um entat ion/Funktion/B EKOM AT/BM 32U/33 U LED-Taster-Funktio n @ 4\ m od_1354691493582_29 01.docx @ 29040 @ @ 1

Function
12 BEKOMAT® 33U / 33U CO
At the BEKOMAT®33U / 33U CO, two LEDs indicate
the individual operating states.
When applying supply voltage, the
BEKOMAT®33U / 33U CO carries out a self-test.
Both LEDs are lit for approximately 1 second, subse-
quently, the device changes over to the "ready-to-op-
erate" state.
Ready to operate, voltage is applied.
In the event that the condensate discharge is dis-
turbed, an alarm mode will start which is indicated by
the flashing of the red alarm LED.
Malfunction/alarm.
Test of the valve function (manual drainage): press
and hold the button for approximately 2 s.
Test of the alarm function (see below): press and hold
the button for at least 1 min.
Do not use for permanent drainage.
Pos: 42 /Beko Technische Dok um entat ion/Funktion/B EKOM AT/BM-Al arm m odus ( nicht Vario) @ 0\m od_1185868789656 _2901.docx @ 6850@ @ 1
.
Switching sequence of the valve in the alarm
mode
Alarm mode:
In the event that the condensate discharge is dis-
turbed, the valve opens after a time cycle (approx.
every three seconds) to eliminate the malfunction au-
tomatically. If the malfunction is not eliminated after
one minute, a trouble indication is released:
• The alarm LED flashes.
• The alarm relay switches over (the signal can be
picked off potential-freely).
• The valve opens every four minutes for 7.5 sec-
onds.
• When the malfunction has been eliminated, the
BEKOMAT will switch back automatically into the
normal mode.
Possible trouble sources include:
• Mistakes during installation.
• Dropping below the minimum pressure.
• Excessive accumulation of condensate (excess
load).
• Blocked / obstructed outlet line.
• Extreme amount of dirt particles.
• Frozen pipework.
Trouble indication via a potential-free contact

Function
BEKOMAT® 33U / 33U CO 13
Pos: 43 /Beko Technische Dok um entat ion/Funktion/B EKOM AT/BM 31U/32 U/33U+ VarioAb l.- War t ungsmeldg. akt iv ( nicht 32U FMK + IF) War t ungsint ervall@ 5\m od_1371731964818_29 01.docx @ 31020 @ @ 1
The BEKOMAT®33U / 33U CO releases a mainte-
nance message for a service that is to be carried out.
Depending on the operating mode, a visual mainte-
nance message (service) is activated which signalises
the replacement of the service unit.
The maintenance message is indicated by the flashing
supply voltage-LED "Power".
The maintenance message is released after 2 x 8.760
h or one million switching cycles.
The maintenance signal is released when one of
these two values is reached.
In the event of a power outage or when the energy
supply is deactivated, the status of the timer will be
maintained.
The activities to be carried out regarding maintenance
are described in the chapter entitled "Check and
maintenance".
Prior to the replacement of the service unit, a reset
needs to be carried out. The control unit is released by
actuating the arresting hook. When removed, the
TEST button must be pressed and held for at least
five seconds.
Pos: 44 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Installation
14 BEKOMAT® 33U / 33U CO
Pos: 45 /Beko Technische Dok um entat ion/Überschr ift en/1/ I nst allat ion @ 0\m od_1183637 835418 _2901.docx @ 5421@ 1 @ 1
10 Installation
Pos: 46 /Beko Technische Dok um entat ion/Sich er heit/G ef ahr Druckluft @ 0\ m od_11841481438 54_2901.docx @ 5778 @ @ 1
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping com-
pressed air or through bursting plant components or plant components which are not
secured.
Pos: 47 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Druckl uft BM @ 0\m od_1184148284291_290 1. docx @ 5814@ @ 1
Measures:
• Do not exceed the maximum operating pressure (see type plate).
• Only carry out service measures when the system is pressureless.
•Use pressure-resistant installation material only.
• The feed pipe must be tubed firmly. Discharge pipe: short, fixed pressure hose onto pressure-resistant
pipe.
• Make sure that persons or objects cannot be hit by condensate or escaping compressed air.
Pos: 48 /Beko Technische Dok um entat ion/Sich er heit/Vorsicht Fehlfunkti on @ 0\m od_121437809 6290_2901. docx @ 9360 @ @ 1
Caution!
Malfunction during operation!
Through incorrect installation and poor maintenance, malfunction may occur at the
BEKOMAT .
Condensate which is not discharged may cause damage to plants and in production
processes.
Pos: 49 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Feh lfunkt ionen BM @ 0\ m od_12143784 34025_2901. docx @ 9379 @ @ 1
r
Measures:
• Condensate drainage which is reliable in performance directly optimises the compressed-air quality.
• To prevent damage and breakdowns, it is imperative to observe the following:
• Exact compliance with the specifications of use and with the performance parameters of the
BEKOMAT, in connection with the case of application (see "Proper use" section).
• Exact compliance with the installation- and operation instructions in this manual.
• Regular maintenance and control of the BEKOMAT in accordance with the instructions in this oper-
ating manual.
Pos: 50 /Beko TechnischeDok umentat ion/Sicher heit /Hinweis Vorschr ift en Werkzeug Reinigung Kon densat Entsorgung @ 0\m od_1233239666823_ 2901.docx @ 13340 @ @ 1
Note:
It is imperative to observe all hazard statements and warnings listed here.
Please also observe all regulations and notes regarding industrial safety and fire prevention at the place of
installation.
As a matter of principle, only use suitable and appropriate tools and materials in a proper condition.
Do not use aggressive cleaners and improper devices such as high-pressure cleaners.
Please note that condensates may contain aggressive or harmful components. Therefore, skin contact
should be avoided.
Condensate is subject to mandatory waste disposal. As such, it must be collected in suitable containers, and
disposed of or processed properly.
Pos: 51 /Beko Technische Dok um entat ion/Inst allation/B EKOMAT/BM 31/32/33+U+AU (nicht Vario) Inst allat i onshi nwe ise @ 0\ m od_11841616 40511_2 901.docx @ 5876@ @ 1

Installation
BEKOMAT® 33U / 33U CO 15
Installation instructions:
• Only the displayed installation position of the
BEKOMAT (3) is permissible. Never install in a hor-
izontal or any other tilted position.
• Feed pipe (1) and ball valve (2) at least G½.
• No filter or screen in the inlet line.
• Slope in the inlet line >1%.
• Use ball valves (2) only.
• Operating pressure: min. 0,8/1,2 bar (12/17 psig),
max. 16 bar (230 psig). See type plate.
• Short pressure hose (4) fixed on a pressure-re-
sistant pipe.
• The required minimum pressure increases by
0,1 bar (1,4 psi) per metre gradient in the dis-
charge pipe (5).
• Discharge pipe (5) rising by max. 5 m (16,4ft).
• Install manifold (6) ¾" with a slope of 1%.
• Introduce the discharge pipe (5) from the top into
the manifold (6).
• Prior to the start-up, always carry out a leak test
and verify the correct engagement of the control
unit.

Installation
16 BEKOMAT® 33U / 33U CO
wrong correct
Pressure differences!
Each condensate accumulation point must be drained
separately.
Continuous slope!
Avoid a water pocket when installing the feed pipe.
Deflector area!
If drainage is to be carried out directly from the pipe, de-
flection of the air flow will be useful.
Ventilation!
If the slope in the inlet line is not sufficient or if any
other inflow problems occur, a venting line needs to be
installed.
Pos: 52 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Electrical installation
BEKOMAT® 33U / 33U CO 17
Pos: 53 /Beko Technische Dok um entat ion/Überschr ift en/1/ Elektr ische I nst allat ion @ 0\m od_1183638507355_2 901.docx @ 5619 @ 1 @ 1
11 Electrical installation
Pos: 54 /Beko Technische Dok um entat ion/Sich er heit/G ef ahr Net zspannung 1 s/w @ 0\m od_1184148186948 _2901.docx @ 5796@ @ 1
Danger!
Supply voltage!
There is the risk of an electric shock involving injury or death when coming into contact
with non-insulated components carrying supply voltage.
Pos: 55 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Netzspann ung BM 31U/32U/33 U @ 7\m od_13904671 97804_2 901.docx @ 38043@ @ 1
Measures:
• During electric installations, all regulations in force need to be adhered to (e.g. VDE 0100 / IEC 60364).
•When the control unit is open, service and installation works must only be undertaken when the
system is deactivated.
• The removed control unit has no IP degree of protection.
• All types of electrical works must be carried out by authorised and qualified personnel only.
Pos: 56 /Beko Technische Dok um entat ion/Inst allation/B EKOMAT/E lektr I nstallation H inweise BM32 U/33U al lg. @ 4\ m od_135772888407 9_2901.docx @ 29514@ @ 1
Note:
Power supply connection:
1.Read the permissible supply voltage on the type
plate and make sure this voltage is observed.
2. For the supply voltage, a reliably accessible sepa-
rator must be provided close-by (e.g. power plug
or switch), which separates all current-carrying
conductors.
3. At a low-voltage supply
(< 50 VAC / < 75 VDC), only use a protective ex-
tra-low-voltage.
4. Carry out installation in accordance with
VDE 0100 / IEC 60364.
5. Observe the terminal assignment.
6. Do not install when the device is energised.
7. Unscrew the screws (1) and remove the upper
part of the cover (2).
8. Unscrew the threaded cable connection (3), re-
move the plug (if there is one), and lead the cable
(4) for the power supply through.
9. Connect the cable (4) with terminals X1 (1.1, 1.2)
(5).
10.Install the cables as shown (see also terminal as-
signment in the following text).
11.Tighten the threaded cable connection (3) with a
slightly sealing effect.
12.Put on the upper part of the cover (2) and tighten
the screws (1) fingertight.

Electrical installation
18 BEKOMAT® 33U / 33U CO
Connection of the potential-free contact and of
the external test:
1. Selection of the suitable cable.
2. Connection to X2 and X3, as shown in the adja-
cent illustration.
3. The installation steps are the same as for the
power supply connection.
4. If the potential-free contact carries voltage that is
dangerous in the case of contact, a corresponding
separator must also be provided, as described
above.
5. When using the potential-free contacts and the
connection external test, sufficient clearance to
the other parts of the unit, or suitable insulation in
accordance with EN 60664-1 must be ensured.
6. When using a multiwire, common line for the con-
nection of the potential-free contact and the exter-
nal test, this line must be suitable for the highest
occurring voltage and the intended temperature
range with regard to its nominal ratings.
Pos: 57 /Beko Technische Dok um entat ion/Inst allation/B EKOMAT/K lemmenbelegung BM 32U/33 U@ 4\m od_1354692952721_29 01. docx @ 29108@ @ 1
Terminal assignment supply voltage (operating voltage)
X 1 X 2 X 3 Power supply
• X 1.1 L/+
• X 1.2 N/-
L = Outer conductor
N = Neutral conductor
L/+
N/-
NO
CO
NC
IN1
GND
phase
neutral
normally open
common
normally closed
external test (IN1)
GND
1.1
1.2
2.1
2.2
2.3
3.1
3.2
Terminal assignment low voltage (operating voltage)
X 1 X 2 X 3 Power supply
• X 1.1 L/+
• X 1.2 N/-
L/+
N/-
NO
CO
NC
IN1
GND
power
power
normally open
common
normally closed
external test (IN1)
GND
1.1
1.2
2.1
2.2
2.3
3.1
3.2

Electrical installation
BEKOMAT® 33U / 33U CO 19
Terminal assignment of the potential-free contact and of the external test
X 1 X 2 X 3 Fault indication/potential-free contact:
• X 2.1 n.o.
• X 2.2 com.
• X 2.3 n.c.
n.c. - com. closed in the event of malfunction or power failure
(closed current principle)
n.o. - com. closed during normal operation
The contacts X2.1 - 2.3 are potential-free.
External test / remote control:
• X 3.1 external test (IN1)
• X 3.2 GND
Contacts connected = test active = discharge
Contacts open = test inactive
The contacts X 3.1 -3.2 are not potential-free.
L/+
N/-
NO
CO
NC
IN1
GND
power
power
normally open
common
normally closed
external test (IN1)
GND
1.1
1.2
2.1
2.2
2.3
3.1
3.2
Note:
At a low-voltage supply (< 50 VAC / < 75 VDC), only use a protective extra-low-voltage.
Tighten the threaded cable connection with a slightly sealing effect.
Pos: 58 /Beko Technische Dok um entat ion/Inst allation/B EKOMAT/E-Sch em a @ 0\m od_1233758178163_290 1. docx @ 13497 @ @ 1
Electric diagram
Pos: 59 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1

Control and maintenance
20 BEKOMAT® 33U / 33U CO
Pos: 60 /Beko Technische Dok um entat ion/Überschr ift en/1/ Kontrolleund War t ung @ 0\m od_118363788 5371_2901. docx @ 5439 @ 1 @ 1
12 Control and maintenance
Pos: 61 /Beko Technische Dok um entat ion/Sich er heit/G ef ahr Druckluft @ 0\ m od_11841481438 54_2901.docx @ 5778 @ @ 1
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping com-
pressed air or through bursting plant components or plant components which are not
secured.
Pos: 62 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Druckl uft BM @ 0\m od_1184148284291_290 1. docx @ 5814@ @ 1
Measures:
• Do not exceed the maximum operating pressure (see type plate).
• Only carry out service measures when the system is pressureless.
•Use pressure-resistant installation material only.
• The feed pipe must be tubed firmly. Discharge pipe: short, fixed pressure hose onto pressure-resistant
pipe.
• Make sure that persons or objects cannot be hit by condensate or escaping compressed air.
Pos: 63 /Beko Technische Dok um entat ion/Sich er heit/G ef ahr Net zspannung 1 s/w @ 0\m od_1184148186948 _2901.docx @ 5796@ @ 1
Danger!
Supply voltage!
There is the risk of an electric shock involving injury or death when coming into contact
with non-insulated components carrying supply voltage.
Pos: 64 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Netzspann ung BM 31U/32U/33 U @ 7\m od_13904671 97804_2 901.docx @ 38043@ @ 1
Measures:
• During electric installations, all regulations in force need to be adhered to (e.g. VDE 0100 / IEC 60364).
•When the control unit is open, service and installation works must only be undertaken when the
system is deactivated.
• The removed control unit has no IP degree of protection.
• All types of electrical works must be carried out by authorised and qualified personnel only.
Pos: 65 /Beko Technische Dok um entat ion/Sich er heit/Vorsicht Fehlfunkti on @ 0\m od_121437809 6290_2901. docx @ 9360 @ @ 1
Caution!
Malfunction during operation!
Through incorrect installation and poor maintenance, malfunction may occur at the
BEKOMAT .
Condensate which is not discharged may cause damage to plants and in production
processes.
Pos: 66 /Beko Technische Dok um entat ion/Sich er heit/M aßnahmen Feh lfunkt ionen BM @ 0\ m od_12143784 34025_2901. docx @ 9379 @ @ 1
r
Measures:
• Condensate drainage which is reliable in performance directly optimises the compressed-air quality.
• To prevent damage and breakdowns, it is imperative to observe the following:
• Exact compliance with the specifications of use and with the performance parameters of the
BEKOMAT, in connection with the case of application (see "Proper use" section).
• Exact compliance with the installation- and operation instructions in this manual.
• Regular maintenance and control of the BEKOMAT in accordance with the instructions in this oper-
ating manual.
Pos: 67 / - --- Seitenumbruch - --- @0\m od_1157028099015_ 0. docx @ 2903 @ @ 1
This manual suits for next models
1
Table of contents
Other Beko Heat Pump manuals
Popular Heat Pump manuals by other brands

Hayward
Hayward EnergyLine pro instruction manual

SpaNet
SpaNet Power Smart SHP-60 Installation & maintenance manual

HYDRO-FIT
HYDRO-FIT 7009803 user manual

Daikin
Daikin J Series Service manual

Ferroli
Ferroli KSR Installation and operation manual

atecpool
atecpool HiHeat ATHP30 Installation instructions manual