Belimo CRK24-B1 Instruction manual

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 1 / 20
Table of contents
Overview of the system 2
Brief description, Accessories 3
Technical data sheet
Technical data 5
Safety notes 5
Product features 6
Configuration 6
Electrical installation 6
Operation 7
Functions
Introduction 9
Function overview 9
Setpoint determination 10
Pre-comfort 11
Energy hold off (EHO) 11
Chilled ceiling with dew point monitoring 12
External setpoint shift 12
External temperature sensor (ai1) 13
Analogue outputs 13
Dimensions, installation, commissioning, service
Dimensions [mm] 15
Mechanical installation 15
Electrical installation 15
Design for supply / wire sizing 16
Commissioning / Power On response 16
Test and simulation mode 16
Internal Function test 17
Simulation control sequence 17
Product information CRK24-B1
Temperature controller for
heated/chilled ceiling systems

CRK24-B1 Overview of the system
2 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
Heated/chilled ceiling applications
Single room controller
Accessories
CRK24-B1
6-way ball valve and rotary actuators
EXT-K3B2-..-.. + LR24A-MP / LR24A-SR
Diagnostic and setting device
ZTH EU
Setting for MP / MFT(2) actuators
PC-Tool
Connection cable ZTH-VAV to CRK24, Diagnostic socket 1/2
ZK1-VAV
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 3 / 20
CRK24-B1 Brief description, Accessories
Brief description
The room temperature controller CRK24-B1 is precisely designed for the regulation of heated /
chilled ceilings. The output sequence of the controller is calibrated to the new 6-way ball valve
R3015-..-..-B2 / R3020-..-..-B2 with LR24A-MP / LR24A-SR actuator. This controller should
therefore only be utilised in the actuator in combination with the 6-way ball valve.
The multitude of override features makes possible an economically and energetically optimised
system solution for individualised control of the room climate.
Device
Standard model CRK24-B1 with user interface (setpoint
adjustment, mode switch and status display). For operation,
see page 7.
Accessories
Mechanical accessories Type Description
CRZA-A Spare cover without user interface
CRZW Spare baseplate
.
.
.
.
.
.
.

4 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
CRK24-B1

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 5 / 20
Technical data sheet CRK24-B1
Technical data
Electrical data Nominal Voltage AC 24 V 50/60 Hz
Dimensioning 3 VA, without actuators
Power supply range AC 19.2 … 28.8 V
Connections Terminal block 1 … 3: 2.5 mm2
Terminal block 4 … 8: 1.5 mm2
Functional data Control characteristics P
– P-band heating / cooling Selectable: 2.0 K / 1.0 K or 4.0 K / 2.0 K
External temperature sensor (ai1) Type NTC, 5 k�, Power supply range 10 … 45°C
e.g. Belimo Type TFK
Setpoint Adjustment range 15 … 36°C (Default 21°C)
– Energy hold off (EHO)
– Pre-comfort
Heating 15°C / Cooling 40°C
Heating –3 K / Cooling +3 K
Dead band 1 K
Frost protection limit 10°C
Operation
– Mode switch and status display (LED) AUTO (green) – ECO (orange) – MAX (red)
– Rotary knob for setpoint adjustment ±3 K
Communication connection for field devices 2 x PP (for PC-Tool, ZTH EU, etc.)
Inputs 2 x analogue, 2 x digital
– External temperature sensor (ai1) Type NTC, 5 k�, Power supply range 10 … 45°C
– External setpoint shift (ai2) 0 … 10 V correspond to: 0 … 10 K
– Digital inputs (di1, di2,) Contact rating 10 mA
Output 1x analogue
– 6-way ball valve (ao1) (0) 2 … 10 V, max. 5 mA
Norms and Standards Protection class III Safety extra-low voltage
Degree of protection IP30 (EN 60529)
Mode of operation Type 1 (EN60730-1)
Software class A (EN 60730-1)
EMC CE according to 2004/108/EU
Ambient conditions
– Operation 0 … +50°C / 20 … 90% r.h. (non-condensating)
– Transport and storage 25 … +70°C / 20 … 90% r.h. (non-condensating)
Dimensions / Weight Dimensions (H x W x D) 99 x 84 x 32 mm
Weight 105 g
Housing colour Baseplate NCS2005-R80B light grey (corresponds approximately
to RAL 7035)
Cover RAL9003 signal white
Temperature controller for single-room
applications with one analogue output:
• The 6-way ball valve for the regulation of
a heated/chilled ceiling can be connected
with the analogue output ao1.
Safety notes
!
• The controller is not allowed to be used outside the specified field of application, especially
in aircraft or in any other airborne means of transport.
• It may only be installed by suitably trained personnel. Any legal regulations or regulations
issued by government agency authorities must be observed during assembly.
• The device does not contain any parts that can be replaced or repaired by the user.
• The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.
.
.
.
.
.
.
.

6 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
CRK24-B1 Technical data sheet
Product features
Energy hold off
(EHO)
In energy saving mode, the room temperature is regulated to the building protection level, i.e.
the heating setpoint is significantly reduced or the cooling setpoint is significantly increased, for
instance in a room with an open window.
Pre-comfort The room temperature is reduced to stand-by level, i.e. the heating setpoint is slightly reduced
and/or the cooling setpoint is slightly increased, for instance in a room that is temporarily
unoccupied.
Frost If the current room temperature falls below 10°C, then the frost function will be activated.
Dew point limitation If the optional connectable dew point limiter responds, then the valve is moved into neutral
position.
External temperature sensor An external temperature sensor can be connected at analogue input ai1.
External setpoint shift An external DC 0 ... 10 V signal at the analogue input ai2 can be used to shift the basic setpoint
by 0 ... 10 K, e.g. for summer/winter compensation.
The functions are described in detail on pages 9 to 13.
Electrical installation
Wiring diagram
U5
CRK24-B1
EHO
13
y
5
U
2
~
AC 24 V
0 … 10 V
12 7 86
ao1
1
U5
2
4
di2
3
5
ai1/di
1a
i2
~
Notes
• Connect via safety isolation transformer.
• Parallel connection of other actuators possible.
Note the performance data.
!
Configuration
Configuration ao1 modulating ao1 On/Off
1 2 3 4 5 6
ON
OFF
l
[V]
ao
1
10
7.3
4.7
2
0 10 33 66 90 100 [%]
l
[V]
ao
1
10
6
2
0 10 33 66 90 100 [%]
Shifting
Pre-comfort
Dew point limiter
Actuator for 6-way valve
External NTC
temperature sensor
DIP
Default settings
1 P-Band normal P-Band wide
2 Output ao1 modulating Output ao1 On/Off
ao1
(heating)
ao1
(cooling)
ao1
(heating)
ao1
(cooling)
Inputs Outputs
3ai1 External temperature sensor 6 ao1 System output for 6-way valve
di1 Pre-comfort Other connections
4 di2 Energy hold off / dew point 7 PP1 Diagnostic socket 1
5 ai2 External setpoint shift

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 7 / 20
Operation CRK24-B1
1
2
3
4
5
6
7
8
21
Mode switch and status display
Selection can be made between three operating modes:
• AUTO – optimum comfort mode
The room will be kept at comfort zone status insofar as the external
control signals permit this. All control functions are enabled.
• ECO – optimum energy mode
The room will be kept at pre-comfort status insofar as the external
control signals permit this. Reduced heating (–3 K) and elevated
cooling setpoints (+3 K) are in effect in this status. Starting from this
status, the room can be returned to comfort status within a short time.
Sequence control is enabled. The operating mode ECO is intended
for rooms not continuously occupied and/or for reduced requirements.
• MAX – Boost function
The room will be heated or cooled at maximum power, insofar as the
external control signals permit this.
The Boost function is switched off:
– Timer off
– Setpoint is reached
– Selection of a different mode (AUTO or ECO)
Measuring point terminals
Measuring points for all connection terminals (also during operation).
Internal function test
A comprehensive internal function test can be started with the mode
switch which makes it possible to check the controller, including
nominal voltage (AC 24V). The three LEDs (status display) are used
thereby to display the voltage level and the statuses.
Simulation control sequence
The rotary knob for the setpoint adjustment can be used to simulate
the connected actuators, and thus the heating and cooling control
sequences, independent of the room temperature.
ZTH EU / PC-Tool connection
The diagnostic socket 1 is used for PP communications with the
connected Belimo MFT actuator. Physical access to the valve actuator
can be dispensed with as a result.
Operating level 1 – Operation Operating mode / Setpoint
DIP switch for configuration
DIP switches 1 and 2
Basic setpoint setting WH (heating setpoint)
Potentiometer 15 … 36°C (Default 21°C)
Label for settings
Recording the settings used
(DIP switch and basic setpoint)
Operating level 2 – Configuration Application / Parameters
Operating level 3 – Service Test / Simulation
Rotary knob for setpoint adjustment
Potentiometer ±3 K
Mode switch
• MAX
• ECO
• AUTO
Status display
• MAX (red)
• ECO (orange)
• AUTO (green)
O
rder-Nr
.
Order-Nr.
CR24-B2xxxxx
W
H
U5/
2
U5/
1
12
ON
OFF
21
36
15
Measuring point
terminals
ZTH EU / PC-Tool connection
Internal function test
Basic setpoint settingDIP switch for configuration
Label for settings
1
2
3
4
5
6
7
8
Rotary knob for
simulation of control sequence
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

8 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
CRK24-B1

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 9 / 20
Functions CRK24-B1
Introduction
The control functions of the CRK24-B1 define the behaviour of the controller output or influence
the current setpoint, respectively.
Operation can be automated and comfort and energy savings potential enhanced through the
utilisation of corresponding sensor mechanisms at the input side.
The corresponding functions are described in detail in the following.
Function overview CRK24-B1
Supply AC 24 V / 50/60 Hz
Application – Room temperature controller in the comfort zone
– Internal temperature sensor (Type NTC, Power supply range 10 … 45°C)
– Setpoint (adjustment range 15 ... 36°C)
Operation – Mode selection switch: AUTO – ECO – MAX
– Mode display LED: AUTO – ECO – MAX
– Setpoint adjustment rotary knob ±3 K
Inputs – Pre-comfort
– Dew point limitation
– Energy hold off (EHO)
– External temperature sensor (Type NTC 5 kΩ, Power supply range 10 … 45°C)
– External setpoint shift 0 … 10 V
Output – 2 … 10 V System output: Belimo 6-way ball valve
Functions – Control characteristics: P
– P-Band, switchable
– Output can be switched (modulating / On/Off)
– Room temperature monitoring (frost)
– Internal Function test with nominal voltage check
– Commissioning mode with simulation of output and sequence
– Diagnostics via integrated PC-Tool connection
Installation Surface mounting with flush-mounted or surface-mounted connection
Application documentation
Continually expanded, comprehensive documentation with specific applications is available for the
CRK24-B1 controller.

10 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
CRK24-B1 Functions
Operating status Heating setpoint Cooling setpoint
Comfort Basic setpoint WH
±3 K setpoint adjustment
+ Setpoint shift 0 … 10 V
Comfort-Heating setpoint WA
+1 K dead band
Pre-comfort Comfort-Heating setpoint WA
– 3 K Pre-comfort-Offset heating
Comfort-Heating setpoint WA
+1 K dead band
+3 K Pre-comfort-Offset cooling
Energy hold off fix 15°C (building protection) fix 40°C (building protection)
Frost fix 10°C without function
Setpoint calculation
Examples Comfort Pre-comfort
Y
tR
+1 K dead band
23°C Comfort setpoint WA
Y
tR
+1 K dead band
23°C Comfort setpoint WA
+3 K Pre-comfort-Offset
Cooling
–3 K Pre-comfort-Offset
Heating
[%]
100
0
EHO
Valve opening
tRoom [°C]
Dead band
WH Basic setpoint
WA current setpoint
Pre-comfort
Frost
Dew point
Ws Setpoint shift 0 … 10 V
Setpoint adjustment ±3 K

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 11 / 20
CRK24-B1 Functions
Pre-comfort Digital input di1
If a local detector (e.g. a motion detector) has an effect on the digital
input di1 and closes the corresponding contact, then the room will be
regulated to stand-by level, i.e. the heating setpoint is reduced by 3 K or
the cooling setpoint is raised by 3K, respectively.
Typical applications
– One motion detector, light switch or other detector at di1 reduces the
energy consumption in unoccupied rooms.
– Superordinate imperative command, e.g. GLT.
Notes
– The frost limit is monitored with the internal sensor during Pre-comfort
when an external temperature sensor is used.
– As a result of the automatic sensor recognition feature, the switch-over
to Pre-comfort takes approximately 40 seconds.
12
3
~
ai/di1
AC 24 V
NTC
CRK24-B1
[%]
100
0
Energy Hold Off (EHO) Digital input di2
If a local detector (e.g. a window switch) has an effect on the digital input
di2 and closes the corresponding contact, then the room will be regulated
in energy-savings mode to the building protection level, i.e. the heating
setpoint is significantly reduced (15°C) and/or the cooling setpoint is
significantly raised (40°C), so that sensitive furnishings (plants, pictures,
etc.) will not be able to suffer any damage.
Typical applications
– One window switch at di2 stops energy consumption as soon as the
window is opened until the lower or upper building protection limit has
been reached.
– Superordinate imperative command, e.g. GLT.
Notes
– The 6-way valve is moved into neutral position during the Energy Hold
Off (ao1 = 6 V).
– The mode switch (operating level 1) is deactivated during the Energy
Hold Off (the input di2 has higher priority).
tRoom [°C]
WA
Pre-comfortY
Pre-comfort
12
4
~
di2
AC 24 V
CRK24-B1
[%]
100
0
tRoom [°C]
WA
EHOY
Energy Hold Off
Legend
Y Output signal
WACurrent setpoint
Legend
Y Output signal
WACurrent setpoint

12 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
CRK24-B1 Functions
Chilled ceiling with dew point limiter Digital input di2
If the optional connectable dew point limiter responds, then the output
ao1 is overridden to 6 V by means of the input di2 (external dew point
limiter). The 6-way ball valve moves into neutral position.
Typical applications
Chilled ceiling systems in which one dew point limit is required.
12 7
~
~
ao1 U51
4
di2
AC 24 V
CRK24-B1
12 5
U5
6
3
YBelimo actuator for 6-way valve
Cooling / Heating
Dew point reached
Dew point
l
[V]
ao
1
10
7.3
4.7
2
0 10 33 66 90 100 [%]
ao1
(heating)
ao1
(cooling)
Dew point
External setpoint shift Analogue input ai2
1 2
5
0 … 10 V
ai2
AC 24 V
CRK24-B1
~
An external DC 0...10 V signal at the analogue input ai2 can be used to
raise the basic setpoint by 0 ... 10 K (corresponding to
0 … 10 V).
Typical application
Summer/Winter Compensation
W [°C]
S [V]
5.00
26
21
16
10
Notes
A negative shift is possible by setting the basic setpoint to the desired
final setpoint, e.g. from 21°C (default value) to 16°C. This results in the
following correspondences:
– 0 … 5 V: 16 … 21°C and
– 5 … 10 V: 21 … 26°C (see illustration at the left).
Legend
W Setpoint
S Shift signal
Setpoint shift

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 13 / 20
CRK24-B1 Functions
External temperature sensor (ai1)
An external NTC temperature sensor can be connected at analogue input ai1. Sensor type: NTC
5k (5 kΩ), e.g. Belimo TFK.
Typical applications
• More flexible placement of the sensor for recording the room temperature
• Temperature measurement in the ventilation channel for recording the average room
temperature.
12
3
AC 24 V
CRK24-B1
ai/di1
T
~
Notes
• The controller recognises it automatically if an
external sensor is connected. No additional
adjustments are required.
• The simultaneous utilisation of Pre-comfort
at di1 is possible, although in this case a
switchover to the internal sensor is made (see
also «Pre-comfort»). As a result, the current room
temperature is monitored for building protection.
External NTC
temperature sensor
Pre-comfort
Analogue outputs
LR24A-MP Actuator for 6-way ball valve
• System output «ao1» (Terminal 6). diagnostic socket «U5/1» (Terminal 7).
U5
CRK24-B
1
13
y5
U
2
~
AC 24 V
12 7 86
ao1 1U5
24
di2
3
5
ai1/di1 ai2
~
Note
When using an LR24A-MP, it is expedient to direct
the communications signal U5 of the actuator to the
controller. Interventions can be implemented on the
actuator by means of controller diagnostic socket 1
without the need for direct physical access. LR24A-MP
Actuator for 6-way valve

14 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
CRK24-B1

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 15 / 20
Dimensions, installation, commissioning, service CRK24-B1
1 2 3 4 5 6 7 8
1.5mm2
2.5mm2AC 24 V -
-
1
2
3
4
5
6
7
8
1 2 3 4 5 6 7 8
Cam
Left stop
1
2
3
1 2 3 4 5 6 7 8
1. Remove the housing cover.
2. Pull out slightly the wall of the housing to
release the pcb.
3. Remove the PCB.
Rotary knob for setpoint adjustment
If the rotary knob has been removed proceed
as follows:
a. Insert the rotary knob approximately half
way and turn it clockwise as far as the stop.
b. Remove the knob and align it so that the
cam is flush with the left stop (see left).
c. Insert the knob fully.
Dimensions [mm]
56
60
56
99
84
90
32
Mechanical installation
Electrical installation
Flush-mounted connection
Surface-mounted connection
Terminal connection 1 … 8

16 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
CRK24-B1 Dimensions, installation, commissioning, service
Power supply design / wire sizing
In addition to the actual wire sizing, attention must also be paid to the surrounding area and the
cable routing. Signal cables must not be laid in the vicinity of load cables, objects liable to cause
EMC interference. etc. Paired or layer stranded cables improve immunity to interference.
24 V supply
Wire sizing and cabling
The wire sizing and installation of the AC 24 V supply, the fuse protection, and the cables are
dependent on the total operated load and local regulations.
Account must be taken of the following performance data, including starting currents:
– Wire sizing values for room temperature controllers: 3 VA per CRK24-B1
– Wire sizing values for the valve actuators can be obtained from current data sheets and
product information (www.belimo.eu)
– Other devices to be operated with the AC 24 V supply
– Reserve capacity for subsequent expansion (if planned)
Analogue input connection ai1 The analogue input ai1 is used to connect an external NTC 5 kΩ temperature sensor. The
sensor value is 5969 Ω at 21°C. A change of 50 Ω corresponds to approximately 0.2 K in this
range.
The sensor cable constitutes a series resistance that must be added to the actual sensor value.
Assuming a cable length of 15 m (2 x 15 = 30 m), the resistance of one 0.75 mm2 Cu cable is
approximately 0.7 Ω, in other words negligible.
To prevent interference, however, the sensor cable should be a maximum of 20 m long.
Commissioning / Power on behaviour
Commissioning 1. Assemble the baseplate of the housing and connect the cables (see page 15)
2. Configure the DIP switches on the printed circuit board according to the required application.
3. Assemble the printed circuit board on the baseplate of the housing and then mount the
housing cover (see page 15)
4. Switch on the nominal voltage AC 24 V
5. Optional: start the test and simulation mode (see below)
When the voltage is applied, the system starts operating normally in AUTO mode unless the
test simulation mode is selected. The active operating status is determined primarily by the
configuration of the DIP switches and the status of the inputs.
Power on behaviour After power on of the voltage supply the output gets initialised as follows:
– ao1 = 0 V
Subsequently the controller switches automatically to the control mode.
Test and simulation mode
All controllers are supplied with two auxiliary programs for commissioning and servicing:
– Internal function test
– Control sequence simulation
Activating test and simulation mode The test and simulation mode of CRK24-B1 controllers can be activated easily with the mode
switch on the operator panel.
To activate test mode
1. Set the mode switch to MAX
– The red LED (MAX status indication) lights up
2. Keep the mode switch pressed for ten seconds
– The internal function test is activated (see below)
To activate simulation mode
3. Press the mode switch again briefly for approx. one second
– The green LED (COMF status indication) flashes
– Control sequence simulation is activated (see below)
Deactivating test and simulation mode The test and simulation mode can be deactivated either by pressing the mode switch again for
ten seconds or by interrupting the power supply. It is also deactivated automatically 15 minutes
after the last user action (auto-reset).

www.belimo.eu S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes 17 / 20
+3
–2
–1
+2
+1
W = X
–3
0
[V]
10
6
2
0
0
–3 +3
CRK24-B1 Dimensions, installation, commissioning, service
Internal function test
The internal function test tests the nominal voltage that is connected to the controller (AC 24 V),
in other words the complete electrical wiring system from the control cabinet to the controller..
The three LEDs (status indication) indicate the voltage level
(see below) and states during the test.
Note
Case B and C do not need further attention. In
case A (<20 V) attention must be paid to the
following points:
– Quality of the wiring and connections
– Cable length and diameter and the transformer
sizing
Nominal voltage (AC 24 V)
LED (status indication) Scenario A Scenario B Scenario C
MAX red flash flash permanently on
ECO orange flash flash permanently on
AUTO green permanently
off flash permanently on
<20 V 20 … 22 V >22 V
Control sequence simulation
CRK24-B1 In the simulation mode, the connected actuator can be operated regardless of the room
temperature. This permits the function of the system to be checked.
Notes
– The external control signals (di1 and di2) are
suppressed during the simulation.
– The potentiometer may be adjusted only slowly,
due to the system-dependent attenuation of the
setpoint potentiometer in simulation mode.
– Simulation mode is automatically deactivated 15
minutes after the last user action (auto-reset).
Potentiometer (setpoint adjustment)
Output
Shift
Heating
Cooling
XpHXpK
out
1

18 / 20 S4-CRK24-B1 • en • v1.2 • 06.2016 • subject to changes www.belimo.eu
CRK24-B1


All-inclusive.
Belimo worldwide: www.belimo.com
5 year
guarantee
World-wide
on your doorstep
Complete product range
froma single source
Tested quality
Short delivery time
Comprehensive support
Switzerland
BELIMO Automation AG
Sales Switzerland
Brunnenbachstrasse 1
CH-8340 Hinwil
Tel. +41 (0)43 843 62 12
Fax +41 (0)43 843 62 66
www.belimo.ch
Benelux
BELIMO Servomotoren BV
BENELUX
Postbus 300, NL-8160 AH Epe
Radeweg 25, NL-8171 MD
Vaassen
Tel. +31 (0)578 57 68 36
Fax +31 (0)578 57 69 15
www.belimo.nl
Germany
BELIMO Stellantriebe
Vertriebs GmbH
Welfenstrasse 27
D-70599 Stuttgart
Tel. +49 (0)711 1 67 83-0
Fax +49 (0)711 1 67 83-73
www.belimo.de
At no charge
Orders:
Tel. 0711 1 67 83-83
Technical Consultation:
Tel. 0711 1 67 83-84
Fax 0711 1 67 83-73
Personal consultation with Regional
Sales Director in:
Berlin, Hanover, Düsseldorf
Leipzig, Frankfurt, Munich
Hamburg, Stuttgart
Austria
BELIMO Automation
Handelsgesellschaft m.b.H.
Geiselbergstrasse 26-32
A-1110 Vienna, Austria
Tel. +43 (0)1 749 03 61-0
Fax +43 (0)1 749 03 61-99
www.belimo.at
Austria West
Tel. +43 (0)644 14 26 365
Fax +43 (0)732 70 10 51
dietmar[email protected]
Hungary
Tel. +36 (06)20/920 46 16
Fax +36 (06)23/37 77 30
gabor.koe[email protected]
Slovakia
Tel. +43 (0)1 749 03 61-0
Fax +43 (0)1 749 03 61-99
Slovenia/Croatia/Bosnia
Tel. +386-(0)41-75 89 63
Fax +386-(0)4-2342-761
Serbia/Montenegro/
Macedonia/Bosnia
Tel./Fax +381-(0)11 311-9127
branimir.petro[email protected]
Table of contents
Popular Temperature Controllers manuals by other brands

Hukseflux
Hukseflux HFP01SC user manual

Auber Instruments
Auber Instruments WS Series Operation & instruction manual

Solo
Solo SL4848-RR quick start guide

S+S Regeltechnik
S+S Regeltechnik THERMASGARD ALTM2 operating instructions

System Sensor
System Sensor 2351TB Installation and maintenance instructions

DELTA DORE
DELTA DORE DELTA 200 user guide

Winland Electronics
Winland Electronics Temp Alert TA2HL Installation & owner's manual

Ecomatik
Ecomatik T-Soil user manual

ILX Lightwave
ILX Lightwave LDT-5412B user guide

Viessmann
Viessmann VITOSOLIC 200 operating instructions

Doepke
Doepke Dupline DTS 2 operating instructions

MULTISPAN
MULTISPAN TC-49 quick start guide