Bentel Security FC410SIO User manual

ITALIANO
SPECIFICHE TECNICHE
Valore Identificativo: 148
Compatibilità: usare solo con Centrali serie FC
Caratteristiche ambientali: Solo per applicazioni interne
Temperatura di funzionamento: da -25 a +70 oC
Temperatura di stoccaggio: da -40 a +80 oC
Umidità relativa:fino a 95% (senza condensa)
Dimensioni (HxLxP): 85 x 60 x 15 mm
Requisiti di montaggio: Scatola americana dual-gang
Sezione cavi consigliata: Min. 1,5 mm2Max. 2,5 mm2
Corrente assorbita
Corrente a riposo:
Corrente in allarme:
0,3 mA
3,0 mA
Stati del dispositivo indirizzabile: – Normale
– Attivo
– Guasto Corto Circuito
– Guasto Circuito Aperto
– Dispositivo non valido
– Dispositivo non risponde
Circuito d'Ingresso
Resistore di Fine Linea:
Resistore di Allarme:
3K3
680 Ω
ENGLISH
TECHNICAL SPECIFICATION
TypeIdentificationValue: 148
System Compatibility: Use only with FC Fire Alarm Controllers
Environment: Indoor Application only
Operating Temperature: -25 to +70 oC
Storage Temperature: -40 to +80 oC
Operating Humidity: Up to 95% non-condensing
Dimensions (HxWxD): 85 x 60 x 15 mm
Mounting Requirements: Dual-gang electrical box
Recommended Wire Size: Min. 1.5 mm2Max. 2.5 mm2
Battery Requirements
Standby current:
Alarm current:
0.3 mA
3.0 mA
Addressable Device Con-
ditions:
– Normal
– Active
– Short Circuit wiring fault
– Open Circuit wiring fault
– Device Type Invalid
– Device No Response
Input Circuit
EOL
Alarm resistor
3K3
680 Ω
Modulo 1 Ingresso / 1 Uscita FC410SIO FIG. 1FC410SIO Single Input / Output Module
FC410SIO
®
ISO 14001
9191.BNT2
ISO 14001
IT-52588
ISO 9001
9105.BNT1
ISO 9001
IT-52587
MODULO 1 INGRESSO / 1 USCITA
SINGLE INPUT / OUTPUT MODULE
ISTISBL3FC410SIO 0.0 241007

Compatibilità Elettromagnetica
Il modulo FC410SIO è conforme a quanto segue:
Øfamiglia di prodotto standard EN50130-4 rispetto alle Perturba-
zioni Dirette, Immunità Irradiata, Scarica Elettrostatica, Transi-
torie Rapide e Alta Energia Lenta;
ØEN 61000-6-3 per le emissioni.
INTRODUZIONE
Il modulo 1 ingresso / 1 uscita FC410SIO è progettato per fornire
un ingresso open-collector monitorato ed un'uscita costituita dallo
scambio libero di un relè.
CARATTERISTICHE
ØIl FC410SIO può commutare fino a 2 A @ 24 Vcc
NOTE PER IL COLLEGAMENTO E L'INSTALLAZIONE
Osservare le seguenti note:
1) Sul modulo FC410SIO non ci sono regolazioni da effettuare
(interruttori o altro).
2) Tutti i collegamenti devono essere conformi alle norme applicabili.
3) Nessun conduttore deve essere collegato a terra.
4) Verificare la corretta polarità dei collegamenti prima di connet-
tere il modulo FC410SIO al circuito loop indirizzabile.
5) Per lo schema tipico di collegamento del FC410SIO, vedere Fig. 4.
NSTALLAZIONE NEL COPERCHIO ACCESSORIO FC470CV
1) Fissare il FC410SIO al coperchio accessorio FC470CV,
tramite le quattro viti e le rondelle fornite.
2) Fissare il coperchio sulla scatola americana dual-gang.
PROGRAMMAZIONE
L'indirizzo di fabbrica del FC410SIO è 255, questo deve essere impo-
stato all'indirizzo di loop del dispositivo tramite lo strumento per la pro-
grammazione dei dispositivi indirizzabili FC490ST. L'indirizzo del
FC410SIO può essere programmato prima dell'installazione usando la
porta di programmazione interna (vedere Fig. 2) o dopo l'installazione
usando la porta di programmazione sul coperchio (vedere Fig. 3).
+Nota: una volta programmato l'indirizzo, annotare la posizione
del dispositivo e l'indirizzo, per segnarlo sul progetto dell'im-
pianto.
Electromagnetic Compatibility
The FC410SIO complies with the following:
Øproduct family standard EN50130-4 in respect of Conducted
Disturbances, Radiated Immunity, Electrostatic Discharge,
Fast Transients and Slow High Energy;
ØEN61000-6-3 for emissions.
INTRODUCTION
The FC410SIO Single Input/Output Module is designed to provide
a monitored open collector input and a volt free relay changeover
output.
FEATURES
ØFC410SIO can switch up to 2 A @ 24 Vdc
WIRING & INSTALLATION NOTES
The following notes apply:
1) There are no user-required settings (such as switches or head-
ers) on the FC410SIO.
2) All wiring must conform to the applicable standards.
3) All conductors to be free of earths.
4) Verify the correct polarity of wiring before connecting the
FC410SIO to the addressable loop circuit.
5) For FC410SIO typical wiring configuration see Fig. 4.
INSTALLATION TO FC470CV ANCILLARY COVER
1) Assemble the FC410SIO to FC470CV ancillery cover, using
the four screw and washers provided.
2) Fit cover onto dual-gang backbox.
ADDRESS SETTINGS
The FC410SIO has a default factory set address of 255, this must
be set to the loop address of the device using the FC490ST Loop
Service Tool. The FC410SIO may be programmed with the ad-
dress prior to being installed by using the internal programming
port (see Fig. 2) or after being installed by using the programming
port on the front cover (see Fig. 3).
+Note: once the address has been programmed, take note of
the device location and address number, to include on site
drawings.
PORTA DI PROGRAMMAZIONE
PROGRAMMING PORT
FC470CV COPERCHIO PER GLI ACCESSORI
FC470CV ANCILLARY COVER
FIG. 2FC410SIO fissato al coperchio / FC410SIO fitted to cover
PORTA DI PROGRAMMAZIONE
ADDRESS SETTING PORT
FIG. 3Placca per FC410SIO / FC410SIO Facia Plate

COLLEGAMENTI
I cavi devono essere selezionati in conformità con il documento di
progettazione e nel rispetto delle norme applicabili. La sezione
massima del cavo collegabile ad ogni morsetto è di 2,5 mm2. La
sezione và calcolata in base alle caratteristiche del cavo e del cari-
co.
INFORMAZIONI PER L'ORDINE
FC410SIO: Modulo 1 Ingresso / 1 Uscita
FC470CV: Coperchio accessorio
CABLING
Cables are to be selected in accordance with the system design
document and the requirements of the applicable standards.The
maximum section of the cable that can be connected at any one
terminal is 2.5mm2. The section is calculated based on the charac-
teristics of the cable and the load.
ORDERING INFORMATION
FC410SIO: Single Input / Output Module
FC470CV: Ancillary Cover
PORTA DI PROGRAMMAZIONE
PROGRAMMING PORT
CONTATTO MONITORATO
MONITORED CONTACT
AL CARICO COMMUTATO
TO SWITCHED LOAD
ALLA CENTRALE DI CONTROLLO
O DISPOSITIVO SEGUENTE
TO CONTROL EQUIPMENT OR
NEXT DEVICE
DALLA CENTRALE DI CONTROLLO
O DISPOSITIVO PRECEDENTE
FROM CONTROL EQUIPMENT OR
PREVIOUS DEVICE
Schema di collegamento semplificato del FC410SIO FIG. 4FC410SIO simplified wiring diagram

RECYCLING INFORMATION
BENTEL SECURITY recommends that customers dispose of their
used equipments (panels, detectors, sirens, and other devices) in
an environmentally sound manner. Potential methods include re-
use of parts or whole products and recycling of products, compo-
nents, and/or materials.
For specific information see
www.bentelsecurity.com/en/environment.htm
WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT
(WEEE) DIRECTIVE
In the European Union, this label indicates that this
product should NOT be disposed of with household
waste. It should be deposited at an appropriate facility
to enable recovery and recycling.
For specific information see
www.bentelsecurity.com/en/environment.htm
BENTEL SECURITY s.r.l. reserves the right to change the techni-
cal specifications of this product without prior notice.
INFORMAZIONI SUL RICICLAGGIO
BENTEL SECURITY consiglia ai clienti di smaltire i dispositivi
usati (centrali, rilevatori, sirene, accessori elettronici, ecc.) nel ri-
spetto dell'ambiente. Metodi potenziali comprendono il riutilizzo di
parti o di prodotti interi e il riciclaggio di prodotti, componenti e/o
materiali.
Per maggiori informazioni visitare
www.bentelsecurity.com/it/ambiente.htm
DIRETTIVA RIFIUTI DI APPARECCHIATURE ELETTRICHE
ED ELETTRONICHE (RAEE - WEEE)
Nell'Unione Europea, questa etichetta indica che que-
sto prodotto NON deve essere smaltito insieme ai ri-
fiuti domestici. Deve essere depositato in un impianto
adeguato che sia in grado di eseguire operazioni di re-
cupero e riciclaggio.
Per maggiori informazioni visitare
www.bentelsecurity.com/it/ambiente.htm
BENTEL SECURITY s.r.l. si riserva il diritto di modificare le speci-
fiche tecniche di questo prodotto senza preavviso.
Other Bentel Security I/O System manuals