OneFex CE-IO4444 User manual

1
/ 13
CE-IO4444 User Manual
CE-IO4444
Ethernet I/O Module
Manual

2
/ 13
CE-IO4444 User Manual
1PRODUCT INTRODUCTION............................................................................................... 5
1.1 Features ...........................................................................................................................................5
1.2 Parameter.........................................................................................................................................5
1.3 Item Selection .................................................................................................................................6
1.4 Dimension........................................................................................................................................6
2WIRING INSTRUCTIONS..................................................................................................... 6
2.1 Terminal Definition.........................................................................................................................6
2.2 RS232 Wiring...................................................................................................................................7
2.3 Input&Output Wiring......................................................................................................................8
2.3.1 DI Wiring ............................................................................................................................................. 8
2.3.2 DO Wiring ........................................................................................................................................... 8
2.3.3 Analog Wiring.....................................................................................................................................9
3DEVICE PARAMETER CONFIGURATION.................................................................... 9
3.1 Download Link ................................................................................................................................9
3.2 Software Interface ..........................................................................................................................9
3.3 Communication Test....................................................................................................................10
3.4 Analog data input expaination...................................................................................................11
4ETHERNET CONFIGURATION&COMUNICATION TEST......................................11
4.1 Ethernet Parameter Config.........................................................................................................11
4.1.1 Direct mode ...................................................................................................................................... 11
4.1.2 Networking mode............................................................................................................................. 14
4.1.3 TCP/UDP Configuration..................................................................................................................18
4.2 Communication Test....................................................................................................................21
4.2.1 Test Software................................................................................................................................... 21
4.2.2 Network Test Tool............................................................................................................................21
4.2.3 Modbus TCP Testing ......................................................................................................................28
5PLC COMMUNICATION.....................................................................................................32
6DEVELOPMENT DATA INSTRUCTION........................................................................32
6.1 Flash On Flash Off Mode ............................................................................................................32
6.2 Modbus Register Instruction......................................................................................................32

3
/ 13
CE-IO4444 User Manual
6.3 Command List...............................................................................................................................34
6.4 Command Details.........................................................................................................................35
6.4.1 Control DO........................................................................................................................................ 35
6.4.2 Query DO Status .............................................................................................................................35
6.4.3 Query DI............................................................................................................................................36
6.4.4 Query AI............................................................................................................................................ 37
6.4.5 Single Analog Output Setting.........................................................................................................37
6.4.6 Multi-channel Analog Output Setting ............................................................................................ 38
6.4.7 Flash ON Flash OFF Command.................................................................................................... 38
6.4.8 All ON and All OFF Command.......................................................................................................39
7PRODUCT MAINTENANCE..............................................................................................40
7.1 Device Usage Environment ........................................................................................................40
8AFTER-SALE SERVICE.....................................................................................................40
8.1 Commitment..................................................................................................................................40
8.2 Disclaimer......................................................................................................................................40
9UPDATE HISTORY...............................................................................................................40

4
/ 13
CE-IO4444 User Manual
Notice
❖Please read this manual carefully before use and save it for reference.
❖Please follow to the operating procedures and precautions in this manual.
❖Please open the package carefully and check whether the device and accessories have been
damaged due to transportation when you receive the device.
Please contact us for return processing once damage occurs.
❖Please do not repair it yourself, and contact our technical support department directly if the
device fails.
❖Manual and Config Tool download link:
https://onefexindustrial.com/ethernet-io-module

5
/ 13
CE-IO4444 User Manual
1 Product Introduction
CE-IO series products are Ethernet I/O module using standard Modbus RTU/TCP protocol,
integrates DO (digital output), DI (digital input), AI (analog input).
The communication method supports Ethernet networking, 7~40V wide voltage power
supply, and supports functions such as logic control between analog acquisition and relay
output.
Widely used in farms, agricultural greenhouses, IoT terminals, water conservancy,
electricity, gas collection and control and other application scenarios, its unique logic control
function can easily realize automatic water supply, fertilization, start and stop valves It is an ideal
device for small automatic control scenes.
1.1 Features
◆DC 7-30V wide voltage power supply, support anti-reverse connection;
◆4*optocoupler inputs (5-24V);
◆4*DO contact isolation, normally ON and normally OFF, 10A 250VAC / 10A 30VDC;
◆4 *analog voltage inputs with 12-bit resolution;
◆4*analog isolated outputs with 10-bit resolution;
◆LED indication for power and working status; 4 leds for DO status;
◆SupportsRS232+ EthernetCommunicationinterface,powerisolationplussignalisolation,reliable
communication;
◆Communication baud rate: 300bps~38400bps (It is 9600 by default and can be
modified by software);
◆SupportstandardModbus RTU/TCPprotocol,readandwrite by registeraddress;
◆Support input and output linkage, such as local linkage or dual-computer linkage, which is
convenient for multi-terminal control;
◆Support flash ON flash OFF;
◆Supporting setting software for setting parameters and IO control;
◆Support software and hardware customization.
1.2 Parameter
Paremater
Contact capacity
10A/250VAC
Durability
100,000 times (Electrical)
10,000,000 times (Mechanical)
Data interface
RS485+rs232+Ethernet
Default IP
192.168.16.254
Working Voltage
DC 7-30V
Power / work indication
1 red LED
(power, always on; working, flashing)
Output indication
4red LEDs (relay on and off)
Working temperature
-40℃~85℃, Industrial Grade
Size
90*145*40mm
Weight
207g
Default communication format
9600,n,8,1
Baud rate
300~38400bps

6
/ 13
CE-IO4444 User Manual
Software support
Setting and control software;
Support various configuration software;
support Labviewd, etc.
Installation
35mm Din Rail Mounting / Screw Holes
1.3 Item Selection
CE-IO0222
2*DI&2*DO&2*AI, RS485+Ethernet, Modbus RTU/ TCP/UDP
CE-IO0222S
2*DI&2*DO&2*AI, RS485+Ethernet, Modbus RTU/ TCP/UDP,
Smart Intelligent Control Version
CE-IO4444
4DO+4DI+4AI+4AO,RS232+Ethernet,Modbus RTU/ TCP/UDP
CE-IO1600
16DO,RS485+Ethernet,Modbus RTU/ TCP/UDP
CE-IO12884
12DO+8DI+8AI+4AO,RS232+RS485+Ethernet,Modbus RTU/ TCP/UDP
1.4 Dimension
90*145*40mm
2 Wiring Instructions
2.1 Terminal Definition
Function
No.
Pin
Explaination
Power supply
DC7-30V
1
-
Positive power supply
2
+
Negative power supply
Communication
3
RXD
232 communication RX interface
4
TXD
232 communication TX interface
5
GND
232 communication ground
6
PB
485 communication shielding
7
485A+
Isolated 485 communication A interface
8
485B_
Isolated 485 communication B interface
Analog Input
9
AI1
The first analog input signal positive
10
AI2
The second analog input signal positive
11
AI3
The third analog input signal positive
12
AI4
The fourth analog input signal positive

7
/ 13
CE-IO4444 User Manual
13
AGND
Analog input signal negative
Digital Input
14
DCOM+
Input signal common positive
15
DI1
The first switch input signal positive
16
DI2
The second switch input signal positive
17
DI3
The third switch input signal positive
18
DI4
The fourth switch input signal positive
Digital Output
35
DO1
The first relay output normally close terminal
34
The first relay output public terminal
33
The first relay output normally open terminal
32
DO2
The second relay output normally close
terminal
31
The second relay output public terminal
30
The second relay output normally open
terminal
29
DO3
The third relay output public terminal
28
The third relay output normally close
terminal
27
The third relay output normally open
terminal
26
DO4
The fourth relay output normally close
terminal
25
The fourth relay output public terminal
24
The fourth relay output normally open
terminal
Analog Output
23
AO1
The first analog output
22
AO2
The second analog output
21
AO3
The third analog output
20
AO4
The fourth analog output
19
GND
Analog output ground
2.2 RS232 Wiring

8
/ 13
CE-IO4444 User Manual
2.3 Input&Output Wiring
2.3.1 DI Wiring
2.3.2 DO Wiring

9
/ 13
CE-IO4444 User Manual
2.3.3 Analog Wiring
3 Device Parameter Configuration
3.1 Download Link
JYDAMEn
https://onefexindustrial.com/ethernet-io-module
3.2 Software Interface
Toolbar
Explaination
Communication
settings
Serial port/network communication mode selection;
Port number/TCP address selection;
Set AI/DI/DO read refresh time
DO control
Operate the DO channel;
Select DO mode;
Set the action time
DI input
View DI input status;
Read DI status to generate query command;
Set DI/DO channel name
Analog Input
Display 4-20ma/0-10v/0-5v real-time data/curve;

10
/ 13
CE-IO4444 User Manual
Display PT100/K type thermocouple/DS18B20 temperature data/curve;
Display real-time acquisition time;
Set the AI/temperature channel name;
Set the AI channel range conversion and display unit;
Manually export excel table data;
Manually save the data curve.
Analog Output
Set AO output;
Generate AO multi-channel output command.
Parameter Setting
Display the current device AI/DI/DO channel number information;
Set the baud rate;
Set the offset address;
Set the working mode;
Set AI/DI/DO automatic return;
Set DO power-down memory
Command area
Generate commands such as AI/DI/DO/AO/parameter setting.
Debugging area
User-defined sending command test
3.3 Communication Test
1 Select the current serial port number of the device (fill in IP for the IP address);
2 Select the default baud rate of 9600;
3 Open the port:
4 There is a receiving command on the right side, and the relay can be controlled, that is, the
communication is successful.

11
/ 13
CE-IO4444 User Manual
3.4 Analog data input expaination
1 Select analog input;
2 The data size and real-time curve can be directly viewed below.
4 Ethernet Configuration&Comunication Test
4.1 Ethernet Parameter Config
Ethernet
IP Address
Network
Mode
Port#
Device
Address
192.168.1.232
TCP
Server
10000
1
There are 2 modes for ethernet parameter configuration
Hardware
Connection
Instuctions
Direct mode
The io is directly connected to computer
through a network cable
Networking mode
The io is connected to the router/switch via a
network cable
4.1.1 Direct mode

12
/ 13
CE-IO4444 User Manual
Open [Network and Sharing Center]---->[Change Adapter Settings]---->[Local Area Connection]--
-->[Properties]---->[IPV4], modify the computer IP to static IP: 192.168.1.10;
(Because the default IP of io is 192.168.1.232, when modifying its parameters, the io IP must be
in the same network segment as the computer IP.
➢Open JYNetConfigEn, it shows as below:

13
/ 13
CE-IO4444 User Manual
➢Chosse Local connection:
➢Searching:
Revise parameter

14
/ 13
CE-IO4444 User Manual
➢researching
4.1.2 Networking mode
Check to make sure that the computer network and the router/switch connected to io are in
the same network.
Note: generally, there are multi-level networks in the enterprise. When the computer is
connected to the wireless network and the io is connected to the router through a network
cable, it must be confirmed that the router connected to the io is the same as the wireless
WIFI router.

15
/ 13
CE-IO4444 User Manual
➢searching;
➢View current network information
Open [Network and Sharing Center]---->[Active Network]---->[Local Area Connection/Wireless
Network Connection]---->[Details], as shown in the following figure:

16
/ 13
CE-IO4444 User Manual
➢Check whether the IP to be modified by the device is occupied

17
/ 13
CE-IO4444 User Manual
➢Revise IP
➢Researching

18
/ 13
CE-IO4444 User Manual
4.1.3 TCP/UDP Configuration
Mode
Instruction
TCP Server
①The device is used as the server side;
②Support two Clients to use different port numbers to communicate
with the device.
TCP CLient
①The device is used as the Client;
②It can be set to communicate with two different server addresses;
③Support setting handshake packets and heartbeat packets
UDP Server
①The device is used as the server side;
②Support setting two clients to use different port numbers to
communicate with the device
UDP Client
①The device is used as the Client;
②It can be set to communicate with two different server addresses;
4.1.3.1 TCP Server

19
/ 13
CE-IO4444 User Manual
4.1.3.2 TCP Client
➢Mode revisement
➢Login information packet (handshake packet)
When using the TCP Client mode, the device will send a handshake message when connecting
to the server for the first time as a client, which can be customized and modified.

20
/ 13
CE-IO4444 User Manual
➢Heartbeat packet
4.1.3.3 UDP Server
Table of contents
Other OneFex I/O System manuals
Popular I/O System manuals by other brands

CyberResearch
CyberResearch CYDIO 96HE user manual

Siemens
Siemens Simatic S7-1500 user manual

National Instruments
National Instruments PXIe-5764 SAFETY, ENVIRONMENTAL, AND REGULATORY INFORMATION

SeaLevel
SeaLevel COMM+850.LPCI user manual

ProSoft Technology
ProSoft Technology Wireless I/O System quick start guide

WAGO
WAGO I/O-SYSTEM 750 manual