  9. BFT KUSTOS BT A25 User manual

BFT KUSTOS BT A25 User manual

12
3
5x0.75 mm²
3x1.5 mm²
230 v
3x1.5 mm²
2x0.75 mm²
3x1.5 mm²
Z=b-x>60mm
Pa
x
b
S
D
F
2s
kg
C=1070mm
1
2
1
2KUSTOS BT A25
a
1090 250
Cu Max
KUSTOS BT A25
84
FC2
(close)
a
FC1
(open)
Pro.Tube BT A25 - Pro.Tube BT A25 ULTRA
a
Pro.Tube BT A40 - Pro.Tube BT A40 ULTRA
1090
1210
Cu MAX
295
355
120
110
80
Cu MAX
S
(mm) 125
kg
(~ 1250 N)
250
kg
(~ 2500 N)
b (mm)
20 100 ÷ 120 130 ÷ 210
30 100 ÷ 130 140 ÷ 210
40 100 ÷ 140 150 ÷ 210
50 100 ÷ 150 160 ÷ 210
KUSTOS BT A25 b
a100 110 120 130 140 150 160 170 180 190 200
100 114 118 110 104 100 96 93
110 108 112 110 103 97 96 92
120 103 107 110 105 99 96 92
130 99 102 106 109 101 96 92
140 98 101 103 102 96 92
150 97 100 100 95 92
160 97 100 97 92
170 96 97 92
180 96 92
190 92
200
210
FW ≥ 2.05
Cable run Use normalised black cables
R02V - HO5VVF
Adjust the limit switches and the stops according to the diagrams, open/closed position.
If necessary, fine-tune the adjustments to be performed upon completion of installation.
Limit switch adjustment (put motor in gear by moving the panel by hand)
For safety warnings, please see complete instruction manual
Motor fastening
Programming (see reverse)
Product reserved for professionals
CLOSE OPEN
4
Open the pre-hole for air passage.
To avoid insects, use a gable gland.
5
D813986 04903_03 20-07-21
ELS
Y #
F2 4 AT
F1 1.25 AT(220-230V)
F1 2.5 AT (120V)
ANT.
ANT
SHIELD
T1 T2 T3 T4
NORWP
FLT2
FLT1
PHOT
STOP
OPEN
START
SW02
SW01
SWC2
SWC1
BAR
10 11
M1
14 15 20 21 28 29 40 41 42 43 44 45 50 51 52 60 61 62 70 71 72 73 74 75
M2
24V
24V -
24V +
24 VSafe+
COM
NO
NO
NC
NC
NC
SW2
-
+
-
+
SW1
JP5 JP2
JP4 +
+
+
+
L N
LN
220-230V ~
*
START
OPEN
COM
PHOT
STOP
FAULT 1
BAR
FAULT 2
S1 S2 S3
RADIO
EER
SET
1
2
3
ZARA
2
1ON
OFF
Zara Control board
Safety
devices
CommandsLimit switch
inputs Accessories
power supply
BlinkerMotor
Solenoid
lock
DIP
Function
1Transmitter programming
Selection of sensing bars.
Check photocells.
Secure entry check.
Photocells during closing
ON: Memorise the commands/copy via remote controls already recorded.
OFF : Disables memorizing of transmitters
ON : Input for resistive edge 8K2.
OFF: Entry for sensitive lintel.
ON : Enable safety check
OFF: Deactivate the cell check.
ON : Enable safety check
OFF: Deactivate the sensing check.
ON: Invert the movement during the closure phase only.
OFF: Active on opening and closing; invert the movement during the closure phase.
2
3
4
5
Sets the automation type of operation:
ON = Apartment building
OFF = Residential
ON : Safety edge with active reversal only when closing, when opening the movement stops
OFF : Safety edge with active reversal in both directions
Fast closure. ON : Closes 3 seconds after the photocells are cleared
OFF: Fast closure deactivated.
7
Safety edge input operation
6
Residential / apartment
building operation
8
OFF : Logic not enabled
Hammer during opening
9
Closing limit
switch pressure
10
*factory pre-parameterised
ON : Before opening completely, the gate pushes for approx. 2 seconds as it closes.
This allows the solenoid lock to be released more easily.
IMPORTANT - Do not use this function if suitable mechanical stops are not in place.
ON : Use when there is a mechanical stop in closed position.This function allows leaves
to press against the mechanical stop without the Amperostop sensor interpreting this
as an obstacle. Thus the rod continues its stroke for a few seconds after meeting the
closing limit switch or as far as the mechanical stop. In this way, the leaves come to rest
perfectly against the stop by allowing the closing limit switches to trip slightly earlier.
OFF : Movement is stopped only when the closing limit switch trips: in this case, the
tripping of the closing limit switch must be adjusted accurately
Apartment
building
Residential
Reaction to the START input (wired or radio):
CLOSED Opens
Stops
Opens
Opens Opens
OPEN Closes Closes
Opens
WHILE
CLOSING
STOPS+TCA No effect
WHILE
OPENING
AFTER
STOP
Apartment
building
Residential
Reaction to the OPEN input (wired):
CLOSED Opens
Opens
Opens
Opens Opens
OPEN
Opens
WHILE
CLOSING
Keeps it
open Keeps it
open
No effectNo effect
WHILE
OPENING
AFTER
STOP
Closes Closes
STOPS+TCA No effect
Apartment
building
Residential
Reaction to the PEDESTRIAN input (radio):
CLOSED Opens
partially Opens
partially
Opens
partially Opens
partially
Stops Opens
partially
OPEN
WHILE
CLOSING
WHILE
OPENING
AFTER
STOP
S2
>5s
S1+ S2
>10s
KEYS
Description
S1
S2
S3
Add Start Key
associates the desired key with the Start command.
Add Pedestrian Key
associates the desired key with the pedestrian command.
Confirms the changes made
to parameter settings and operating
Erase List
WARNING! Erases all memorized transmitters
from the receiver’s memory.
Pressed BRIEFLY, it gives the START command.
HELD DOWN (>5 sec.), it activates the AUTOSET function.
2
TRIMMER
Function
T1
T2
Waiting time before automatic closing. 0 120
5 50
0
0 0
25
10 100
% Force exerted by leaf
% Slow-down speed
Motor 1 closing delay time [s]
NOTE: set 0 for single motor operations
(leaf 1).
T3
T4
+
mini. +
maxi
3
2
3
How to programme the remote control
How to perform an open/close test by using the remote control.
If they close, switch wiring:
Left Right
M1 : 10&11 / M2 : 14&15
M1 closes second.
4Start an autoset, gate closed.
LED RADIO
FLASHES
RADIO
START
x1
S1 S2 S3 S1 S1
OK
Choose the key
LED RADIO
FLASHES
S1
S3 X1
START
S3 X1
STOP
START
=
5s
S1 S S3
S1 S2 S3
SET
SET SET
OK KO
AUTO OPEN AUTO CLOSE
AUTO OPEN AUTO CLOSE
S1 S2 S3 S1 S2 S3
5
mini maxi
+++ +
4
6Fine-tune the adjustments. Motor functions using the potentiometers (T1, T2, T3, T4).
Remember to check
by pressing S2 for 5 sec.
As an option, to go further....
1 - I wish to deactivate the photocells during opening:
3 - I wish to activate pedestrian opening:
Place dipswitch 5 in the ON position.
4 - I wish to adjust the time difference between M1 & M2: This is done by regulating the T4 potentiometer.
2 - I wish to activate and adjust automatic closure:
This is done by regulating the T1 potentiometer.
3
Testing the direction of opening - running / stop: apply power, motor
engaged and at stroke centre.
Checking the direction of rotation. I press S3, my two motors must open.
Please refer to the remote control programming
by pressing S2.
Press the 2 top keys simultaneously
(hidden key). The LED remains fixed
24V
2
1
TX1 2
1
RX1
4
5
3
50 51 52
70 72 73
DIP3=ON DIP3=OFF
24V
2
1TX1 2
1
RX1
4
5
3
50 51
70 72
Wire the THEA photocells. 1b1a Wire the DESME photocells
Remove the wire between
terminals 70 and 72
Remove the wire between
terminals 70 and 72
Open the pre-hole
for air passage.
or

Other manuals for KUSTOS BT A25

1

Other BFT Fencing & Gate manuals

BFT STOPPY User manual

BFT

BFT STOPPY User manual

BFT D6000 User manual

BFT

BFT D6000 User manual

BFT RANCH B 219/500 Guide

BFT

BFT RANCH B 219/500 Guide

BFT MOOVI AC 30-60 User manual

BFT

BFT MOOVI AC 30-60 User manual

Popular Fencing & Gate manuals by other brands

Reer I-Gate manual

Reer

Reer I-Gate manual

Carlson Pet Products 0930 PW Assembly instructions

Carlson Pet Products

Carlson Pet Products 0930 PW Assembly instructions

Orbinox BC Installation, operation & maintenance manual

Orbinox

Orbinox BC Installation, operation & maintenance manual

barrier DOCK-SAFE INSTALLATION PROCEDURE

barrier

barrier DOCK-SAFE INSTALLATION PROCEDURE

U-Line H-6251 manual

U-Line

U-Line H-6251 manual

Casanoov 400B160 VELETA instruction manual

Casanoov

Casanoov 400B160 VELETA instruction manual

Feeney DesignRail installation instructions

Feeney

Feeney DesignRail installation instructions

vita VA20234 Assembly instructions

vita

vita VA20234 Assembly instructions

Safety 1st Easy Close Metal quick start guide

Safety 1st

Safety 1st Easy Close Metal quick start guide

Kiwitech PowerPac VP POWD instructions

Kiwitech

Kiwitech PowerPac VP POWD instructions

Parking Facilities PF9500A O & M Manual

Parking Facilities

Parking Facilities PF9500A O & M Manual

Summer Fun 2700600 Directions for use

Summer Fun

Summer Fun 2700600 Directions for use

Casanoov ART300B140 manual

Casanoov

Casanoov ART300B140 manual

Betafence Nylofor City installation manual

Betafence

Betafence Nylofor City installation manual

Casanoov VOGEL 350C180 manual

Casanoov

Casanoov VOGEL 350C180 manual

Boundaryline SLEEKWALL SOLID install guide

Boundaryline

Boundaryline SLEEKWALL SOLID install guide

Centrewire Chiltern MK2 installation guide

Centrewire

Centrewire Chiltern MK2 installation guide

PERCo FP-01C instruction manual

PERCo

PERCo FP-01C instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.