
Pre-Installation
Greenstar Heatslave II External 2022+ - 6 721 843 980 (2022/01) 17
Key to illustration 20:
1. 1,500mm measured between an opening or vented window and
vertical flue terminal.This measurement can be reduced to 1000mm
providing the flue terminal is at least 300mm above the opening.
2. Minimum clearance to an additional flue, 1,500mm between room
sealed flues or room sealed flue and open flue, 1,000mm between
open flues.
3. 600mm above a vertical structure less than 750mm from the side of
the terminal.
4. The flue must extend at least 600mm above the intersection of the
roof (flat and pitched) and be 400mm horizontally from a pitched
roof or 500mm in regions with heavy snow fall
5. The flue must not penetrate the roof in the shaded area. The flue must
be at least 2,000mm from the opening or vent when sited below the
window,600mm when sited to either side or above.The terminal
must be at least 1,500mm room sealed, 1,000mm open flue from
the opening or vent when measured horizontally.
6. The flue must not penetrate the roof in the shaded area. The flue must
be at least 1,000mm from the opening or vent when sited below the
window, 750mm when sited to either side and 300mm above.The
terminal must be at least 1,500mm from the opening or vent when
measured horizontally.
7. 300mm minimum clearance measured from a non opening skylight
to a vertical flue.Vertical flue clearance,
8. 600mm minimum clearance measured from an opening or vented
skylight to a vertical flue. If the terminal is within 1,500mm of the
opening or vented skylight then it must be at least 600mm above the
opening.
9. 750mm clearance to a structure from a vertical flue.
Not required if the terminal is 600mm above the structure.
10. 750mm adjacent to a boundary line unless it will cause a nuisance.
BS 5410: Part 1 recommended that care is taken when siting
terminal in relation to boundary lines.
11. 1,200mm separation measured between a vertical flue and a
horizontal flue terminal. Not required if the horizontal flue is
1,500mm above vertical flue terminal.
12. 1,000mm (BS 5410-1) above, below and either side of an opening
door, air vent or opening window. These clearances are required by
BS 5410 Part 1 to reduce a possible pluming nuisance.If 1,000mm
cannot be achieved then the distance can be reduced to 600mm to
comply with Approved Document J of the building regulations if it
will not cause a nuisance or dispute.
13. 300mm adjacent to a boundary line unless it will cause a nuisance.
BS 5410: Part 1 recommended that care is taken when siting
terminal in relation to boundary lines.
14. 1,500mm vertically between terminals and the same wall.
15. 1,000mm (BS 5410-1) below eaves, gutters and sanitary pipe and
300mm from vertical sanitary pipes and drains.
If 1,000mm cannot be achieved then the distance below eaves,
gutters and sanitary pipe can be reduced to comply with Approved
Document J of the building regulations if it will not cause a nuisance
or dispute. 75mm if combustible material is protected or 600mm
without protection to combustible material1).
16. The dimension below eaves, gutters, pipes and drains can be
reduced to 75mm, as long as the flue terminal is extended by
100mm past any overhang. The telescopic flue joint must be sealed
with suitable silicone sealant if it is external to the building
17. 1,200mm between terminals facing each other.
18. 2,500mm (BS 5410-1) distance to a surface or boundary line.
If 2,500mm cannot be achieved then the distance can be reduced
to 600mm to comply with Approved Document J of the building
regulations if it will not cause a nuisance or dispute.
19. Terminals must be at least 1,800mm from an oil storage tank
unless a wall with of at least 30 minutes fire resistance and
extending 300mm wider and higher than the tank is between the
tank and the terminal. The flue air intake must be at least 900mm
away from the oil storage tank vent.
20. 1000mm diagonally to an opening door, air vent or opening
window.
21. 300mm to an internal or external corner. 300mm above a surface,
such as the ground/ floor level or roof surface.
22. The dimension below eaves, balconies and car ports can be
reduced to 75mm, as long as the flue terminal is extended to clear
any overhang. The telescopic flue joint of the terminal must be
sealed with suitable silicon sealant if it is external to the building.
23. 1,000mm (BS 5410-1) from an opening or vented window,
300mm to a fixed unvented window. If 1,000mm cannot be
achieved then the distance from an opening or vented window can
be reduced to 600mm to comply with Approved Document J of the
building regulations if it will not cause a nuisance or dispute.
24. The flue terminal must be at least 1,500mm from the opening or
vented skylight when sited below the opening or vented skylight.
25. Proximity of flue duct outlet to boundaries, 2000mm distance to an
opening in adjacent building facing a terminal. BS 5410: Part 1
recommended that care is taken when siting terminal in relation to
boundary lines.
26. The distance between a boundary facing a flue terminal can be
measured diagonally from the point of discharge with a minimum
distance of 600mm which must be maintained. The exclusion zone
ensures compliance with Approved Document J of the building
regulations.
27. For the purpose of determining suitable flue terminal positions for
oil appliances discharging over public boundaries, the boundary
can be considered to extend to the centre line of any adjacent
routes or waterways e.g. paths, streets, rights of way, canals, rivers
or railways.
NOTICE:
▶ All measurements are the minimum clearances
required.
▶ Terminals must be positioned so to avoid
combustion products entering the building.
▶ Support the flue at approximately one metre
intervals and at a change of direction, use suitable
brackets and fittings:
- flue bracket 125mm x 1- Part No.: 7 716 191 179
▶ In spite of the dimensions given here, the terminal
must not be closer than 300mm to combustible
material, in the case of a thatched roof double this
dimension.
▶ Terminals must be positioned so to avoid products
of combustion accumulating in stagnant pockets
around the building or entering the building.
▶ Terminals must be at least 1.8m from an oil storage
tank unless a wall with of at least 30 minutes fire
resistance and extending 300mm wider and higher
than the tank is between the tank and the terminal.
1) A way of providing protection of combustible material would be to fit a heat
shield at least 750mm wide.
NOTICE:
▶ Installations in car ports are not recommended.
▶ Dimensions from a flue terminal to a fanned air inlet
to be determined by the ventilation equipment
manufacturer.