
12
S193 Series Installation
12/5/2012 Bradley • 215-1712EW Rev. B; ECN 12-05-38
Optional Features
Ground Fault
Provides equipment electrical protection to ground.
After installation of water and power, test the ground fault.
1. Press the GF Test button.
• Watch for the ground fault light to illuminate and Bank Ready light(s) to shut off. The Ground Fault system is active
and working properly.
2. Press the GF Reset button to reset the ground fault.
IMPORTANT! If a trip occurs under normal operation, DO NOT RESET the Ground Fault without first evaluating and
servicing the unit.
IMPORTANT! Normal state is Ground Fault light OFF, Bank Ready lights ON.
Freeze Protection (ENHT)
Protects system and internal components in sub-freezing conditions. Allows unit to function at -23°F with an 11 mph wind. With
this option, three phase power must be continuously applied to the SN heater for the internal freeze protection heater to operate.
If three phase power cannot be continuously applied, the heat exchanger must be completely drained of water and electrically
locked out and tagged or freezing may occur. Use start up procedure previously outlined to restart this equipment. This option
does not require a separate electrical circuit.
IMPORTANT! All freeze protected SN heaters are equipped with a temperature sensor that can provide a signal to a
remote device when temperature inside the cabinet falls below 40°F (refer to the schematics for more
information).
NEMA 4X
Corrosion-proof enclosure made of stainless steel which is ideal for harsh environments.
Computer Interface Temperature Controls
Controls temperature from a remote location.
• To create an if/then scenario and set 2 input points to determine safe range of temperatures.
• Absolute temperature control to maintain specific set temperature.
Explosion Proof Purge System
Electrical components installed in a NEMA 4 enclosure allow the system to be pressurized by clean instrument air or inert gas.
The purge process removes flammable gases and/or prevents the accumulation of ignitable dusts within the protected enclosure.
Heat, moisture, dust and corrosion are eliminated by a slow, continuous flow of inert gas or dry compressed air. This type of
system conforms to Class 1, Division 2 hazardous area standards. Other Class and Division ratings may be available.
Preventive Maintenance
For your system to work properly and have protection from freezing, keep the system dry inside the enclosure. Moisture inside an
enclosure increases the humidity inside, which condenses on cooler surfaces of the enclosure. This causes electrical problems
and reduces the efficiency of enclosure insulation.
Preventive Maintenance
1. Dry out the enclosures.
2. Seal any weeping leaks in seals or walls.
3. Replace missing plugs on the back of the enclosure.
4. Check seals monthly when temperatures rise above 32°F and weekly when temperatures fall below 32°F.
5. Check the performance of the internal freeze protection system for proper performance prior to the first seasonal freeze.
Check weekly during temperatures below 32°F. Refer to the "Optional Features" section for additional information on freeze
protection.
6. The manual reset safety overheats on the heat exchangers may trip when temperatures fall below 32°F. The overheats are
set to trip at 100°F. Heat trace installed on piping can heat water to temperatures above 100°F. This causes the overheats to
trip. Reset the overheats and lower the heat trace temperature to below 100°F.
If systems are sealed and checked at the frequency outlined above during weekly OSHA Shower Checks, the system will provide
years of reliable service. Preventive measures to correct small problems that may arise over the years will prevent more costly
failures or catastrophic freeze failures in the future.