
HAMWORTHY HEATING LTD
FERNDOWN
500001111/C
6.1 Flue System General Requirements
The Hamworthy Ferndown is designed for use with the
following flue systems supplied by Hamworthy - see
Figures 6.1.1, 6.1.2, 6.1.3 & 6.1.4:
80/125mm concentric room sealed, balanced flue
system for rear through the wall discharge.
100/150mm concentric, room sealed, balanced flue
system for remote discharge, horizontal or vertical –
maximum length 7m.
100mm separate air and flue ducts, room sealed,
balanced flue system for remote discharge – maximum
length 10m.
100mm flue duct, for connection to an open flue
(chimney) system – maximum length 10m.
Flue systems should be designed with reference to BS
5440 part 1, IGE/UP/10, and Third Edition of the 1956
Clean Air Act Memorandum.
Flue installations can be configured to suit a number of
applications, see Figures 6.1.1, 6.1.2, 6.1.3 & 6.1.4: but
must comply with one of the following options:
Room Sealed.
Type C13: Horizontal balanced flue. – Fig 6.1.1.
Type C33: Vertical balanced flue. – Fig 6.1.2.
Type C53: Separate intake and discharge ducts
terminating in different pressure zones. – Fig 6.1.3.
Open Flue.
Type B23: Intake from ventilated plant room and
discharge via horizontal/vertical flue. – Fig 6.1.4.
WARNING
The Sherborne boiler is a High Efficiency/
Condensing boiler and in certain conditions
‘pluming’ will be visible from the flue terminal.
Should pluming be a concern, the flue system
design should discharge at high level.
Care should be taken to ensure that the flue is
installed such that any condensation is continuously
drained back to the boiler or any resultant low points
in the flue system. Horizontal flue runs should be
kept to a minimum and must be inclined at 2°
upwards in the direction of the exhaust gas flow. All
joints should be such that any condensation is
directed back down the slope.
6.2 Condense Drain
The boiler module is provided with a condense drain
suitable for connection to 22mm plastic waste pipe
(not supplied), which must be connected to a
tundish (not supplied).
Discharge piping from a tundish should be of a
synthetic material due to the mild acidity of the
condensate (pH 3-5), with all discharge piping
having a minimum fall of 30mm/m away from the
boiler. Consideration should be given to possible
freezing of condense water traps and pipework. This
must be avoided at all times by routing pipework
within the building, where possible.
6.3 Design Waste Gas Volume and Temperature
Figure 6.4 Flue Resistance
Component Length
m
Straight tube ø100mm per m 1
45° bend ø100mm 2.25
90° bend ø100mm 4.10
Concentric straight tube ø80/125mm per m 1
Concentric straight tube ø100/150mm per m 1
Concentric 45° bend ø100/150mm 1.30
Concentric 90° bend ø100/150mm 2.20
Equivalent tube lengths.
6.5 Disconnection
Each Ferndown is fitted with a telescopic appliance
connector, enabling the boiler to be disconnected from
the flue system.
NOTE! The flue system must be self supporting and
not present a risk to people in or around the building.
See Section 13: SERVICING for further information.
6.6 Flue Discharge
The flue system must ensure safe and efficient
operation of the Ferndown to which it is attached,
protect the combustion process from wind effects and
disperse the products of combustion to the external air.
The flue must terminate in a freely exposed position and
be so situated as to prevent the products of combustion
entering any opening in a building in accordance with
BS 5440 part 1, IGE/UP/10.
When the application requires the flue discharge to
terminate below 2 m above ground level, the use of a
terminal guard is required.
6.4 Maximum Length of Flue Duct.
For Ferndown installations the maximum allowable
linear equivalent length of straight smooth bore tube
for both (air supply and flue discharge) twin duct,
and concentric systems is approximately 10m and
7m respectively. This dimension relates to the
distance between the boiler and the discharge
terminal. The table below nominates the equivalent
length of flue tube. Components can be combined in
any order provided that the total equivalent length of
flue does not exceed the maximum. Note: if the
maximum stated lengths of flue are exceeded the
boiler will not achieve maximum output.
7