manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Brivis
  6. •
  7. Air Conditioner
  8. •
  9. Brivis HSNBR26 User manual

Brivis HSNBR26 User manual

1. Determine hole positions according to left and right
positions of the installation plate. The hole centre is obtained
by measuring the distances as shown in the diagram above.
2. Drill the pipe exit hole with a 65mm hole saw.Ø
3. Drill the piping hole on either the left or right side and as required,
the hole should be slanted downwards towards the outside.
4. Always take steps to protect the pipes when drilling through
metal plate, solid structures or the like.
INSTALLATION MANUAL
Brivis HSNBR26 - 32 - 42 - 50
Inverter Hi-Wall Split System
WALL PIPE EXIT HOLE
INSTALLATION PLATE MOUNTING
I
N
D
O
O
R
U
N
I
T
Please read these safety precautions carefully before undertaking installation
Please be sure to follow the precautions as listed below, they are important for ensuring your safety.
This symbol indicates the possibilityof death or serious injury.
This symbol indicates the possibilityof injury or damage to property.
1) This equipment must be properly earthed and installed with a circuit breaker. Electrical shock may
result if earthing is inadequate.
2) Do not install the unit in areas where leakage of flammable gases may occur. If gas leaks are allowed
to accumulate around the unit, it may cause fire.
3) Install condensate drain piping as described in the installation instructions. If drainage is insufficient
water may leak into the room and damage furniture and fixtures.
1) Install strictly inaccordance with these installation instructions. If installation is defective or incomplete,
it maycause refrigerant or water leaks, electrical shockor fire.
2) Use the supplied accessories and specified partsfor installation, otherwise it maycause the unit to fall,
leak water, electrical shock or fire.
3) Install in a strong firm location,sufficient to withstand the unitsoperating weight. If the mounting is
insufficient or incomplete, the unit may fall and cause damage and/or injury.
4) Electrical installation must follow all local state and national wiring standards and regulations. A
separate and independent electrical circuit and single outlet must be used. If electrical circuit capacity
is insufficient or electrical connections are defective, it may cause electrical shock or fire.
5) Use the specified cable and ensure connectionsare tight. Clamp the cable so that no external forces
can be placed on the terminals. If connection is inadequate, it may cause overheating and failure.
6) Wiring routing must be properlyarranged so that the control board cover is fixed properly.If thecover
is not fixed properly, it may cause overheating at the connection point and fire or electrical shock.
7) When carrying out refrigerant pipe connections, ensure that no air or other contaminants can enter
the refrigeration circuit. Otherwise, it may cause performance issues, abnormally high pressures
in the refrigeration cycle, possible explosion and/or personal injury.
8) Do notmodify the length of the power supply cord or use an extension cord. Do not share the
electrical outlet with other electrical appliances. Otherwise, it may cause fire or electrical shock.
SAFETY PRECAUTIONS
CAUTION
WARNING
CAUTION
WARNING
Please read this manual carefully before operating the unit, to ensure correct installation.
If the power cord is damaged, replacement work must be performed by authorised personnel only.
Installation work must be performed in accordance with all state and national wiring standards by
authorised personnel only.
Contact an authorised service technician for repair and/or maintenance of this unit.
This appliance is not intended for use by persons (including children) with reduced physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by persons responsible for their safety.
Children should be supervised to ensure that they do not play with this appliance.
The pictures in these instructions are for explanation purposes only. Please refer to actual product type.
The design and specifications are subject to change without notice for continuous product improvement.
Please contact Brivis or your Installer for details.
The unit should not be installed close to any heat sources
or where steam is prevalent.
There should be no obstacles blocking air
circulation in or around the unit.
Locate unit where air circulation/direction is best.
Locate unit where drainage setup is best.
Locate unit taking into account prevention of unwanted
noise.
Do not install the unit near doorways.
Ensure the clearances as indicated by arrows in the adjacent figures
are maintained from walls, ceilings, fences or other obstacles.
Install away from direct sunlight. If unavoidable, external
sunlight prevention should be taken into consideration.
A(mm) B(mm)
530 290
560 335
Mountingdimensions
760x590x285
845x700x320
Indoor unit
Outdoor unit
If a shade or awning is built over the unit to prevent
direct sunlight or rain, please be careful that heat
radiating from the condensing unit is unrestricted.
Keep unit away from any animals or plants which
could be affected by hot air discharged.
Ensure the clearances as indicated by arrows in the adjacent
figures are maintained from ceilings, fences or obstacles.
Do not place any obstructions which may cause recirculation
or short circuit of the condenser air discharge.
Do not install the unit where it may cause a noise issue for either
the home owner or neighbours, or exceed any local, state or
regulatory bodies legislative guidelines.
Secure the outdoor unit with bolts and nuts 10mm
diameter tightly and into a concrete or rigid mount.
Securing the outdoor unit
NOTE: The outdoor unit dimensions are as per below
Install the outdoor unit according to the dimensions
as indicated in the following table:
Air inlet
Air outlet
Air inlet
INSTALLATION PRECAUTIONS
ELECTRICAL CONNECTION - INDOOR UNIT
Minimum nominal cross-sectional area of wiring:
Ratedcurrent
ofappliance
(A)
> 3up to6
> 6up to10
>10upto 16
>16upto 25
Nominalcross-sectional
area
(mm )
2
0.75
1.0
1.5
2.5
The cable and the circuit breaker sizes
are determined by the maximum
current indicated on the nameplate
located on the side panel of the unit.
Please refer to the nameplate before
selecting the cable and circuit breaker.
Indoor unit cable connection
NOTE:
Before performing any electrical work, turn off the mains power to the system.
1. The inside and outside connection cables can be connected without removing the front grille.
2. The indoor power cord type is H05VV-F or H05V2V2-F, the outdoor power cord and
interconnected cord type is H07RN-F.
3. Lift the indoor unit panel up, remove the electrical box cover by loosening the screw.
4. Ensure the colour of wires and the terminals of the outdoor unit directly match those
of the indoor unit exactly.
5. Isolate any disconnected wiring, ensure that they cannot touch any other electrical components
or connections. Secure the cable with the cord clamp.
NOTE:
Electronic box
cover
Front Panel
1
2
3
4
5
7
8
9
10
6
Installation Plate
Clip Anchor
Self-tapping Screw A ST3.9x25
Seal
Drain Joint
Connecting
refrigerant
pipe
Liquid
Gas
Remote control
Air freshening filter (installed with Air filter)
Self-tapping Screw B ST2.9x10
Ø6.35mm
Ø9.52mm
Ø9.52mm
Ø12.7mm
Ø15.9mm
Purchased separately. The pipe sizes
differ depending on the system size.
Contact Brivis for the correct sizes.
1
5-8(depending on model)
5-8(depending on model)
1
1
1
2
1
1
With the exception of the supplied parts above, other parts required to complete the
installation must be supplied by installer.
Remote control holder
ACCESSORIES
Number
Accessory QtySupplied
optional
parts
SELECT THE BEST LOCATION
INTERCONNECTING PIPE AND CONDENSATE DRAIN
1. Run the condensate drain hose sloping down.
Do not install the condensate drain hose as
illustrated in the incorrect figures.
2. When connecting an extension to the condensate
drain hose, be sure to insulate the connection. Do not run drain uphill Do not submerge outlet
Do not allow the drain to form a trap or allow
the condensate drain hose to droop.
Condensate drain
Co rrect Incor rect
1. Fit the installation plate firmly on the
structural parts of the wall with spaces
around the installation plate shown.
2. If the wall is made of brick, concrete
or the like, drill the 5mm diameter
mounting holes in the wall. Insert the
clip anchors for appropriate mounting
screws.
3. Fit the installation plate on the wall
with the typeA screws.
Drill the holes and mount the installation
plate in accordance with the wall
structure and the corresponding mounting
points on the installation plate. The
installation plates provided with the
units differ from unit to unit depending
on the size. (Dimensions are in
mm unless otherwise stated)
NOTE:
NOTE:
"
"
Installation Plate Mounting
Ensure that the mounting wall is strong enough
to prevent it from vibration or failure.
Terminal block of indoor unit
To outdoor unit To outdoor unit
Cord clamp
L N S L N S
Electrical safety considerations prior to initial Installation
1. If there is a serious safety issue regarding the power supply, the installer should stop the installation of
the unit, fully explain the situation to the client and delay installation until the issue is resolved.
2. Power supply voltage should be in the range of 90% - 110% of the rated voltage.
3. Acircuit breaker and mains power switch 1.5 times capacity of the maximum current of the unit shall be
installed in the power circuit.
4. Ensure the air conditioner is earthed correctly.
5. Wire the unit in accordance with the attached Electrical Connection Diagramlocated on the inside of the
panel of the outdoor unit.
6. All wiring must comply with all relevant local and national electrical codes and shall be installed only by
suitably qualified and skilled electricians.
7. An all-pole disconnection device which has at least 3mm separation distance in all poles and circuit
breaker shall be incorporated in the fixed wiring according to the local and national wiring standards.
8. A separate dedicated circuit and single power outlet mustbe used for this system.
See the following table for suggested wire sizes and fuse specifications:
Electrical Connection
Correct orientation
of nstallation latei p
120 or
more to wall 120 or
more to wall
120 or
more to wall
150mm or more to ceiling
150mm or more to ceiling
Left rear side
refrigerant
pipe hole Ø65
835
140 110
Left rear side
refrigerant
pipe hole Ø65
Right rear side
refrigerant
pipe hole Ø65
Right rear side
refrigerant
pipe hole Ø65
Indoor unit outline
Indoor unit outline
120 or
more to wall 120 or
more to wall
Indoor unit outline
990 135
260
150mm or more to ceiling
Left rear side
refrigerant
pipe hole 65ØRight rear side
refrigerant pipe
hole 65Ø
HSNBR42 - 50
HSNBR32
HSNBR25
120 or
more to wall
750
180 110
Install the outdoor unit on a firm rigid base to prevent excess noise and vibration.
Set the direction of the unit to ensure optimal condenser air circulation.
If there is risk of exposure to strong prevailing winds such as in coastal applications, ensure
that the unit is placed at 90 degrees to the wind direction, or provide protection from the wind
by the use of shields.
In particularly windy applications, install the unit to prevent adverse interaction with the unit.
If mounting on a wall or structure, the installation bracket should be adequately sized to support
the unit fully. The installation wall should be solid brick, concrete or similar construction, or
action must be taken to reinforce and/or support the unit.
The connection between bracket, wall and unit should be firm, stable and reliable.
Make sure that no obstacles restrict the condenser air flow or block any heat radiation.
Strong
wind Strong
wind
Barrier
Incorrect Correct
Seal Drain joint Base pan hole
of outdoor unit
(A) (B)
The condensate drain joints differ slightly according to the
different size outdoor units in the range.
For the condensate drain joint with a seal (Fig.A), first fit the seal
onto the drain joint, then insert the drain joint into the base pan
hole of outdoor unit. Rotate joint 90 degrees to secure.
To install drain joint as shown in Fig.B, insert the condensate
drain joint into the base pan hole of outdoor unit until it clicks
in place. Connect the condensate drain joint with a drain hose
(provided by installer) to facilitate drainage of water produced
by the outdoor unit during heating mode.
CONDENSATE DRAIN INSTALLATION
OUTDOOR UNIT INSTALLATION PRECAUTIONS
REFRIGERANT PIPE CONNECTION
1. Cut the pipe with a suitable pipe cutter.
2. Place flare nuts on pipe after completing
burr removal, then flare the pipe.
3. Firmly hold the copper pipe in a suitably
sized die as shown in the table below.
.
.
Align the pipes to be connected.
Finger tighten the flare nut, then tighten
properly with a spanner and torque
wrench as shown.
Excessive torque can break the nut.
Outer diam.
(mm) A (mm)
Max. Min.
6.35 1.3 0.7
9.52 1.6 1.0
12.7 1.8 1.012.7
15.9 1.8
2.2 1.0
2.0
Bar
Copper pipe Clamp handle
Handle
Bar
Indoor unit pipe Flare nut Interconnecting
pipe
.
Outer
diam. Tightening
torque(N.cm) Additional tightening
torque(N.cm)
Ø6.35mm
Ø12.7mm
Ø15.9mm
Ø9.52mm
1500
(153kgf.cm) 1600
(163kgf.cm)
3500
(357kgf.cm)
4500
(459kgf.cm)
3600
(367kgf.cm)
4700
(479kgf.cm)
2500
(255kgf.cm) 2600
(265kgf.cm)
CHARGING, AIR PURGE AND TEST OPERATION
1. Remove the electrical control board cover from the outdoor unit byloosening the screw.
2. Connect the interconnecting cables to the terminals asidentified with their respectively matched
numbers and colours on the terminal blocks of indoor and outdoor units.
3. Secure the cableonto the control board with the cord clamp.
4. To prevent the ingress of water, loop theinterconnecting cable so that water cannot track along the
cable and enter the indoor and outdoor units.
5. Isolate any unused cables or wires correctly.Ensure that they cannot come into contact with any
other electrical components or metal parts.
Cover
Screw
Terminal block of outdoor unit
Liquid side: 6.35mmØ
R410A: (Pipe length-5)x20g/m
Liquid side: 9.52mm:Ø
R410A: (Pipe length-5)x40g/m
Refrigerant pipe length
Less than 5m
More than 5m
Air purging method
Vacuum pump
Additional amount of refrigerant required
Open the valve stem until it hits the valve
stopper. Do not try to open further.
Securely tighten the valve stem cap with
a spanner to help prevent leaks.
Valve stem cap tightening torque. See
Tightening torque table.
..
.
.
Flare nut
Stopper
Cap
Valve body
Valve stem
Vacuum pump
Make sure that any refrigerant added to the refrigeration system is added in liquid form to
ensure correct charging levels.
When relocating the unit to another place, use a vacuum pump to perform proper evacuation.
.
.
.
.The indoor unit and interconnecting pipe between the indoor and outdoor units must be leak tested
and evacuated to remove any non-condensables, contaminants or moisture from the system.
Check that each pipe (both liquid and gas side) between the indoor and outdoor units has
been properly connected and all wiring is complete and checked before testing.
Pipe length and refrigerant amounts:
Outdoor
unit Indoor
unit
Refrigerant
Packed valve Flare nut
Gas
Liquid
AC
D
B
1. Completely tighten the flare nuts, A, B, C and D, and
attach the manifold valve charge hose to a charge port
of the valve on the gas pipe side.
2. Then connect the charge hose to the vacuum pump.
3. Fully open the Low tap of the manifold valve.
4. Switch on the vacuum pump to evacuate the system.
After starting the pump, slightly loosen the flare nut of
the gas side valve, and check that air is entering.
(Operation noise of the vacuum pump changes and
the compound gauge indicates 0 instead of minus).
Re-tighten the flare nut and evacuate the system.
5. After the evacuation is complete, fully close the Low
tap of the manifold valve and switch off the vacuum
pump.
Evacuate for 15 minutes or more and check that
the compound gauge indicates -76cmHg (-1.0x10 Pa).
5
6. Turn the stem of the liquid line valve B about 45 counter-
O
clockwise for 6~7 seconds. After allowing gas to escape,
tighten the stem of the liquid line. Make sure that the
pressure displayed on the pressure gauge is slightly
higher than atmospheric pressure.
7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the Liquid and Gas valve stems B and A.
9. Securely tighten the cap of the valves.
Manifold valve
Compound meter
-76cmHg
Low tap Hi tap
Charge hose Charge hose
Vacuum pump
Pressure gauge
Gas side valve
Perform test operation after completing gas leak check at the flare nut connections and after an
electrical safety check.
Check that all piping and wiring have been properly connected.
Check that the gas and liquid side service valves are fully open.
1. Switch on the power, and press the ON/OFF button on the remote control to turn the unit on.
2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all of the unit functions
are operating correctly.
3. When the ambient temperature is lower than 17 C, the unit cannot be controlled by the
O
remote control to run in cooling mode, but manual operation can be employed. Manual operation
should only be used when the remote control is disabled or maintenance is necessary.
Hold the indoor unit front panel sides and lift up at an angle until the panels clicks and remains open.
Press the Manual control button to select theAUTO or COOL, the unit will now operate under Forced
AUTO or COOL mode (see User Manual for details).
4. The test operation should last for at least 30 minutes.
1.Airpurging
2.Using the Vacuum Pump
4.Test running
3.Safety and leakage check
A: Liquid line valve B: Gas line valve
C and D are the ends of indoor unit connecting pipes.
CAUTION
1. Soapy water method:
Apply a soapy water solution, directly to the indoor
and outdoor unit connections with a soft brush to check
for leaks at the connection points of the refrigerant pipe.
If bubbles are observed, a leak is present.
2. Leak detector
Use the leak detector to check for potential leaks.
O
U
T
D
O
O
R
U
N
I
T
ELECTRICAL CONNECTION - OUTDOOR UNIT
CAUTION
Indoor unit
check point D
B
C
A
Outdoor unit
check point
Cover
NOTE:
Angled Rough Burred
90O
Manual control bu tton
Connect the indoor unit first, then the
outdoor unit.
Do not allow the piping to be dislodged from the
back of the indoor unit.
Ensure that the condensate drain has a constant
fall to the outlet.
Insulate any condensate drain extensions.
Be sure that the drain hose is located at
the lowest part of the piping bundle. Locating it
on the upper side can cause drain tray to
overflow inside the unit.
Ensure that power wiring is routed separately
to any other wiring.
1. Pass the piping through the hole in the wall.
2. Hook the indoor unit onto the upper portion
of installation plate. Engage the indoor unit with
the upper edge of the installation plate. Ensure
the hooks are properly seated on the installation
plate by moving it left and right to check.
3. Positioning adjustment can be easily made by
propping the indoor unit with a cushioning material
between the indoor unit and the wall. Make sure
this is removed at completion.
4. Press the lower left and right hand sides of the
unit firmly against the installation plate until the
hooks engage with the relevant mounting slots.
CAUTION
Indoor unit installation
1. For left-hand or right-hand piping,
remove the pipe cover from the side panel.
2. For right rear and left rear pipe exits,
install the piping as shown.
NOTE: When choosing the condensate
drain connection side, please enure that the
condensate drain connection on the other
side (if applicable) is plugged. The condensate
drain shall be installed by a qualified installer. Right rear pipe exit
3. Bundle the pipes, connecting cables, and
condensate drain securely with tape, as
shown in Figure on the right.
Left rear pipe exit
Interconnecting pipe installation
Because the condensate water from
the indoor unit is collected in a tray
before flowing out, ensure that no foreign
objects are placed in the tray that may
cause a blockage.
I
N
D
O
O
R
U
N
I
T
To indoor unit To indoor unit
Cord clamp
L S
NL S
N
or
Condensate tray
Pipe cavity
Refrigerant pipes
Wrapping
Condensate pipe
Interconnecting
Cables

This manual suits for next models

3

Other Brivis Air Conditioner manuals

Brivis HSNBR25 User manual

Brivis

Brivis HSNBR25 User manual

Brivis L26 User manual

Brivis

Brivis L26 User manual

Brivis ICE DO-SC18Z9 Installation manual

Brivis

Brivis ICE DO-SC18Z9 Installation manual

Brivis Contour Series User manual

Brivis

Brivis Contour Series User manual

Brivis Reverse Cycle Inverter Hi-wall Air... User manual

Brivis

Brivis Reverse Cycle Inverter Hi-wall Air... User manual

Brivis HSNBT25 User manual

Brivis

Brivis HSNBT25 User manual

Brivis MON2H053 User manual

Brivis

Brivis MON2H053 User manual

Popular Air Conditioner manuals by other brands

Fujitsu ASYG 09 LLCA installation manual

Fujitsu

Fujitsu ASYG 09 LLCA installation manual

York HVHC 07-12DS Installation & owner's manual

York

York HVHC 07-12DS Installation & owner's manual

Carrier Fan Coil 42B Installation, operation and maintenance manual

Carrier

Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity IDUFCI60KC-3 installation manual

intensity

intensity IDUFCI60KC-3 installation manual

Frigidaire FAC064K7A2 Factory parts catalog

Frigidaire

Frigidaire FAC064K7A2 Factory parts catalog

Sanyo KS2432 instruction manual

Sanyo

Sanyo KS2432 instruction manual

LG MultiV Series installation manual

LG

LG MultiV Series installation manual

CLIMAVENETA a-CHD U-2T 606+2209 OPERATING AND INSTALLATION Manual

CLIMAVENETA

CLIMAVENETA a-CHD U-2T 606+2209 OPERATING AND INSTALLATION Manual

Midea EWK06CW5 user manual

Midea

Midea EWK06CW5 user manual

Pioneer FAB Series installation manual

Pioneer

Pioneer FAB Series installation manual

SPT WA-1511S user manual

SPT

SPT WA-1511S user manual

Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

Mitsubishi Electric

Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Mitsubishi Electric

Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic CS-S18HKQ Service manual

Panasonic

Panasonic CS-S18HKQ Service manual

Panasonic CS-E15NKE3 operating instructions

Panasonic

Panasonic CS-E15NKE3 operating instructions

Gree GWH18TC-K3DNA1B/I Service manual

Gree

Gree GWH18TC-K3DNA1B/I Service manual

Friedrich ZoneAire Compact P08SA owner's manual

Friedrich

Friedrich ZoneAire Compact P08SA owner's manual

Daikin R32 Split Series installation manual

Daikin

Daikin R32 Split Series installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.