Brivis B063047 User guide

Brivis Touch Controller
Installer Manual

1
Brivis Touch Controller Kit
Scope
Please read these instructions carefully before installing this
product. This manual covers the installation of the wall mounted
Brivis Touch Controller for the following Brivis applications:
GasDuctedHeating
Gas Ducted Heating & Refrigerated Cooling (Dual Comfort)
Evaporative Cooling
Zoning, including Brivis ZonePlus
For the installation of Brivis Heating and Cooling products please
refer to the equipment Installer Manuals.
This manual is based on Australian Standards - for all other
applications, please refer to relevant local codes and regulations.
Any deviations from these instructions may, at the discretion of
Brivis, void the warranty. As a result, the customer and/or installer
may be charged a fee for non-product warranty related call outs.
Also, note that failure to comply with these instructions may
preclude Brivis from being able to service the product.
Terminology:
Shall:Indicatesamandatoryrequirementofthismanual.
Should:Indicatesarecommendedrequirementofthismanual.
Disclaimer
IMPORTANT NOTICE: This document is a guide only. Laws, regulations and industry standards can
vary between States and Territories. Accordingly, this guide must be read in conjunction with, and
subjectto,alllaws,regulationsandindustrystandardsapplicablein theState or Territoryinwhich the
products are installed. You must ensure that the installation of the products will comply with
those laws, regulations and standards, and that the products recommendedtocustomersare
fitforthepurposeforwhichtheyareintended.
Table 1: Brivis Touch Controller Kit Brivis Part No. B063047
Contents and Description Qty
Brivis Touch Controller 1
Interface Module 1
Power Transformer 1
Power & Communication Loom 1
Plug & Screw Kit (for Brivis Touch) 1
Screw (for Interface Module) 2
Screw Driver 1
Inspect the product to ensure it matches your order. In the event of
damage or incorrect delivery, notify the supplier immediately. Brivis
accepts no responsibility for installation of damaged or incorrect
product.
Please read these installation instructions before undertaking the
installation process.
Specifications subject to change without notice.
Pictures for illustration purposes only.
© Brivis Climate Systems Pty Ltd 2016
The Brivis Touch Controller is compatible with selected Brivis
units only. For information on compatibility please contact Brivis.
Pre-2010 compatible Brivis heaters will have limited on-board
diagnostics.

2
TableofContents
1.0 Home Screen – Key Functions .................................................4
2.0 Brivis Touch Controller Installation..........................................5
2.1 Location of the Brivis Touch.....................................................5
2.2 Location of the Interface Module..............................................6
2.3 Install the Brivis Touch .............................................................6
2.5 Install Interface Module.............................................................7
2.6 Connection of Interface Module to P&C Loom ........................8
2.7 Connection of Interface Module to Appliance..........................9
3.0 System Setup.............................................................................9
3.1 Turning the System ON.............................................................9
3.2 Set Day/Time............................................................................10
3.3 Installer Setup..........................................................................11
3.4 Reset Networker ID..................................................................12
3.5 Networker Parameters.............................................................13
3.6 Cooler Parameters...................................................................13
3.7 Heater Parameters...................................................................13
3.8 System with no Zones.............................................................13
3.9 System with Zones (Inc. Brivis ZonePlus) ............................. 14
3.10 System Operation..................................................................14
3.11 Service Notification Message ...............................................14
3.12 Outdoor Temperature Sensor (Optional)..............................15
4.0 Product and Warranty Registration ........................................15
5.0 Instruct Home Owner on System Operation...........................15
6.0 Troubleshooting.......................................................................16
6.1 Power Outages.........................................................................16
7.0 Appendix ..................................................................................17

3
Definitions
Brivis Networker
Networker is a term used for a temperature sensing or
communicating device which communicates over two-wire bus.
There can be only one Master Networker (n01), all others must be
slaves (n02, n03 ….n10).
Brivis Touch Controller
Primary user interface with touchscreen display. Where multiple
Brivis Touch Controllers are installed, the “Master” Brivis Touch
Controller can be identified by the letter “M” displayed in the
bottom right hand corner of the screen. The Master has default
sensor identification “n01”.
The Brivis Touch Controller is a touchscreen thermostat which
communicates over two-wire bus. It is compatible with NC-3, NC-6
and N-T1 sensors.
Brivis NC-6 Networker Controller
A user interface with LCD display. The NC-6 has default sensor
identification “n01 ID00:1” (Master) and should be changed to a
slave if used on the same system as the Brivis Touch Controller.
Brivis NT-1 Remote Temperature Sensor
Zone temperature sensor with an LED that blinks during
communication with Master Brivis Touch Controller. Default NT-1
sensor identification is “n02”. Additional Brivis Touch Controllers
can be used in place of up to 3x NT-1 sensors. The NT-1 sensor
can also be used as the outdoor temperature sensing device.
Zone
One room or a group of rooms; normally selected on the basis of
usage or that have similar heating or cooling needs.
ControlledZone
A zone that is separately controlled by its own zone sensor and
zone damper. There are as many zone sensors in the home
comfort system as there are Controlled Zones.
CommonZone
A zone that is not separately controlled by its own sensor and zone
damper. It operates whenever heating or air conditioning is on,
regardless of the status of any controlled zones.
Constant Zone
A predetermined zone, typically the largest and containing the
return air grille, is designated as the Constant Zone. The Constant
Zone functions as a Common Zone only during refrigerated cooling
mode to ensure the minimum cooling airflow requirements are met.
MultiTemperatureSetPoint(MTSP)System
The zone temperature set point can be set independently across
all Touchscreens and/or Temperature Sensors.
Single Temperature Set Point (STSP) System
The zone temperature set point is the same across all
Touchscreens and/or Temperature Sensors.

4
1.0 Home Screen – Key Functions
Diagram 3
:
Evaporative Cooling Home Screen
Manual or Schedule
Operation
* Active
with MTSP & STSP
systems only
D
iagram 1:
Heating Home Screen
Flame
Symbol
Power
Zones Where
Fitted
*
Mode Indicator
Adjust Set
Temperature
Indoor
Temperature
Fan Status
Indicator
Day
Digital
Clock
M - Master
Controller
System Mode
(HEAT/COOL/EVAP)
Menu – Display
Options or Settings
Fan Select
Mode
Diagram 2:
Add-On Home Screen

5
2.0 Brivis Touch Controller Installation
The Brivis Touch Controller is connected to a compatible Brivis
appliance through the Interface Module. A 20m, four core, Power
& Communication Loom (P&C Loom),connects the Brivis
Touch Controller to the Interface Module. The Power
Transformer (12VDC) supplies power to the Interface Module.
Diagram 4: Connection Diagram
To connect the Brivis appliance to the Brivis Touch:
1. Determine location of the Brivis Touch.
2. Determine location of the Interface Module.
3. Install the Brivis Touch.
4. Install Interface Module.
5. Connect Interface Module to Appliance.
2.1 Location of the Brivis Touch
For proper operation the Brivis Touch must accurately monitor the
temperature in the space it controls.
Guidelines:
The Brivis Touch should be mounted:
Approximately 1.5m above floor level (ensure hole into wall
cavity is properly sealed).
Close to the centre of the living space on an internal wall.
On a section of wall that does not contain pipes, electrical wires,
antenna cables or ductwork.
The Brivis Touch should NOT be mounted:
Where it is exposed to direct sunlight or other heat sources
which may cause a false reading.
Near or in the path of supply air outlets or return air grilles.
On outside walls, near windows or doors leading to outside.
In areas with poor air circulation such as recesses or behind
doors.
Note:
Do not install the wiring with the power turned on, as the
fuse may blow, which
is
not be covered under warranty.
Note:
When there are multiple Brivis Touch Controllers on a
system, always ensure that the location of each is within 20m
of the Interface Module
Power & Communication
Loom, 20m (supplied)
0.75mm² figure-8 cable
(field supplied)
Appliance
(field supplied)
Power Transformer
12VDC 1.5m loom
(supplied)
Brivis
Touch
(supplied)
TW2
TW1
Interface
Module
(supplied)
Isolation
Switch
(field supplied
GPO)

6
2.2 Location of the Interface Module
The Interface Module shall be located within 1.5m of a 10 Amp
240 volt fixed switched socket outlet. The Brivis Touch shall be
within 20m of the Interface Module.
2.3 Install the Brivis Touch
The Brivis Touch Backing Plate must be installed prior to
mounting the Brivis Touch.
To mount the Backing Plate do the following:
1. Remove the Brivis Touch Backing Plate from the packaging.
2. Use Backing Plate as a template and mark the two Mounting
Hole centres and the Loom Access hole centre, refer to
Diagram 5.
3. Install the supplied wall Plug Kit in the Mounting Hole
locations. For drill sizes refer to Diagram 5.
4. Fasten Backing Plate with wall Plug Kit screws.
Diagram 5: Brivis Touch “Backing Plate”
To mount the “Brivis Touch”:
1. Run the supplied P&C Loom from the Touch to the
Interface Module.
2. Draw the loom from the wall cavity and feed through the
P&C Loom Access opening on the Touch Backing
Plate.
3. Connect the P&C Loom terminal (female) to the Touch
terminal (male) before mounting it on the wall, refer to
Diagram 6.
4. Push excess cable back into the wall cavity and mount
Touch onto the Backing Plate. The three Male Clips on
the Backing Plate will engage and secure the Touch,
refer to Diagram 7.
Diagram 6: Brivis Touch Controller P&C Loom Connection
Mounting Hole
Drill size
ø
6.0mm
Mounting Hole
Drill size ø6.0mm
P&C
Loom
Access
Drill size ø13
2
3
1

7
Diagram 7: Mounting Brivis Touch to Backing Plate 2.5 Install Interface Module
The Interface Module facilitates communication between the
Brivis Touch and the Brivis appliance(s) through the P&C Loom,
and is capable of connecting up to four Brivis Touch units.
The Interface Module requires a 12VDC power supply from the
Power Transformer.
The Interface Module also has an “Isolation Switch”; a red
“Status L.E.D” indicates it is ON, refer to Diagram 8.
Diagram 8:Mounting Interface Module Power & Communication
Loom Connection,
(Any of the four ports)
Transformer
connection
Isolation
switch
Status
L.E.D
2-wire bus
connection
TW1
TW2
TW1
TW2
Male Clips

8
To install the Interface Module:
1. Position in an environmentally protected area where the
temperature does not exceed 70°C.
2. Locate within 1.5m of a 10 Amp 240 volt fixed switched socket
outlet.
3. Distance from Interface Module to Brivis Touch shall be no
more than 20m.
4. Mount with supplied screws as shown in Diagram 9.
Diagram 9: Mounting Interface Module on flat surface
2.6 Connection of Interface Module to P&C Loom
The Interface Module is capable of connecting up to four
Brivis Touch Controllers. The P&C Loom can be connected
to the Interface Module through any of the four ports, refer to
Diagram 10.
Diagram 10: Connection of Interface Module to P&C Loom

9
2.7 Connection of Interface Module to Appliance
The Interface Module has four terminal points for the
connection of the Brivis Appliance control wires TW1 &
TW2. When connecting to an appliance, use only the first
set (Set 1) of two terminals or the second set (Set 2).
Never use a mixed combination of terminals when
connecting to a single appliance. For example, a Brivis
Touch operating a Brivis Evaporative Cooler and a Brivis
Gas Heater may have the two right terminals connected
to the Heater (SET 1) and the two left terminals connected
to the Evaporative Cooler (SET 2), refer to Diagram 11.
Diagram 11: Connection of Interface Module to Appliance
For more information regarding appliance connection please
refer to the product installation manual supplied with the
appliance.
3.0 System Setup
3.1 Turning the System ON
Once the system is fully connected, it can now be turned ON in the
following sequence:
1. Mains power to heater 516 Zone Module (if connected).
2. Mains power to Heater / Evaporative Cooler / Refrigeration
appliance(s).
3. Mains power to Interface Module.
Press isolation switch on Interface Module (L.E.D on).
Once completed the Brivis Touch Controller will power up and you
will be prompted to enter the day and time.
Note:
When there is more than one Brivis appliance connected to
the Interface Module ensure that the TW1 & TW2 polarity is
correct at both ends of the 2
-
wire bus cable.
Note:
Do not install any wiring with the power turned on, as the
fuse may blow, which would not be covered under warranty.
TW1
TW
2
TW1
TW
2
To Heater
To Evaporative
Cooler
SET 2
SET 1
Note
: Once you access the MENU Screen and select a
configuration option, if no button is pressed for 60 seconds while
in that configuration screen, the Touch will exit the configuration
mode and return to normal operation; this applies to all options
other than SCHEDULE.

10
3.2 Set Day/Time
To access and modifythe day and time do the following:
1. Identify the Master Controller; it has an ‘M’ in the bottom right hand
corner on the home screen. Press on the home screen, top
right hand corner, refer Diagram 12.
Diagram 12: Home screen in the OFF state
2. Press on the MENU screen, refer Diagram 13.
Diagram 13: MENU Screen
3. The MENU > SET DAY/TIME screen will appear, refer Diagram 14.
To modify either the day or the time press the buttons
adjacent to the time and day.
Diagram 14: Set the Day and Time
4. When complete press to save and you will return to the
MENU screen, refer Diagram 13 or the home screen, refer Diagram
12, when system is first started. Press to return to the home
screen, Diagram 12.
When the system is first powered up the ‘MENU > SET DAY/TIME’
screen will appear, refer Diagram 14. If more than one Brivis
Touch Controller is installed the ‘MENU > SET DAY/TIME’ screen
will appear for all. Set the correct day and time on the assigned
Brivis Touch Master Controller and then press ‘Done’. For all
other Brivis Touch Controllers press ‘Done’ as they will need to be
converted to a SLAVE Controllers.

11
3.3 Installer Setup
Interconnection of Brivis Heating and/or Cooling appliance(s) shall
be complete prior to entering INSTALLER SETUP. If your system
contains one Brivis Touch, one heater (no zoning) and/or one
evaporative cooler no network parameters need to change.
To enter installer setup, enter PIN 5240 and press ‘OK’, refer
Diagram 15.
Diagram 15: Brivis Touch INSTALLER SETUP
When accessing the CUSTOM SETUP screen through the Master
Brivis Touch Controller the following options may be available,
and is dependent on connected appliances.
1. Reset the identification of the Brivis Touch Controller (only
required if more than one Brivis Touch Controller is fitted).
2. Access the installer parameters (system functionality).
3. Access the evaporative cooler installer parameters if an
evaporative cooler exists on the system.
4. Access the heater installer parameters if a heater exists on the
system, refer Diagram 16.
Diagram 16: Master Brivis Touch Controller CUSTOM SETUP
Note
: If multiple
Brivis Touch Controllers
are installed, only the
Master Controller has the ability to set the day and time. The Master
Controller can be identified by the letter "M" in the bottom right hand
corner on the home screen.

12
When accessing the CUSTOM SETUP screen through a Slave
Brivis Touch Controller the following option will be available.
1. Reset the identification of the Brivis Touch Controller, refer
Diagram 17.
Diagram 17: Slave Brivis Touch INSTALLER SETUP
3.4 Reset Networker ID
On either the Master Brivis Touch Controller or Slave Brivis
Touch Controller, pressing Reset Networker ID, refer Diagram
17, initiates a prompt to confirm clearing of its identification
(address), refer Diagram 18. Accepting this change clears the unit
identification and the Brivis Touch Controller is forced to restart.
Upon restarting the user is prompted to set the new identification
number as shown in Diagram 19. The unit identification number
shall be in the range from 1 to 10 inclusive, and once entered
press BACK to save and return to INSTALLER SETUP Screen.
Diagram 18: Confirmation to prompt ID change
Diagram 19: Set Networker Address

13
3.5 Networker Parameters
The ‘NETWORKER PARAMETERS’ section in the Master Brivis
Touch Controller provides access to all Networkers connected to
the system. This may range from n01 through to n10 if installed,
refer Diagram 20.
Diagram 20: All Networkers on the system
Accessing ‘n01 – Master Brivis Touch Controller
Press the ‘n01 – Master Networker’ button to gain access to:
-Zoning parameters for Add-On Cooling, Heating and
Evaporative Cooling systems.
-Fan scaling parameters for Add-On Cooling and Heating
systems.
-MTSP parameters for Add-On Cooling and Heating systems.
Refer to the appendix for a detailed list of the available Master
Networker parameters.
Accessing ‘n02 to n09 – Slave Controllers’
Press the ‘n02 – Slave Networker’ button through to ‘n09 – Slave
Networker’ (if available) to gain access to the parameters for each
Slave Controller.
Accessing ‘n10 – Outdoor Sensor’
This is the designated address (n10) for the outdoor sensor, if
connected.
3.6 Cooler Parameters
The Cooler parameters allow you to change the unit identification
number for zoning applications and other parameters depending
upon the model. For more information refer the product installation
manual supplied with the appliance.
3.7 Heater Parameters
The Heater parameters allow you to change the unit identification
number, high and low fan speeds, thermistor set point and zoning
requirements. For more information refer the product installation
manual supplied with the appliance.
3.8 System with no Zones
Some systems do not require ‘n01’ parameters to be changed, the
only requirement is to install the appliance(s), turn system power
ON, set the day and time on the Brivis Touch Controller and
press the ON/OFF button to start the system. This applies to
systems with no zoning and include:

14
-One Brivis Gas Ducted Heater
-One Brivis Gas Ducted Heater + one Evaporative Cooler
-One Brivis Gas Ducted Heater + one Add-On
3.9 System with Zones (Inc. Brivis ZonePlus)
For systems installed with zones, the Brivis Touch Controller
parameters need to be changed. The appliance cannot be started
until all system zoning parameters have been programmed. Once
the zoning parameters have been programmed the system may be
run in either Manual or Schedule mode. For specific appliance
installation parameters refer to the relevant appliance installation
manual and appendix contained within for zoning parameters.
Refer to Brivis ZonePlus manuals for detailed information on
STSP or MTSP systems or contact Brivis Technical Support.
3.10 System Operation
Instruct the home owner on system operation including:
System design – MTSP or STSP
Zone identification
Minimum / maximum no. of simultaneous zones for design
conditions for Heating and Cooling (if fitted)
Common Zone operation (if applicable)
Constant Zone operation (if applicable)
Operating the system in manual mode
Auto Operation – programming the Comfort Schedule
3.11 Service Notification Message
When the operating hours logged for an appliance exceeds the
predetermined period, the Brivis Touch Controller displays the
following:
Diagram 21: System Alert
Pressing the “ ” icon will result in the following message being
displayed for either Heater or Evap Cooler fan run hours above
limit, refer Diagram 22.
Note
: For Add-On Refrigerated Cooling connection, heater
parameters (H01) must be programmed.
The
S
panner
icon appears flashing
at one second intervals.
The “ ” icon is displayed with the Alert text flashing
at one second intervals.

15
Diagram 22: Fan run hour limit
The owner can book a service call or clear the spanner icon
notification by pressing the “Clear”button
3.12 Outdoor Temperature Sensor (Optional)
The Brivis Touch Controller can display the ambient (outdoor)
temperature. To enable, install a Brivis NT-1 Remote
Temperature Sensor and set the JUMPER position to “AMB” (see
Diagram 23). Connect the NT-1 to the 2-wire bus (TW1 & TW2).
The most accurate way of reading the ambient temperature is to
install the NT-1 sensor under the eaves on the south side of the
home away from potential heat sources.
4.0 Product and Warranty Registration
Brivis recommends the registration of all products to ensure
efficient product support if and when required. Please inform the
home owner that product registration can be completed either:
on-line at brivis.com.au
or via the registration form in the product Owner’s Manual (e.g.
Brivis Heater Owner’s Manual)
5.0 Instruct Home Owner on System Operation
System design conditions
MTSP or STSP (if fitted)
Zone identification
Minimum / maximum no. of simultaneous zones for design
conditions for Heating and Cooling
Common Zone operation (if applicable)
Constant Zone operation (if applicable)
Manual Operation
Schedule (Auto) Operation
Diagram
2
3
: NT-1

16
6.0 Troubleshooting
The Brivis Touch Controller comes with in-built diagnostics to
assist in determining the cause of a fault
With some faults the system will attempt to automatically restart,
often several times
Critical faults, where the equipment cannot automatically restart,
will require a service call
Refer to the Troubleshooting section of the Brivis product
Installer Manual for specific equipment related issues before
calling for service
6.1 Power Outages
If power is restored within 10 minutes of a power outage, the
Brivis Touch Controller will resume normal operation with the
mode and settings immediately before the outage.
When powered OFF, the controller will retain its Day and Time
setting for up to 5 days.

17
7.0 Appendix
Parameter ID
Number and
Value (default)
Installer Parameter Description Installer Parameter
Value Settings
Please record
the values you
have set
n01 ID00:0 Networker Address or Number Master = 1; Slave ≥ 2
n01 ID01:1 Refrig Common Zone - Enable Refrig/Heater ID No.
n01 ID02:1 Refrig Common Zone - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID03:0 Refrig Zone A - Unit Refrig/Heater ID No.
n01 ID04:0 Refrig Zone A - Relay Relay No. 1 to 4
n01 ID05:1 Refrig Zone A - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID06:0 Refrig Zone B - Unit Refrig/Heater ID No.
n01 ID07:2 Refrig Zone B - Relay Relay No. 1 to 4
n01 ID08:1 Refrig Zone B - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID09:0 Refrig Zone C - Unit Refrig/Heater ID No.
n01 ID10:3 Refrig Zone C - Relay Relay No. 1 to 4
n01 ID11:1 Refrig Zone C - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID12:0 Refrig Zone D - Unit Refrig/Heater ID No.
n01 ID13:4 Refrig Zone D - Relay Relay No. 1 to 4
n01 ID14:1 Refrig Zone D - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID15:1 Heating Common Zone - Enable Heater ID No.
n01 ID16:1 Heating Common Zone - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID17:0 Heating Zone A - Unit Heater ID No.
n01 ID18:1 Heating Zone A - Relay Relay No. 1 to 4
n01 ID19:1 Heating Zone A - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID20:0 Heating Zone B - Unit Heater ID No.
n01 ID21:2 Heating Zone B - Relay Relay No. 1 to 4
n01 ID22:1 Heating Zone B - Temperature Sensing ID No. Sensor No. 1 to 4
Table 2
: Master Controller Parameters

18
Parameter ID
Number and
Value (default)
Installer Parameter Description Installer Parameter
Value Settings
Please record
the values you
have set
n01 ID23:0 Heating Zone C - Unit Heater ID No.
n01 ID24:3 Heating Zone C - Relay Relay No. 1 to 4
n01 ID25:1 Heating Zone C - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID26:0 Heating Zone D - Unit Heater ID No.
n01 ID27:4 Heating Zone D - Relay Relay No. 1 to 4
n01 ID28:1 Heating Zone D - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID43:0 Heating - OFF Cycle Circulation Fan Operation 0 = OFF; 1 = ON
n01 ID92:0 Multi Set Point Control - Enable 0 = OFF; 1 = ON
n01 ID93:1 Refrig - Cooling Zone to Force Open 0 = None; 1=A; 2=B; 3=C; 4=D
n01 ID105:0 Heating - Enable Fan Scaling 0 = OFF; 1 = ON
n01 ID106:1 Heating - Common Zone Fan Speed Range = 1 to 16
n01 ID107:1 Heating - Zone A Fan Speed Range = 1 to 16
n01 ID108:1 Heating - Zone B Fan Speed Range = 1 to 16
n01 ID109:1 Heating - Zone C Fan Speed Range = 1 to 16
n01 ID110:1 Heating - Zone D Fan Speed Range = 1 to 16
n01 ID111:0 Refrig - Enable Fan Scaling 0 = OFF; 1 = ON
n01 ID112:1 Refrig - Common Zone Fan Speed Range = 1 to 16
n01 ID113:1 Refrig - Zone A Fan Speed Range = 1 to 16
n01 ID114:1 Refrig - Zone B Fan Speed Range = 1 to 16
n01 ID115:1 Refrig - Zone C Fan Speed Range = 1 to 16
n01 ID116:1 Refrig - Zone D Fan Speed Range = 1 to 16
Table
2
: Master Controller Parameters
Cont’d

19
© Brivis Climate SystemsPty. Ltd. 2016.
All rightsreserved. No part of thesedocuments may be used in anyway orform without priorwritten consent fromBrivis Climate Systems Pty Ltd.
Brivis Australia
61 Malcolm Rd
Braeside Victoria 3195
Australia
1300 BRIVIS (1300 274 847)
Fax: +61 (03) 9264 9400
www.brivis.com.au
email: sales@brivis.com.au
Brivis New Zealand
Distributor: Warm Air Ltd
69 Marsden Street
Lower Hutt 5010 New Zealand
PO Box 38523
Wellington Mail Centre
Wellington 5043 New Zealand
0800 WARMAIR (0800 9276 247)
Ph: +64 (04) 920 1670
Fax: +64(04) 920 1681
www.warmair.co.nz
Brivis South Africa
Distributor: Lorenz and Associates
Northlands Deco Park
Cnr Witkoppen and Newmarket Roads
North Riding, Johannesburg South Africa 2194
0861 BRIVIS (0861 274 847)
Ph: +27 (011) 704 6112
Fax: +27 (011) 704 0022
www.brivis.co.za
For all your Sales and Service enquiries call us on 1300 BRIVIS (1300 274 847)
www.brivis.com.au
Part Number: B063217
February2016
Brivis Climate System PtyLtd
ABN64096079088
AU24752