BroadAccess PSBC12 Series User manual

P/N 760-0000331 Rev C December 2005 Page 1
000331c.doc 18-Dec-05 2:30 PM
BroadAccess
Installation Instructions
PSBC12XX Charger
Description
The PSBC12XX charger is a power supply unit installed in outdoor/indoor
cabinets or standard 19” racks, which is used for charging batteries and powering
equipment directly. Overcurrent and overvoltage protection is provided to prevent
damage that might be caused by a faulty battery and/or external load. Temperature
compensation is employed to enhance battery life.
The PSBC12XX charger supports battery sets, which are charged as long as AC
power is on. When AC power is off, the batteries supply current directly to the
load.
If alarm monitoring, event logs or detailed PSBC12XX charger parameters are
required, the PSM1006 GUI software supplied with the PSBC12XX charger can
be installed on a PC which connects to the PSBC12XX charger controller. For
more information, refer to the BroadAccess PSBC 12XX-X Charger Management
Software User Guide.
Table 1. PSBC12XX Charger - Features
Power
Supply
(VDC)
Max No. of
Rectifiers Battery Sets
Supported Input
Voltage
(VAC)
Output
Voltage
(VDC)
Current Output Per
Rectifier Module
48 5 285-275 54 12A at 230 Vac input
Compatibility
The PSBC12XX charger is suitable for use with BroadAccess systems Ver 40
Release 3.0 and higher, or cabinets adapted for this charger.
Charger Controls and Indicators
PSBC12XX charger front panel controls and indicators are shown in Figure 1 and
described in Table 2.
Table 2. Front Panel Components
Designation Description Function
Mounting
Brackets - Enables mounting of chargers in cabinets and racks
Rectifier
Modules 1 to 5
rectifiers Convert AC power to DC power. The modules operate in
parallel in “N+1” configuration. Each rectifier supplies
12A/600W. The rectifiers are capable of load sharing.

Charger Controls and Indicators
Page 2 December 2005
P/N 760-0000331 Rev C
Designation Description Function
Controller
Module - Measures and monitors voltages, currents, power,
temperature, battery parameters and other data. Enables
remote monitoring through a RJ-45 connector.
Load
Distribution
Module
- Contains the following circuit breakers:
No. 1 - two outputs in parallel
No. 2 - two outputs in parallel
No. 3 - one output
No. 4 - one output
Output Current
Bar Graphs - Verifies current sharing operation and indicate the
percentage of full load at each rectifier.
Handles - Used for pulling out or pushing in rectifier
modules/controller.
Mounting Bracket
Rectifier Module
Handle
Load Distribution Module
Mounting Bracket
Controller Module
Output
Current Bar
Graphs
Blank Filler
Plate RJ-45
Connector
Figure 1. PSBC12XX Charger Front Panel

BroadAccess PSBC12XX Charger - Installation Instructions
P/N 760-0000331 Rev C December 2005
Page 3
Items on the rear panel are shown in Figure 2 and described in Table 3.
Table 3. Rear Panel Components
Designation Description Function
Temperature
sensors 2 temperature sensors Sense external temperature
Load connectors 6 load terminals Connects load to PSBC12XX charger
Alarm connector Alarm D-type 9 pin
connector PSBC12XX charger alarm signaling
AC cord Connection to AC power supply
Ground terminal Ground
Battery terminals 2 sets of battery
terminals Connects batteries to PSBC12XX charger
Temperature
Sensors
AC Cord
Alarm
Connector
Load
Connectors
Ground
Terminal Battery
Terminals
Figure 2. PSBC12XX Charger Rear Panel

Parts Required
Page 4 December 2005
P/N 760-0000331 Rev C
Parts Required
Warning: The AC line must be protected by a 32A “D” type circuit breaker.
Warning: Each battery set must be protected by a 50A “C” type circuit breaker.
Before commencing installation, unpack and identify all parts listed in Table 4.
Table 4. PSBC12XX Charger Installation Part List
Item Part Description Quantity
1 Alarm cable 1
2 Load cable Up to 6
3 Battery cables Up to 2
4 Temperature sensor cable Up to 2
5 RS-232 cable or Ethernet 1
Tools Required
The following tools are required for installation:
•Phillips screwdriver
Installation
Note: Ensure that ventilation around the unit is adequate. Allow at least 50 mm of
clearance on both front and rear side to enable free air flow through the unit's
ventilation holes.
1. From rack front, position the unit at the required height, taking into account
other cages to be placed in the rack.
2. Insert and tighten all four bolts securing PSBC12XX charger to rack.
Cable Connections
Caution: Use caution when routing wires and cables. Avoid severe bending and routing
over sharp edges. Use grommet material when possible to avoid wear to cable
insulation.
Warning: Insulated cable terminals must be used for the connection of loads and battery to
the output and alarm terminals.

BroadAccess PSBC12XX Charger - Installation Instructions
P/N 760-0000331 Rev C December 2005
Page 5
1. Connect the ground cable from the outdoor cabinet to the PSBC12XX charger
ground terminal.
2. Place temperature sensors near the batteries in the battery compartment. Route
the sensor cable to the PSBC12XX charger and connect sensor cable connector
to the PSBC12XX charger rear panel temperature sensor connectors.
Note: Instructions for routing the temperature sensor through the cabinet to the
batteries appear in the installation instructions provided with the cabinet.
3. Connect alarm cable connector to PSBC12XX charger rear panel alarm
connector. Route cable and connect to MDF distribution blocks external alarms
terminal as required.
4. Connect the battery sets to the PSBC12XX charger rear panel battery terminals
using the battery cables as follows:
Red cables to + terminals on PSBC12XX charger and batteries
Black cable to - terminals on PSBC12XX charger and batteries
5. Connect loads to the PSBC12XX charger rear panel load connectors using the
load cables as follows:
Load 1 (usually Cage 1):
♦Red cable: from load + terminal to PSBC12XX charger load
terminal 1 (red)
♦Black cable: from load - terminal to PSBC12XX charger load
terminal 1 (black)
Load 2 (usually Cage 2):
♦Red cable: from load + terminal to PSBC12XX charger load
terminal 2 (red)
♦Black cable: from load - terminal to PSBC12XX charger load
terminal 2 (black)
Load 3 (usually outdoor cabinet roof fan):
♦Red cable: from load + terminal to PSBC12XX charger load
terminal 3 (red)
♦Black cable: from load - terminal to PSBC12XX charger load
terminal 3 (black)

Maintenance
Page 6 December 2005
P/N 760-0000331 Rev C
Load 4 (usually spare):
♦Red cable: from load + terminal to PSBC12XX charger load
terminal 4 (red)
♦Black cable: from load - terminal to PSBC12XX charger load
terminal 4 (black)
6. Connect the communication cable (RS-232 or Ethernet as required) RJ-45
connector to the PSBC12XX charger controller module RJ-45 connector and
route cable to the side so that is is ready for connection to a BroadAccess cage
(Ethernet), PC COM port (RS-232) or modem as required.
Warning: The PSBC12XX charger operates on 85-275 Vac. Ensure that the PSBC12XX
charger is plugged into an appropriate voltage supply protected by a 32 A circuit
breaker.
7. Plug the AC input cord into the mains and verify that the display in the
modules come on.
8. Verify that the controller panel is operating.
9. Verify that no controller panel red LEDs are ON.
10.Switch on the load distribution panel CAGE-1 and CAGE-2 circuit breakers in
accordance with your load configuration.
Maintenance
Warning: High voltage exists inside the PSBC12XX charger. Removal of the PSBC12XX
charger cover must be performed only by an authorized technician.
Warning: Certain PSBC12XX charger parts may reach high temperatures. Handle with
extreme care after prolonged operation.
Module Replacement
The following modules can be easily removed and replaced (hot insertion) if
faulty:
•controller
•rectifiers
Table of contents
Popular Batteries Charger manuals by other brands

Motorola solutions
Motorola solutions Curve Series user manual

ATOMI
ATOMI Qi Wireless Charge Stand user manual

Sterling Power Products
Sterling Power Products BB12120 Handbook

Parkside
Parkside PAP 20 A1 Translation of the original instructions

Husqvarna
Husqvarna 40-C80 Operator's manual

APLIC
APLIC 303104 user manual