
11111924-01 - 2/23
8HE Multiple Boiler Application Instructions
2Venting (continued)
2.4 Determine the input required to the system. See
Section 1.3 and Table 1-2.
2.5 Individual Vents
Individual vents are highly recommended if
the job site conditions allow. Individual vents
are particularly useful in boiler rooms having
a low ceiling height. Individual vents are easy
to design and in many cases result in the
lowest installed cost. They also are the most
dependable in operation and less susceptible to
condensation than are combined vents.
Install individual vents per National Fuel Code -
ANSI Z223.1/NFPA 54.
2.6 Common Vents
See Section 2.1, "Avoiding Flue Gas
Condensation", and see Figures 2-3 through 2-8
and Table 2-9.
Combined vents will perform satisfactorily if strict
design procedures are followed. Referring to
Table 2-10, note that a connector rise of at least
one foot is required. Where the vent dampers are
mounted vertically, include damper height in the
connector rise. A connector rise of three feet is
desirable.
Keep horizontal laterals as short as possible.
Place the first boiler as close to the chimney as
practical.
The horizontal vent manifold is an extension of
the vertical common vent.
2.6.1 Common Vent Sizing
Size the common vent CV per Table 2-9. Note
that the CV diameter applies to both the chimney
and the vent manifold / lateral.
Size the vent connector diameter CN per Table
2-10.
If a tapered or graduated manifold vent is
desired, use the same procedures above for
sizing the intermediate manifold diameter
but for the total input of the boilers served by
intermediate tapered or graduated manifold
vent.
Within Table 2-9 are several entries of NR.
This means that the combination involved is
not recommended. The most common reason
for a combination to be designated NR is that
condensation inside the vent pipe is likely to
occur. This is particularly true of single wall vent
pipe.
If a masonry chimney is desired, the minimum
cross sectional area of the chimney is found in
Table 2-11 as a function of the vent diameter.
Confirm adequate ceiling height. Referring to
Table 2-10, note that a connector rise of at least
one foot is required. Where the vent dampers are
mounted vertically, include damper height in the
connector rise. A connector rise of three feet is
desirable. Thus, to make the desired connector
rise and have space for the manifold vent, the
minimum boiler room ceiling height must be
equal to:
32½ in. Boiler Height
+ D Drafthood Height
+ F Minimum Connector Rise (include the
height of vertically mounted vent
dampers)
+ CV Manifold Diameter
+ 6 in. Clearance
= Minimum Ceiling Height
If the minimum ceiling height above is not
available, common vents will not perform
satisfactorily and should not be used.
2.6.2 Example of Common Venting:
Start with the previous example of a 3 story
apartment building that will use five 806HE and
one 805HE boiler.
For a common vent layout as shown in Figure
2-3 use Table 2-9 to find the common vent size,
CV, at 1734 MBH input. Common Vent required
is 15 ft. high, 18 in. Diameter Double Wall. Single
Wall Vent is Not Recommend.
Find vent connector using Table 2-10. For Type
B connectors with 3 ft. rise, 805HE uses 8 in.
diameter and 806HE uses 9 in. connector.
Calculate minimum ceiling height.
32½ in. Boiler Height
+ 27 13/16 in. Height to Outlet of Drafthood, D
+ 36 in. Desired Conn. Rise, F (incl. damper hgt)
+ 18 in. Manifold Diameter, CV
+ 6 in. Clearance
~ 10 ft.1 in. Minimum Ceiling Height
An eleven foot clear ceiling height will work. With
only one elbow, no correction is necessary. The
design of a constant diameter manifold vent is
complete. Mark these vent and connector sizes
on the drawing of the boiler room.