
5
Carlin Combustion Technology MN70200B 101323
PRESS THE BUTTON TO VIEW DIFFERENT SETTING MODES
Pre-Purge* Trial for
Ignition Post-Purge Flame
Stabilize
CAD
Ohms
Max
Ignition
Type
TT
Jumpered
Internally**
Vent
Input
Allowed
Recycles
Alarm
Contacts
Clear
Fault
History
Restore
Factory
Defaults
PRESS THE
BUTTONS
TO
CHANGE
SETTINGS
No Valve 10 Sec†† 0 Sec 5 Sec 3300 Interrupted Yes Not Used None N/O Yes Yes
0 Sec†15 Sec 10 Sec 10 Sec 5300 Smart Ign No Intake 3 N/C No No
3 Sec†30 Sec 15 Sec 15 Sec 7200 Intermittent Exhaust
10 Sec 45 Sec 30 Sec 30 Sec
15 Sec 2 min 45 Sec
30 Sec 5 min
60 Sec 15 min
2 min
Shaded box = default setting; CAD Ohms Max default is application dependent.
**When selecting “No” valve during initial startup, “Pre-Purge” will be set to “No Valve” and “Post-Purge” will be set to “0 Sec”.
**Changing this setting to ‘Yes’, with limits powered will exit Settings mode and result in immediate ‘Call For Heat’.
*†
If flame is sensed during Pre-Purge, control will lockout immediately (except when Pre-Purge is set to 0 or 3 seconds).
††A 10 second TFI is recommended for commercial burners 7GPH and larger.
AVAILABLE SETTINGS
Setup Menu Definitions
•Pre-Purge: Time period motor is on prior to Trial for Ignition. This
setting is often referred to as “valve delay on”. Note: If flame is
sensed during Pre-Purge, control will lockout immediately (except
when Pre-Purge is set to 0 or 3 seconds).
• Trial for Ignition: Flame-establishing period during ignition.
45 sec TFI up to 3 GPH
15 sec TFI up to 19.9 GPH
• Post-Purge: Time period the motor is on after the Call for Heat is
satisfied to allow for evacuation of combustion gases. This setting
is often referred to as “motor delay off”. A call for heat during Post-
Purge will result in a recycle. Note: If Pre-Purge is set to “0 Sec-
onds” or “No Valve”, Post-Purge can only be set to “0 Seconds”.
• Flame Stabilize: The time period after Trial for Ignition that the
ignitor remains on to stabilize flame.
• CAD Ohms Max: The maximum Ohms range that the control will
allow the burner to operate.
• Ignition Type
Interrupted: Spark is turned off after Flame Stabilization period.
Smart Ignition: If flame is lost at any time after the Flame
Stabilization period, the control will recycle (60 - 65 seconds).
Following this recycle, the control will operate in Intermittent
Duty mode (ignition on throughout the call for heat) for 5 heat
cycles. Following these five cycles, the control will revert back to
Interrupted Duty and will remain in Interrupted Duty until another
recycle event occurs. If control recycles and operates in Inter-
mittent Duty three consecutive times, on a fourth consecutive
recycle the control will lockout, due to hitting smart ignition limit,
displaying “15 max smart ign”
Intermittent: Spark remains on during call for heat.
• TT Jumpered: Allows TT to be “jumpered” by software program.
• Vent Input: Applicable only to applications equipped with a combus-
tion air proving switch (Intake) or a blocked vent switch (Exhaust):
Intake: When the burner is equipped with a combustion air
proving switch, the “Intake” setting should be selected. At
each burner startup, the control will check the air intake during
pre-purge (Valve On Delay)*. If the air is blocked, the control will
abort pre-purge and shutdown the burner. If the air intake is not
blocked during this startup test, but becomes blocked during
normal burner operation, the burner will shut down if the air
remains blocked for 20 seconds. Following any shutdown, the
burner will be permitted to recycle 3 times following a 1 minute
delay. Lockout occurs if the blockage persists throughout 3
recycles during any single call for heat.
*If “no valve” is selected in setup, the air intake cannot be
checked prior to TFI. In this case, the burner will only shut
down following the 20 second blockage described above. For
all burners with valves, Valve Delay settings of less than 15
Seconds will be automatically changed to 15 Seconds to allow
for the prepurge test.
Exhaust: When the appliance is equipped with a blocked vent
switch, the “Exhaust” setting should be selected. If a blocked
vent is detected during burner startup, the Pro X 70200 control
will NOT respond to the blocked intake vent until 30 seconds
after the ignition sequence is complete (following Flame Sta-
bilization), if the vent remains blocked at that time, the burner
will shutdown and lockout. If the vent is not blocked during
this startup test, but becomes blocked during normal burner
operation, the burner will shut down and recycle, depending on
the Allowed Recycles selected. Lockout occurs if the blockage
persists and the Allowed Recycles setting is reached during any
call for heat.
NOTE: If the Pro-X 70200 is being connected to both a com-
bustion air proving switch and blocked vent switch, call Carlin
Technical Support for assistance.
• Allowed Recycles: Number of Recycles allowed during a single
Call for Heat prior to lockout.
• Alarm Contacts: Option to choose N/O (Normally Open) or N/C
(Normally Closed)
• Clear Fault History: Allows all prior burner fault conditions stored
in control to be cleared.
• Restore Factory Defaults: Allows all factory defaults to be
restored in control (refer to settings shaded in gray in the table
above). Will reset and reboot control and require answer to “sole-
noid valve” question at startup.
Per UL requirements, the control will not turn on if the
cad cell senses flame (light) during the self-test. If the
cad cell sees flame, the control will remain in self-test
mode until the cad cell no longer senses flame.
SETTING
MODE
OPTIONS