
4
Accessory description and usage (Listed alphabetically)
1.
Coastal Filter
A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.
SUGGESTED USE: In geographic areas where salt damage could occur.
2.
Compressor Start Assist — Capacitor/RelayType
Start capacitor and start relay gives ‘‘hard’’ boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft (15.24m).
Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
3.
Compressor Start Assist — PTC Type
Solid-state electrical device which gives a ‘‘soft’’ boost to the compressor at each start-up.
SUGGESTED USE: Installations with marginal power supply.
Replacement installations with rapid pressure balance (RPB) thermostatic expansion valve on indoor coil.
4.
Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor
lubrication on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft (15.24m).
When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with low-ambient controller.)
All commercial installations.
5.
Cycle Protector
Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the
compressor has been interrupted for any reason, including normal room thermostat cycling.
SUGGESTED USE: Installations in areas where power interruptions are frequent.
Where user is likely to ‘‘play’’ with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft (15.24m).
High-rise applications.
6.
Evaporator FreezeThermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where winter start control has been added.
7.
Liquid Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) which stops and starts
refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor
operation cycle.
NOTE: Compressor start assist–capacitor/relay type must also be used.
SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. (Refer to ARI
Unitary Directory.) In certain long-line applications. (Refer to Long-Line Application Guideline).
8.
Low-Ambient Controller
This solid-state head pressure controller is a cycle control device activated by a temperature sensor. It is specifically designed to control
outdoor fan motor run time in response to saturated condensing temperature. For outdoor air temperatures between 55°F and 0°F
(12.8°C and –17.8°C), it maintains condensing temperature at 75°F and 130°F (23.8°C and 54.4°C).
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).
9.
Support Feet
Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the
unit base; minimizes corrosion.
SUGGESTED USE: Coastal installations.
Windy areas or where debris is normally cirdculating.
Rooftop installations.
10.
Thermostatic Expansion Valve (TXV)
A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant
gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB valves are available.
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. (Refer to ARI
Unitary Directory.
Required for use on all zoning systems.
11.
Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor
cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer toARI Unitary Directory.)
12.
Winter Start Control
An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under
low-load conditions.
SUGGESTED USE: All air conditioners where low-ambient controller has been added.