Refrigerant Service Ports — Each refrigerant sys-
tem has one service port located in the top of the compressor
motor casing. All units also have one service port on the liq-
uid line and one on either the discharge flange or the dis-
charge line. Be sure that the caps on the ports are tight.
Crankcase Heater(s) — Heater(s) is energized as long
as there is power to unit.
IMPORTANT: Unit power must be on for 24 hours
prior to start-up. Otherwise, damage to the compres-
sor may result.
Evaporator Fan — Fan belt and variable pulleys are
factory installed. Remove tape from the fan pulley. See
Table 5 for air quantity limits. See Tables 6-11 for fan per-
formance data. Be sure that fans rotate in the proper direc-
tion. See Tables 12A-13B for static pressure information for
factory-installed options and field-installed accessories. See
Tables 14Aand 14B for fan revolutions at various motor pul-
ley settings. See Fig. 20 for fan performance using horizon-
tal adapter. Refer to Table 15 for evaporator-fan motor per-
formance. To alter fan performance, see Evaporator-Fan
Performance Adjustment section on page 18.
Table 5 — Air Quantity Limits
UNIT
50TJ MINIMUM MAXIMUM
L/s Cfm L/s Cfm
016 2125 4500 3525 7,500
024 2800 6000 4800 10,000
028 3300 7000 5300 11,250
Condenser Fans and Motors — Fans and motors
are factory set. Refer to Condenser-Fan Adjustment section
on page 20 as required.
Return-Air Filters — Check that correct filters are in-
stalled in filter tracks. See Tables 1A and 1B. Do not operate
unit without return-air filters.
Outdoor-AirInletScreens— Outdoor-air inlet screens
must be in place before operating unit.
Accessory Economizer Adjustment — Remove
filter access panel. Check that the outdoor-air damper is closed
and return-air damper is open.
Economizer operation and adjustment is described in Base
Unit Operation section below and Economizer Adjustment
section on page 20.
Base Unit Operation
COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 are ener-
gized. The indoor (evaporator) fan contactor (IFC), and com-
pressor contactor no. 1 (C1) are energized and evaporator-
fan motor, compressor no. 1 (50TJ024,028) or unloaded com-
pressor (50TJ016), and condenser fans start. The condenser-
fan motors run continuously while unit is cooling. If the ther-
mostat calls for a second stage of cooling by energizing Y2,
compressor contactor no. 2 (C2) is energized and compres-
sor no. 2 starts (50TJ024,028), or compressor no. 1 runs fully
loaded (50TJ016).
HEATING, UNITS WITHOUT ECONOMIZER (If
Accessory or Optional Heater is Installed) — Upon a call
for heating through terminal W1, IFC and heater contactor
no. 1 (HC1) are energized. On units equipped for 2 stages of
heat, when additional heat is needed, HC2 is energized through
W2.
COOLING, UNITS WITH ECONOMIZER — Upon a call
for cooling, when outdoor ambient temperature is above the
outdoor-air temperature control setting, the evaporator and
condenser fans and compressor energize. The economizer
damper moves to VENT position.
Upon a first-stage call for cooling, when outdoor ambient
temperature is below the temperature control setting, the evapo-
rator fan starts and economizer damper modulates to main-
tain mixed-air temperature. The compressor(s) remains off.
Upon a second-stage call for cooling, compressor no. 1
(50TJ024,028) or unloaded compressor (50TJ016) is ener-
gized and mechanical cooling is integrated with economizer
cooling. Compressor no. 2 is locked out. If the outdoor-air
temperature is below 10 C (50 F), a cooling lockout switch
prevents the compressor(s) from running.
When supply-air temperature drops below a fixed set point,
the economizer damper modulates to maintain the tempera-
ture at the fixed set point.
Afreeze protection thermostat (FPT) is located on the evapo-
rator coil. It detects frost build-up and turns off the com-
pressor, allowing the coil to clear. Once frost has melted, the
compressor can be reenergized.
HEATING, UNITS WITH ECONOMIZER (IfAccessory or
Optional Heater is Installed) — The outdoor-air damper stays
at VENTposition while the evaporator fan is operating. Upon
a call for heating through terminal W1, the indoor (evapo-
rator) fan contactor (IFC) and heater contactor no. 1 (HC1)
are energized. On units equipped for 2 stages of heat, when
additional heat is needed, HC2 is energized through W2.
Fig. 18 — Seal Strip Location
(Air Hood Cross-Sectional View)
Fig. 19 — Outdoor-Air Hood Details
12