40MBDAQ: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
AUTO−RESTART Function
The indoor unit is equipped with an AUTO−RESTART function, which
is carried out through an auto−restart module. In the event of a sudden
power failure, the module memorizes the setting conditions prior to the
power failure. The unit resumes the previous operation setting (not
including the SWING function) automatically three (3) minutes after the
power returns.
If the memorization condition is the FORCED COOLING mode, the
unit runs in the COOLING mode for 30 minutes and switches to the
AUTO mode at the 75°F (24°C) setpoint. If the unit is off before the
power turns off and the unit is required to start up, the compressor delays
the start up for 1 minute before powering on. In other instances, the
compressor waits three (3) minutes before restarting.
FOLLOW ME
If the indoor PCB receives the signal, which results from pressing
FOLLOW ME on the remote controller or wired remote controller, the
buzzer emits a sound which indicates the FOLLOW ME function is
initiated. However, when the indoor PCB receives the signal from the
remote controller every three minutes, the buzzer will not respond. When
the unit is running with the FOLLOW ME function, the PCB controls
the unit according to the temperature from the FOLLOW ME signal, and
the temperature collection function of the room temperature sensor is
shielded.
When the FOLLOW ME function is available, the PCB controls the unit
according to the room temperature from the remote controller and the
setting temperature. The PCB changes the mode based on information
from the remote controller signal, however it is not affected by the setting
temperature.
If the unit is running under the FOLLOW ME function and the PCB
does not receive a signal from the remote controller for seven minutes or
after pressing FOLLOW ME again, the FOLLOW ME function turns
off automatically, and the temperature controls the unit according to the
room temperature detected from its own room temperature sensor and
setting temperature.
Refrigerant Leak Detection
With this new technology, the display area displays “EC” when the
outdoor unit detects a refrigerant leak. This function is only active in the
COOLING mode. This function helps to prevent the compressor from
being damaged by a refrigerant leak or a compressor overload.
• Open Condition: When the compressor is running, the T2 coil
temperature sensor value has no to very little change.
46°F (8°C) Heating
When the compressor is running, the indoor fan motor runs without the
ANTI-COLD air function. When the compressor is off, the indoor fan
motor is off.
Silence Operation
Press SILENCE on the remote control to initiate the SILENCE function.
When the SILENCE function is activated, the compressor running
frequency remains lower than F2 and the indoor unit emits a faint breeze,
which reduces the noise to the lowest level and creates a quiet and
comfortable space for the user.
Drain Pump Control
HEAT
A call for heat start the outdoor unit and the indoor blower follow its anti-
cold blow configuration. The pump will NOT turn on if the level switch
remains closed (no condensate present). If the level switch opens (water
level rise or switch malfunction), the pump starts in approximately 4
seconds.
If the level switch closes within 3 minutes, the pump continues to run for
one minute and then the pump turns off. If the level switch remains open
for three minutes, the blower turns off, the EEV closes, and the pump
turns off.
EE Alarm
If the level switch closes after the EE alarm has been posted, the EEV
opens, the blower starts, and the pump remains off.
COOL
A call for cool starts the indoor blower. When the compressor starts, the
pump turns on and continues to run until the outdoor unit cycles off
(single zone) or indoor unit = thermal OFF (MZ). If the level switch
opens (water level rise or switch malfunction), the pump remains on. If
the level switch closes within 3 minutes, the pump continues to run and
no alarm is posted. If the level switch remains open for 3 minutes, the
blower turns off, the EEV closes, and the pump powers off.
EE Alarm
If the level switch closes after the EE alarm has been posted, the EEV
opens, the blower starts, and the pump runs when the compressor starts.
NOTE: The EE alarm condition in the HEAT or COOL mode only
directly impacts the compressor operation of a single zone
system.
The Multi-zone outdoor unit continues to run unless the ducted unit is the
only indoor unit operating. A ducted unit on a multi-zone system
immediately restarts if the EE alarm clears and the compressor is running
to serve other units.