
19
slowly, usually dripping water into the drain pan in the
process.
7. TURN POWER ON. (Close unit electrical disconnect.)
NOTE: Be sure power is off before making any adjustments inside
unit.
8. Check fan and motor operation. Motor to fan wheel rota-
tion must match airflow direction shown in Fig. 3-8.
Set unit air delivery for required blower rpm per job submit-
tals or product data catalog. Adjust fan motor pulley
(Fig. 20) as follows:
a. Loosen setscrew on movable pulley flange.
b. Screw flange toward fixed flange to increase fan speed
and away from fixed flange to decrease speed.
c. Reset setscrew.
d. Check belt tension. The drive belt should be tensioned to
allow 1/2 to 3/4-in. deflection at the midpoint between
pulleys with moderate pressure.
Fig. 20 — Fan Pulley Adjustments
Inspect the unit for loose wires, correct blower wheel operation,
and loose or missing access panels or doors. Unless otherwise re-
quired for balancing and start-up procedures, units should not be
operated without proper ductwork, supply/return air grilles, and
access panels and/or doors in place.
START-UP
Start-up procedures vary depending upon the time of year (sum-
mer or winter) and building characteristics (new building or old
building, occupied or unoccupied, etc.).
Start-up in the cooling mode requires that proper care be given to
avoid condensation problems. Condensation forms on surfaces
that are colder than the dew point of the surrounding air. If a unit is
started and is fed low-temperature chilled water in a hot, humid
setting, condensation will form on many parts of the unit. In order
to avoid excessive condensation, water of higher temperature
should be used, approximately 65°F to 70°F. Also, the building
should be as completely enclosed as possible and outside-air sup-
ply fans and toilet and kitchen exhaust fans should be off.
As the building temperature drops, the chilled water temperature
can gradually be reduced until it reaches 50°F. At this point, the
outside-air fans can be turned on. When the chilled water tem-
perature is reduced to its design point, the exhaust fans can be
turned on.
Air System Balancing
All ductwork, air grilles, filters, and access doors and panels
must be complete and connected to establish actual system oper-
ating conditions before air system balancing procedures are
started.
NOTE: Units are factory set for system designed operating condi-
tions specified at the time of order entry.
Proper belt drive alignment and tension must be maintained when
adjusting the unit fan drive speed. The drive belt tension should
not exceed 3/16-in. (4.76 mm) deflection midway between the
pulleys under 8 lb of force. New belts tend to stretch during their
initial period of use. After 5 days of operation, check and readjust
belt tension and pulley alignment if necessary. Failure to do so
may result in excessive unit noise and/or premature belt/bearing
failure.
SERVICE
Clean Coils
1. Brush between coil fins with a stiff wire brush. Do not
bend fins. Follow up by cleaning with a vacuum cleaner. If
coil is cleaned with an air hose, take care not to drive dirt
and dust into other components.
2. Install clean air filters.
Check Drain
Check drain pan, drain line and trap at start of each cooling sea-
son. A standard type pipe cleaner for 3/4 in. (19.05 mm) ID pipe
can ensure removal of obstructions so that condensate is carried
away. Check the drain line at filter cleaning time during the cool-
ing season.
Fan and Motor Bearings
Fan shaft bearings are permanently lubricated and sealed, and
need no attention. Check tag on motor for motor bearing lubrica-
tion instructions (if any). Most motors furnished with these units
are permanently lubricated.
CAUTION
The air vent provided on the unit is not intended to replace the
main system vents and may not release air trapped in other
parts of the system. Inspect the entire system for potential air
traps and vent those areas as needed. Some systems may
require repeated venting over a period of time to properly
eliminate air from the system. Failure to do so could result in
equipment damage.
CAUTION
Do not exceed motor nameplate FLA (full load amps).
Operator must confirm motor current draw before putting unit
into service and again after air balancing the system. Failure to
do so could result in equipment damage.
CAUTION
Follow all safety considerations previously outlined. Failure to
do so could result in personal injury or equipment damage.
WARNING
Lock open and tag electrical disconnect before servicing
equipment. Failure to do so could result in personal injury or
death.