19
code
1 th-01
Automatic when the temperature
Defective thermistor Unit is shut down
2 th-02
Automatic when the temperature
Defective thermistor Unit is shut down
3 th-03 Defrost sensor fault, circuit A Automatic when the temperature
Defective thermistor Unit is shut down
4 th-04 Defrost sensor fault, second coil Automatic when the temperature
Defective thermistor Unit is shut down
5 th-10 Outside temperature sensor fault Automatic when the temperature
Defective thermistor Unit is shut down
6 th-11 Automatic when the temperature
Defective thermistor The master/slave mode is
stopped
7 th-12 Suction sensor fault Automatic when the temperature
Defective thermistor Unit is shut down
8 th-24 Economiser sensor fault Automatic when the temperature
Defective thermistor Unit is shut down
9 Pr-01 Discharge pressure transducer fault Automatic when the voltage transmitted
Defective transducer or connection
fault
Unit is shut down
10 Pr-04 Suction pressure transducer fault Automatic when the voltage transmitted
Defective transducer or connection
fault
Unit is shut down
11 Pr-13 Economiser pressure transducer fault Automatic when the voltage transmitted
Defective transducer or connection
fault
Unit is shut down
12 Pr-24 Water pump pressure transducer fault Automatic when the voltage transmitted
Defective transducer or connection
fault
Unit is shut down
13 Co-E1 Communication loss with the EXV
board
Automatic when communication is
re-established
Installation bus fault or defective
slave board
Unit is shut down
14 Co-O1 Communication loss with PD-AUX
board No.1
Automatic when communication is
re-established
Installation bus fault or defective
slave board
Unit with optional water pressure
sensors, unit is shut down.
15 Co-O2 Communication loss with PD-AUX
board No. 2
Automatic when communication is
re-established
Installation bus fault or defective
slave board
None
16 A1-01 CP A1 fault: Kriwan electrical
protection open
Manual Compressor overheating Compressor is shut down
17 A2-01 CP A2 fault: Kriwan electrical
protection open
Manual Compressor overheating Compressor is shut down
18 P-01 Automatic if the same alarm has not tripped
during the last 24 hours, otherwise manual.
thermistor
Unit is shut down
19 P-05 Low suction temperature. Automatic when the temperature returns to
normal, and if this alarm has not appeared
during the last 24 hours, otherwise manual.
Pressure sensor defective, EXV
blocked or low refrigerant charge
Unit is shut down
20 P-08 High superheat Automatic when the temperature returns to
normal, and if this alarm has not appeared
during the last 24 hours, otherwise manual.
Pressure sensor defective, EXV
blocked or low refrigerant charge
Unit is shut down
21 P-11 Low superheat Automatic when the temperature returns to
normal, and if this alarm has not appeared
during the last 24 hours, otherwise manual.
Pressure sensor defective, EXV
blocked or low refrigerant charge
Unit is shut down
22 P-14
interlock fault
Automatic if the unit is in manual
shut-down status, otherwise manual.
Unit is shut down, if the alarm
occurs in defrost mode, if not
the unit remains on.
23 P-16 Compressor A1 not started or no
pressure increase registered
Manual Connection problem Compressor is shut down
24 P-17 Compressor A2 not started or no
pressure increase registered
Manual Connection problem Compressor is shut down
25 P-29
Manager
Automatic when communication is
re-established
CCN installation bus defective Unit goes into autonomous
mode
26 P-30 Communicaiton loss between master
and slave
Automatic when communication is
re-established
CCN installation bus defective Unit goes into autonomous
mode
27 P-31 Manual Network command Unit is shut down
28 P-32 Fault water pump 1 Manual Pump overheating or poor pump
connection
29 P-37 Repeated high pressure unloading Automatic Transducer defective or fan circuit fault None
30 P-40 Repeated low suction temperature
unloading
Manual Pressure sensor defective or
refrigerant charge too low
Unit is shut down
31 P-43
less than 8°C, prevents unit start-up
Automatic when the temperature detected
returns to normal
Operating compressor protection
out of range or pressure sensor fault
The unit cannot start
32 P-50 Refrigerant leak Automatic when the concentration returns
to a lower value than the normal threshold
Refrigerant leak or volatile
components present in the machine
atmosphere
None
33 P-63 High pressure fault Manual Fan fault Unit is shut down
34 P-97 Reversed entering/leaving water sensors Manual Sensor defective, sensors reversed Unit is shut down
35 MC-nn
returns to normal or when the unit is no
longer in master/slave mode
Master/slave mode is stopped
36 FC-nO Unit is shut down