
NOTE: In response to thermostat call for heat R to W/W1 and
with HIGH HEAT ONLY switch SW1 set to OFF, the control
selects low-stage heating only with LOW HEAT switch SW2 set
to ON, or the control selects adaptive heating mode with LOW
HEAT switch SW2 set to ON. The control selects high-stage
heating only with HIGH-HEAT ONLY switch SW1 set to ON. In
response to thermostat call for high-stage heat R to W1 and W2,
the control selects high-stage heating regardless of switch SW1
and SW2 settings. See Fig. 14 for description of switch settings or
Fig. 15 for control circuit diagram.
The start-up and shutdown functions and delays described in item
1. apply to the 2-stage heating mode as well, except for switching
from low- to high-stage and vice versa.
a. When the thermostat "calls for heat," the R-W/W1 circuit
closes for low-stage or the R to W1-and-W2 circuits close
for high-stage. The furnace control performs a self-check,
verifies the low-heat and high-heat pressure switch contacts
LPS and HPS are open, and starts the IDM in low speed or
high speed as appropriate.
b. Switching from low- to high-gas heat—If the thermostat
R-W/W1 circuit for low-stage is closed and the R-W2
circuit for high-gas heat closes, the control CPU switches
the IDM speed from low to high. The high-heat pressure
switch relay HPSR closes. When the inducer motor IDM
provides sufficient pressure to close the high-heat pressure
switch HPS, the high-heat gas valve solenoid GV is
energized. The blower motor BLWM switches speed to
high-gas heat 5 sec after the R-W2 circuit closes.
c. Switching from high- to low-gas heat—If the thermostat
R-W2 circuit for high-gas heat opens and the R-W/W1
circuit for low-gas heat remains closed, the control CPU
switches the inducer motor IDM speed from high to low.
The high-heat pressure switch relay HPSR opens to de-
energize the high-heat gas valve solenoid GV. When the
inducer motor IDM reduces pressure sufficiently, the
high-heat pressure switch HPS opens. The low-heat gas
valve solenoid GV remains energized as long as the
low-heat pressure switch LPS remains closed. The blower
motor BLWM switches to low-gas-heat 5 sec after the
R-W2 circuit opens.
3. Cooling Mode
a. Single-Speed Cooling Outdoor Unit
(See Fig. 11 for thermostat connections.)
(1.) The thermostat closes the R to G-and-Y circuits. The
R-Y/Y2 circuit starts the outdoor unit, and the R to
G-and-Y/Y2 circuits start the furnace blower motor
BLWM on high-cool speed.
(2.) The EAC terminals EAC-1 and EAC-2 are energized
with 115v when the blower motor BLWM is operat-
ing.
(3.) When the thermostat is satisfied, the R to G-and-
Y/Y2 circuits are opened. The outdoor unit stops, and
the furnace blower motor BLWM continues operating
on the high-cool speed for an additional 90 sec.
b. Two-Speed Cooling Outdoor Unit
(See Fig. 12 for thermostat connections.)
(1.) The thermostat closes the R to G-and-Y1 circuits for
low cooling or closes the R to G-and-Y1-and-Y/Y2
circuits for high cooling. The R to Y1 circuits start the
outdoor unit on low-cooling speed, and the R-G circuit
starts the furnace blower motor BLWM on low-
cooling speed (same speed as for low-gas heat). The R
to Y1-and-Y2 circuits start the outdoor unit on high-
cooling speed, and the R to G-and-Y2 circuits start
the furnace blower motor BLWM on high-cooling
speed.
NOTE: Y1 is found in the outdoor unit. The furnace control CPU
controls blower motor BLWM speed by sensing only G for
low-cooling speed and Y/Y2 for high-cooling speed.
(2.) The EAC terminals EAC-1 and EAC-2 are energized
with 115v when the blower motor BLWM is operating
on either cooling speed.
(3.) When the thermostat is satisfied, the R to G-and-Y1
or R to G-and-Y1-and-Y/Y2 circuits open. The out-
door unit stops, and the furnace blower continues
operating on the cooling speed for an additional 90
sec.
4. Continuous Blower Mode
a. When the R to G circuit is closed by the thermostat, the
blower motor BLWM operates on low-gas heat speed
(identical to low-cool speed). Terminals EAC-1 and EAC-2
are energized with 115v as long as the blower motor
BLWM is energized.
b. During a "call for heat," the blower motor BLWM stops
during ignitor warm-up (17 sec), ignition (7 sec), and
blower on delay (45 sec), allowing the furnace heat
exchangers to heat up quickly.
c. The blower motor BLWM reverts to continuous blower
speed after the heating cycle is completed. In high-gas heat,
the furnace control CPU holds the blower motor BLWM at
high-gas-heat speed during the selected blower off delay
period before reverting to continuous blower speed.
(1.) When the thermostat "calls for low-cooling," the
blower motor BLWM continues to operate on low-
cool speed. When the thermostat is satisfied, the
blower motor BLWM continues on continuous blower
speed.
(2.) When the thermostat "calls for high-cooling," the
blower motor BLWM operates on high-cool speed.
When the thermostat is satisfied, the blower motor
BLWM operates an additional 2 sec on high-cool
speed before reverting back to continuous blower
speed.
(3.) When the R-G circuit is opened, the blower motor
BLWM continues operating for an additional 90 sec if
no other function requires blower motor BLWM
operation.
5. Heat Pump Mode
NOTE: A dual fuel thermostat or accessory interface kit is
required with single-speed heat pumps. See dual fuel thermostat or
interface kit Installation Instructions for single-speed heat pump
thermostat and interface connections. No interface kit is needed for
2-speed heat pumps. See 2-speed heat pump Installation Instruc-
tions to determine whether a standard or dual-fuel heat pump
thermostat is required and for thermostat connections.
a. Single-Speed Heat Pump Cooling
(1.) The thermostat and interface kit close the R to
G-and-Y/Y2 circuit to start the furnace blower motor
BLWM on high-cooling speed. The Y/Y2 input to the
furnace control is necessary to provide adequate cool-
ing airflow.
(2.) The EAC terminals EAC-1 and EAC-2 are energized
with 115v when the blower motor BLWM is operat-
ing.
12