Carrier i-Vu CIV-OR Installation manual

i
i-
-V
Vu
u®
®
O
Op
pe
en
n
R
Ro
ou
ut
te
er
r
I
In
ns
st
ta
al
ll
la
at
ti
io
on
n
a
an
nd
d
S
St
ta
ar
rt
t-
-u
up
p
G
Gu
ui
id
de
e
CARRIER CORPORATION ©2020 · Catalog No. 11-808-412-01 · 12/24/2020

Verify that you have the most current version of this document from www.hvacpartners.com or
www.accounts.ivusystems.com or your local Carrier office.
Important changes are listed in Document revision history at the end of this document.
CARRIER CORPORATION ©2020. All rights reserved throughout the world. i-Vu is a registered trademark of Carrier
Corporation. All other trademarks are the property of their respective owners.

Contents
Introduction.................................................................................................................................................................. 1
What is the i-Vu® Open Router? ........................................................................................................................1
Specifications ........................................................................................................................................................2
Safety considerations...........................................................................................................................................3
Installing the i-Vu® Open Router................................................................................................................................ 4
Mounting the i-Vu® Open Router .......................................................................................................................4
Wiring the i-Vu® Open Router for power ..........................................................................................................5
To wire for power ................................................................................................................................... 5
Addressing the i-Vu® Open Router ....................................................................................................................6
To set the i-Vu® Open Router address on the Open network ............................................................ 6
To choose an IP addressing scheme ................................................................................................... 7
To obtain an IP address using DHCP ................................................................................................... 7
To assign a custom IP address............................................................................................................. 7
Wiring for communications.............................................................................................................................. 10
Ethernet, BACnet MS/TP, and ARC156 wiring specifications ..........................................................10
To connect the i-Vu® Open Router to the Ethernet ..........................................................................11
To wire the BACnet MS/TP network ...................................................................................................11
To wire to a BACnet ARC156 network................................................................................................11
Communicating through the Local Access port with a USB Link............................................................... 12
To communicate using PuTTY ............................................................................................................13
Configuring BACnet Device Instance and network number........................................................................ 15
To set up BACnet Broadcast Management Devices (BBMDs)..........................................................16
Adjusting the i-Vu® Open Router driver properties ................................................................................................19
Driver ................................................................................................................................................................... 19
Device .................................................................................................................................................................. 20
Notification Classes........................................................................................................................................... 21
Calendars ............................................................................................................................................................ 22
Common and Specific Alarms ......................................................................................................................... 22
BACnet router properties.................................................................................................................................. 23
BACnet firewall................................................................................................................................................... 23
Alarm Store/Forward ........................................................................................................................................ 23
Configuring Properties using the Equipment Touch ...............................................................................................24
Troubleshooting .........................................................................................................................................................25
Communication LED's....................................................................................................................................... 25
To get the serial number .................................................................................................................................. 26
To restore factory defaults ............................................................................................................................... 27
To replace the i-Vu® Open Router's battery .................................................................................................. 27
To take the i-Vu® Open Router out of service............................................................................................... 27
Compliance ................................................................................................................................................................28
FCC Compliance................................................................................................................................................. 28
CE Compliance ................................................................................................................................................... 28
BACnet Compliance........................................................................................................................................... 28
Appendix A: BACnet Protocol Implementation Conformance Statement ............................................................29
Document revision history ........................................................................................................................................30


i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
1
What is the i-Vu® Open Router?
The i-Vu® Open Router is a controller that acts as a router between the main BACnet IP network and a BACnet
MS/TP network segment. The i-Vu® Open Router increases the capacity of an Open system, allowing individual
MS/TP network segments (with up to 60 Open controllers each) to be connected via a common BACnet IP
backbone.
Introduction

Introduction
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
2
Specifications
Driver
drv_ivuopenrouter
Maximum number of Open
controllers supported
60
Power
24 Vac ±10%, 50–60 Hz
24 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
Port E1 (10/100 BaseT
Ethernet)
For Ethernet LAN, BACnet IP, and Modbus TCP/IP communication at 10 or 100 Mbps,
half duplex
Both Assigned (default) and DHCP IP addressing are supported and DIP switch
selectable
Port S1 (BACnet MS/TP)
For communication with the controller network using BACnet MS/TP at 9600 bps, 19.2
kbps, 38.4 kbps, or 76.8 kbps (DIP switch selectable). Default is 76.8k bps.
BACnet
For communication with the controller network using ARC156 (156 kbps)
Port S2
EIA-232 port (115.2 kbps) for i-Vu® Open Router configuration using PuTTY or
Hyperterminal.
Local Access (Router Config)
For system start-up and troubleshooting using Field Assistant
Real time clock
Battery-backed real-time clock keeps track of time in event of power failure
Battery
10-year Lithium CR123A battery ensures the following data is retained for a maximum
of 720 hours during power outages:
•Time
•Graphics
•Control programs
•Editable properties
•Schedules
•Trends
To conserve battery life, you can set the driver to turn off battery backup after a
specified number of days and depend on the archive function to restore data when the
power returns.
A low battery is indicated by the Battery Low LED or a low battery alarm in the i-Vu®
application, a touchscreen device, and Field Assistant.
Protection
Built-in surge and transient protection for power and communications in compliance
with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable internal
solid-state polyswitches that reset themselves when the condition that causes a fault
returns to normal.
The power and network connections are also protected against transient excess
voltage/surge events lasting no more than 10 msec.
CAUTION To protect against large electrical surges on serial EIA-485 networks,
place a PROT485 at each place wire enters or exits the building.

Introduction
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
3
Status indicators
LED status indicators for Port S1 and S2 communication, Ethernet Port E1
communication, and low battery status. Seven segment status display for running,
error, power status, archive valid, and brownout.
Environmental operating
range
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-condensing
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged aluminum cover, removable screw-type terminal blocks
Overall dimensions
A:
B:
7-1/2 in. (19.1 cm)
11-5/16 in. (28.7 cm)
Mounting dimensions
C:
D:
E:
F:
5 in. (12.7 cm)
10-7/8 in. (27.6 cm)
1-1/4 in. (3.2 cm)
1/4 in. (.6 cm)
Mount with 6-32 by 1/2 in. mounting screws
Depth
1-1/4 in. (3.2 cm)
Weight
1.4 lbs (0.64 kg)
BACnet support
Conforms to the BACnet Building Controller (B-BC) Standard Device Profile as defined
in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision 9
Listed by
UL916 (Canadian Std C22.2 No. 205-M1983, CE, FCC Part 15 - Subpart B - Class A
Safety considerations
WARNING Disconnect electrical power to the i-Vu® Open Router before wiring it. Failure to follow this
warning could cause electrical shock, personal injury, or damage to the controller.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
4
1 Mount the i-Vu® Open Router (page 4).
2 Wire for power (page 5).
3 Set the i-Vu® Open Router's address and IP address (page 6).
4 Wire for communications (page 10).
5 Communicate through the Local Access port (page 12).
6 Configure BACnet Device Instance and network number (page 15).
Mounting the i-Vu® Open Router
WARNING
When you handle the i-Vu® Open Router:
•Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
•Do not touch components or leads.
•Handle the board by its edges.
•Isolate from high voltage or electrostatic discharge.
•Ensure that you are properly grounded.
Screw the i-Vu® Open Router into an enclosed panel using the mounting slots on the cover plate. Leave about 2
in. (5 cm) on each side of the controller for wiring.
Installing the i-Vu® Open Router

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
5
Wiring the i-Vu® Open Router for power
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
CAUTIONS
•The i-Vu® Open Router is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present.
•Carrier controllers can share a power supply as long as you:
•Maintain the same polarity.
•Use the power supply only for Carrier controllers.
To wire for power
1 Make sure the i-Vu® Open Router’s power switch is in the OFF position to prevent it from powering up before
you can verify the correct voltage.
2 Remove power from the power supply.
3 Pull the screw terminal connector from the router's power terminals labeled 24 Vac/Vdc and Ground.
4 Connect the transformer wires to the screw terminal connector.
5 Apply power to the power supply.
6 Measure the voltage at the i-Vu® Open Router’s power input terminals to verify that the voltage is within the
operating range of 21.6 –26.4 Vac or 23.4 - 28.6 Vdc.
7 Insert the screw terminal connector into the i-Vu® Open Router's power terminals.
8 Turn on the i-Vu® Open Router's power.
9 Verify that the Run LED (a dot in the lower right corner of the Module Status LED) begins blinking. The Module
Status LED will display 8 for about 5 seconds and then reverts to 0, until controllers have been found and
downloaded. There is a chase pattern when the router is running with no errors.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
6
Addressing the i-Vu® Open Router
The i-Vu® Open Router needs two addresses, one for the Open network and one for the IP Network.
The i-Vu® Open
Router needs...
That is unique
on the...
Notes
A router address
Open network
You set the i-Vu® Open Router address on the rotary switches.
(1-99)
NOTE The i-Vu® Open Router address is also used to auto-
generate the BACnet device instance/name for the router and
the MS/TP network number for the connected Open network.
See Configuring BACnet device instance and network number
for more information.
An IP address
IP Network
Use the IP Address DIP switch to choose one of the following:
•Use DHCP to obtain an IP address
•Assign a custom IP address (default)
The default IP settings are:
•192.168.168x, where x = router address
•subnet mask = 255.255.255.0
•default gateway = 192.168.168.254
To set the i-Vu® Open Router address on the Open network
CAUTION The i-Vu® Open Router address must be unique on the IP and Open network.
1 If wired for power, turn off the power.
NOTE The i-Vu® Open Router only reads the rotary switch positions during power up or upon reset.
2 Use the rotary switches to set the address. Set the Tens (10's) switch to the tens digit of the address, and set
the Ones (1's) switch to the ones digit. Valid addresses are 1 - 99.
EXAMPLE If the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
10's 1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
3 Turn on the i-Vu® Open Router's power.
CAUTION The factory default setting is 00 and must be changed to successfully install your i-Vu® Open
Router.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
7
To choose an IP addressing scheme
Carefully plan your addressing scheme to avoid duplicate IP addresses.
•If there is a DHCP server on the network, and, if you have a single i-Vu® Open Router or multiple i-Vu® Open
Routers that exist on the SAME subnet, use DHCP addressing. Skip to the section To obtain an IP address
using DHCP (page 7).
•If you have multiple i-Vu® Open Routers that reside on different subnets, you cannot use DHCP addressing.
Instead, give each i-Vu® Open Router an assigned IP address. Skip to the section To assign a custom IP
address (page 7).
NOTE This network configuration also requires that you configure IP Broadcast Management Devices
(BBMDs). See To set up BACnet Broadcast Management Devices.
To obtain an IP address using DHCP
1 Turn the i-Vu® Open Router's power off.
2 Set the IP Addr DIP switch DHCP to On.
3 Turn the i-Vu® Open Router's power on. The DHCP server assigns an IP address to the i-Vu® Open Router.
CAUTION If the DHCP server is not found, the following default IP address settings will be used:
•IP address = 192.168.168.xx, where xx = i-Vu® Open Router address (rotary switch settings)
•Subnet Mask = 255.255.255.0
•Default Gateway = 192.168.168.254
To assign a custom IP address
1 Obtain the IP address, subnet mask, and default gateway address for the router from the facility network
administrator.
2 Turn the i-Vu® Open Router's power off.
3 Set the i-Vu® Open Router's IP Addr DIP switch Assigned to On.
4 Configure the i-Vu® Open Router by setting the Router Config Mode DIP switch Console to On using a
terminal program such as PuTTY or Hyperterminal.
5 Turn the i-Vu® Open Router's power on.
PREREQUISITES
•A computer with a USB port
•A USB Link cable —See To communicate through the Local Access port with a USB Link (page 12)

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
8
CAUTION If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.
Using PuTTY
1 Download and install PuTTY from the PuTTY website
(http://www.chiark.greenend.org.uk/~sgtatham/putty/download.html).
2 Connect the laptop to the local access port of the router, ZS sensor, or an SPT sensor using the USB Link
cable(s).
USB Link
Connect to
Local Access port
12 ft
Connect to
USB port
7 3/4 in.
NOTE If using a USB isolator, plug the isolator into your computer's USB port, and then plug the USB Link
cable into the isolator.
3 To change a router's IP address, subnet mask, or default gateway, set its IP Address DIP switch to Assigned.
4 Start PuTTY.
5 Under Category > Connection, select Serial.
6 Under Options controlling local serial lines, enter the following settings:
Field
Value
Serial line to connect to
Replace X with the computer's port number that the USB Link cable is
connected to.
NOTE To find the port number, select Start > Control Panel > System >
Device Manager > Ports (Com & LPT). The COM port number is beside
Silicon Labs CP210x USB to UART Bridge.
Speed (baud)
115200
Data Bits
8
Stop Bits
1
Parity
None
Flow Control
None

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
9
7 Click Open. A window similar to the one below appears.
8 Do one of the following:
○To change a property value:
a. Type the number of the property, then press Enter.
b. Type the new value, then press Enter.
○To take an action, type number of the action, then press Enter.
9 If you changed a value, type 1, then press Enter to restart the controller.
10 Close PuTTY.
11 Verify that you can communicate with the i-Vu® Open Router by issuing a PING command to the IP address
specified in step 12.
NOTE Your computer must be on the same subnet as the i-Vu® Open Router for the PING command to work.
12 When finished, set the i-Vu® Open Router's Router Config Mode DIP switch to OFF to restore normal
functionality to the Local Access port.
13 Cycle the i-Vu® Open Router's power to accept the Router Config Mode changes.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
10
Wiring for communications
The i-Vu® Open Router has multiple ports. See table below for port descriptions.
Port
Protocol
Port type(s)
Baud rate(s)
Use for
Ethernet
Port E1
BACnet/IP
Ethernet
10 Mbps
100 Mbps
LAN connection
BACnet
ARC156
EIA-485 (2-
wire)
156 kbps
Open network connection
S1
BACnet MS/TP
EIA-485 (2-
wire)
DIP Switch selectable:
9600 bps
19.2 kbps
38.4 kbps
76.8 kbps (default)
Open network connection
S2
N/A
EIA-232
115.2 kbps
Router configuration
Local
Access
N/A
Rnet
115.2 kbps
•Router configuration
•System start-up and
troubleshooting with Carrier
Tools
Ethernet, BACnet MS/TP, and ARC156 wiring specifications
For...
Use...
Maximum Length
Ethernet
CAT5e or higher Ethernet cable
328 feet (100 meters)
BACnet
MS/TP*
BACnet
ARC156*
22 or 24 AWG, low-capacitance, twisted,
stranded, shielded copper wire
2000 feet (610 meters)
*For details see the Open Controller Network Wiring Guide.
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
11
To connect the i-Vu® Open Router to the Ethernet
Connect an Ethernet cable to the Ethernet Port E1.
To wire the BACnet MS/TP network
1 Turn the i-Vu® Open Router's power off.
2 Check the communications wiring for shorts and grounds.
3 Verify that the Port S1 jumpers are set to 485-2w.
4 Set the MS/TP baud rate DIP switches 7 and 8to match the baud rate of the Open network. The default is
76.8k.
5 Connect the i-Vu® Open Router's Port S1 to the Open MS/TP network. Use the same polarity throughout the
network segment.
Wire the Port S1 terminal...
To this Open controller terminal...
Shield (Pin 1)
Shield
Net- (Pin 4)
Net-
Net+ (Pin 5)
Net+
6 Turn the i-Vu® Open Router's power on.
To wire to a BACnet ARC156 network
1 Turn off the i-Vu® Open Router's power.
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the controller’s screw terminals labeled Net +, Net -, and Shield on the
BACnet port.
NOTE Use the same polarity throughout the network segment.
4 If the i-Vu® Open Router is at either end of a network segment, connect a BT485 to the i-Vu® Open Router.
5 Turn on the i-Vu® Open Router's power.
6 Verify communication with the network by viewing a Module Status report in the i-Vu® interface.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
12
Communicating through the Local Access port with a USB Link
Using a computer and a USB Link, you can communicate locally with the i-Vu® Open Router to download or to
troubleshoot.
CAUTIONS
•Maintain polarity when controllers share power.
•Failure to maintain polarity while using the USB Link on a computer that is grounded via its AC adapter may
damage the USB Link and the controller.
•If multiple controllers share power but polarity was not maintained when they were wired, the difference
between the controller's ground and the computer's AC power ground could damage the USB Link and the
controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer. Plug the isolator into your computer's
USB port, and then plug the USB Link cable into the isolator.
PREREQUISITES
•For the i-Vu® application to communicate with the controller, the controller must have been downloaded with
at least its driver.
•Laptop with USB port
•USB Link (Part #USB-L)
Using a USB Link
1 The USB Link driver is installed with an i-Vu® v5 or later system. But if needed, you can get the latest driver
from http://www.silabs.com/products/mcu/Pages/USBtoUARTBridgeVCPDrivers.aspx. Install the driver
before you connect the USB Link to your computer.
2 Connect the laptop to the controller or sensor using the appropriate USB Link cable(s).
USB Link
Connect to
Local Access port
12 ft
Connect to
USB port
7 3/4 in.
NOTE If using a USB isolator, plug the isolator into your computer's USB port, and then plug the USB Link
cable into the isolator.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
13
3 Set the controller's Router Config Mode DIP switch.
To communicate in...
Set switch to...
The i-Vu® application
Off
PuTTY
NOTE See To communicating using PuTTY (page 13)
On
4 Turn the controller's power off, then on again.
To communicate using PuTTY
You can connect a computer to a controller's Local Access port and use PuTTY, a free open source terminal
emulation program, to:
•Set the baud rate for Port S1 on the i-Vu® Open Router
•Set controller properties, such as IP address and network information
•Retrieve a Modstat
PREREQUISITES
•A computer with a USB port
•A USB Link cable
NOTE The USB Link driver is installed with an i-Vu® v5 or later system. But if needed, you can get the latest
driver from http://www.silabs.com/products/mcu/Pages/USBtoUARTBridgeVCPDrivers.aspx. Install the
driver before you connect the USB Link to your computer.
CAUTION If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
14
Using PuTTY
1 Download and install PuTTY from the PuTTY website
(http://www.chiark.greenend.org.uk/~sgtatham/putty/download.html).
2 Connect the laptop to the controller or sensor using the appropriate USB Link cable(s), as described above.
3 To change a router's IP address, subnet mask, or default gateway, set its IP Address DIP switch to Assigned.
4 Start PuTTY.
5 Under Category > Connection, select Serial.
6 Under Options controlling local serial lines, enter the following settings:
Field
Value
Serial line to connect to
Replace X with the computer's port number that the USB Link cable is
connected to.
NOTE To find the port number, select Start > Control Panel > System >
Device Manager > Ports (Com & LPT). The COM port number is beside
Silicon Labs CP210x USB to UART Bridge.
Speed (baud)
115200
Data Bits
8
Stop Bits
1
Parity
None
Flow Control
None
7 Click Open. A window similar to the one below appears.
8 Do one of the following:
○To change a property value:
a. Type the number of the property, then press Enter.
b. Type the new value, then press Enter.
○To take an action, type number of the action, then press Enter.
9 If you changed a value, type 1, then press Enter to restart the controller.
10 Close PuTTY.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
15
Configuring BACnet Device Instance and network number
All BACnet Open controllers must have a unique Device Instance and Name. These BACnet addresses are
automatically generated and usually do not require modification. However, sometimes you need to override the
automatic addressing assignments.
Autogenerated addressing scheme:
The i-Vu® Open Router's rotary address setting determines the automatic BACnet addressing scheme for the
connected Open network.
Legend
16 = Carrier's BACnet Vendor ID
xx = i-Vu® Open Router's rotary switch address (BACnet Device Instance address)
yy = Open controller's rotary switch address (MS/TP MAC address)
For the i-Vu® Open Router:
•BACnet Device Instance Number = 1600xx
•BACnet Device Instance Name = device1600xx
•BACnet IP Network Number = 1600
•BACnet MS/TP Network Number = 161xx
•BACnet ARC156 Network Number = 163xx
•Port S1 MS/TP MAC Address = 0 (fixed)
For the Open controllers connected to the i-Vu® Open Router
•BACnet MS/TP Device Instance Number = 161xxyy
•BACnet ARC156 Device Instance Number = 163xxyy
•BACnet MS/TP Device Instance Name = device161xxyy
•BACnet ARC156 Device Instance Name = device163xxyy
•BACnet MS/TP or ARC156 MAC Address = yy
•BACnet MS/TP Network Number = 161xx (learned from the router, defaults to 16101 if no i-Vu® Open Router
is operating)
If the BACnet automatic settings need to be changed, launch the Router Configuration utility using a terminal
program. See To assign a custom IP address (page 7) for instructions on connecting to and using a terminal
program.
To change the BACnet settings:
1 Enter the BACnet selection# from the menu. Type the new setting and click Enter. The new setting will appear
on the Router Configuration screen.
2 Cycle power to the router for the new settings to take effect.
NOTE If the BACnet MS/TP or ARC156 network number of the router is assigned and not auto-generated,
and the Open controllers connected to that router are set such that their BACnet settings are auto-generated,
then the Open controller BACnet settings will be auto-generated based on the assigned MS/TP network
number in the router:
Example A router's BACnet MS/TP or ARC156 network has been assigned to 200.

Installing the i-Vu® Open Router
i-Vu® Open Router CARRIER CORPORATION ©2020
Installation and Start-up Guide All rights reserved
16
If the connected Open controllers are using autogenerate, then their settings will be:
•BACnet MS/TP Network Number = 200
•BACnet Device Instance Number = 200yy
•BACnet Device Instance Name = device200yy
•BACnet MS/TP MAC Address = yy
To set up BACnet Broadcast Management Devices (BBMDs)
If your system has multiple routers that reside on different IP subnets, you must set up one router on each IP
subnet as a BACnet/IP Broadcast Management Device (BBMD).
Every subnet with a router must have a BBMD configured in order for broadcasts from routers on that subnet to
reach the rest of the routers on the network.
NOTES
•The i-Vu® Standard or Plus application - If the i-Vu® web server is on a separate subnet than the rest of the
routers, the internal router must be assigned a routable IP address and configured as a BBMD.
•The i-Vu® Pro application - If the i-Vu® Pro server is on a separate subnet than the rest of the routers, you
must register it as a foreign device to a router acting as a BBMD device.
Table of contents