
The power switch must be turned to OFF and the unit discon-
nected from the power source whenever performing service,
maintenance functions or cleaning the refrigerated area.
3.1 HOW TO SEE THE ALARM AND RESET THE RECORDED ALARM
.deyalpsid era slangis mrala eht ,yeknwoD ro PU eht hsuP .1
2. When the signal is displayed, hold the SET key untill the "rst" message is displayed, and push the
.deyalpsid eb lliw erutarepmet lamron eht dna gniknilb st ra ts egassem "tsr" eht ,niaga TES
confirm
Message Cause Outputs
“P1” Room probe failure Compressor output according to par.
“Con” and “COF”
“P2” Evaporator probe failure Defrost end is timed
“HA” Maximum temperature alarm Outputs unchanged.
“LA” Minimum temperature alarm Outputs unchanged.
“dA” Door openCompressor and fans restarts
“EA” External alarm Output unchanged.
“CA” Serious external alarm (i1F=bAL) All outputs OFF.
“CA” Pressure switch alarm (i1F=PAL) All outputs OFF
DANGER