Centrometal Cm Pelet-set Touch 14 User manual

Technical manual
HEATING TECHNIQUE
Centrometal d.o.o. - Glavna 12, 40306 Macinec, Croatia, tel: +385 40 372 600, fax: +385 40 372 61 1
THE DIGITAL BOILER CONTROLLER - USER
READY
TURPS- 07/2018-ENG Software version v1.23f
80°C
120°C
0%
1700
15k
30%
60°C
70°C
50°C
55°C
THE FIRST COMMISSIONING MUST BE CARRIED OUT BY AN AUTHORIZED
PERSON, OTHERWISE THE PRODUCT WARRANTY IS NOT VALID!
Book 2/2
Cm-Pelet set_Touch 14-90 kW

The controller
THE CONTROLLER
Boiler controller components used by a user:
Touchscreen with
bicolour LED
Main switch (0/1)
switches the boiler
on / off
UTP cable connector
Safety thermostat
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
2

Touchscreen must not be pressed while switching the main switch on, otherwise
the controller will show a firmware update mode, which is used by an authorized
person only. If this happens, please switch the main switch off and switch it back
on without pressing the touchscreen.
Switching on / Display
SWITCHING ON / DISPLAY
Button ’’OK’’
Initial message countdown
Software version
Language selection
Burner power:
- 14 kW (Cm Pelet-set 14)
- 20-35 kW (Cm Pelet-set 35)
- 40/50 kW (Cm Pelet-set 50)
- 60-90 kW (Cm Pelet-set 90)
After switching the main switch on, the language selection and software version will appear on the screen. You can
choose between different languages. To select the preferred language press a flag on display.
Software version
Burner power:
- 14 kW (Cm Pelet-set 14)
- 20-35 kW (Cm Pelet-set 35)
- 40/50 kW (Cm Pelet-set 50)
- 60-90 kW (Cm Pelet-set 90)
The possibility of online boiler
monitoring and online boiler
operation management
(it is necessary to have
Cm Wifi-box as an additional
equipment)
If the option ''LANGUAGE SELECTION'' is ''OFF'' in the main menu under the name ''DISPLAY'', the initial message will
appear on the screen (see the picture below) and it will stay as long as is set in the submenu ''INITIAL MESSAGE TIME''
or until you press the ''OK'' button.
Scroll page
3
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW

THE MAIN MENU
The main menu, symbols
SYMBOLS
The main menu is used to select a preferred submenu. To enter into a certain menu press an icon on the
screen. To switch between the ''Main menu'' and ''Boiler working display'' press the ''VIEW SELECTION''
button. To display drop-down menu (if it is enabled) use the ''SHORTCUTS'' button.
Button ’’ON / OFF’’
options: on / off boiler operation’’
Button ’’VIEW SELECTION’’
options: main menu / home screen
Button ’’SHORTCUTS’’: Drop-down
menu (if it is active)’’
Button ’’ENTER’’
Button ’’BACK’’
Button ’’PREVIOUS SCREEN’’
Button ’’NEXT SCREEN’’
Button ’’OK’’
Tipka ’’START’’/’’STOP’’
Navigation buttons:
’’LEFT’’, ’’RIGHT’’, ’’UP’’, ’’DOWN’’
Button ’’DELETE’’
Button ’’FACTORY SETTINGS’’
Button ’’INFORMATION’’
Button ’’COPY’’ Button ’’PASTE’’
View selection:
Main menu / work
Time
Boiler start / stop
Date
Shown if additional equipment
CM2K is enabled only
Shortcuts:
drop-down menu
(if it is active)
Current boiler status
(Work phase)
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
4

Symbols
SYMBOLS
6 7 8
4
5
19
3
1110
2
13
Simboli:
1 - Boiler temperature
2 - Fuel level *
3 - Transporter is working
4 - Photocell
5 - Flame symbol
6 - Igniter is working
7 - Burner fan is working
8 - Burner fan rpm
9 - Burner working hours counter
10 - Burner working hours reset buttom
11 - Dynamic configuration view
(view depends on set configuration)
12 - Heating mode / Freeze guard /
Additional equipment view (cascade, wifi...)
13 - Outside temperature
14 - Boiler working stage
* - additional equipment
on screen only if additional equipment
is installed and enabled (fuel level sensor)
12
14
Boiler type display:
EKO-CK P +
Cm Pelet-set_Touch
14-90 kw
EKO-CKB P +
Cm Pelet-set_Touch
14-50
EKO-CKB P +
Cm Pelet-set_Touch
14-50
+ recirculation
built in boiler
Pump (no demand to work)
Pump has demand to work (when there is demand to work, given by a customer, yellow rectangle appears
inside the pump symbol, but pump doesn't work if all the conditions are not fulfilled; i.e. too low temperature
in the boiler, otherwise it works). It rotates while working, it doesn't rotate while not working.
5
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW

Symbols
SYMBOLS
70°C
50°C
55°C
Heating (working mode)
External control – there is a demand
Heating + DHW (working mode)
View button / Drop-down menu
(all existing elements of automatic /
remote boiler start are enabled)
View button / Drop-down menu
(all existing elements of automatic /
remote boiler start are enabled)
All elements of automatic / remote boiler
start are disabled (ON/OFF button is crossed
in red)
Accumulation tank with current
temperature at top of the tank and
at the bottom of the tank.
60°C
Hydraulic crossover with the
current temperature
(there are configuration without
temp. sensor)
Domestic hot water tank
with current temperature
Heating circuit
Room thermostat
Next to the room thermostat
symbol bright blue circle (the
room thermostat has requested
for operating the pump, the pump
does not work if you have not met
all the conditions for its operation,
for example. low temp. in the
boiler, otherwise normally works)
Cm WiFi-box - not connected
Cascade
Cm WiFi-box - connected
DHW (working mode)
External control – there is no demand
Room corrector symbol show current
measured room temperature (20.0°C), set
room temperature in controller + set room
corrector correction (20.0+5.0°C).
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
6

Since freezing guard is enabled, burner is started
from the OFF phase. Snowflake disappeares if burner
is started by schedule, external start, Wifi monitoring,
CMGSM, by pressing the ON/OFF button or if it goes
to the OFF phase.
"Freeze guard" triggered one of the pumps.
Option "Freeze guard" is enabled
Burner start is disabled in drop down menu due to
''freezing guard'', freezing protection system
works without possibility for burner to work
( )until the boiler is cooled down to minimum temperature .
Symbols, The parameters adjusting
SYMBOLS, THE PARAMETERS ADJUSTING
3-way thermostatic mixing valve
+ pump
3-way mixing valve with actuator and
return flow temp. sensor
+ pump
4-way mixing valve with actuator and
return flow temp. sensor
+ pump
By switching of a certain button to OFF:
- Schedule: disabled
- Freezing guard: boiler start for freezing protection is disabled, but freezing protection is woking in a
way it can perform without starting the boiler and a half of snowflake and an exclamation mark
appear in the upper right corner of the screen
- External control: start from an external source is disabled and crossed external start icon is shown
on the screen
- WiFi/CM GSM: boiler start/stop by WiFi/CM GSM module is disabled, other WiFi/CM GSM options
are disabled
Current status of existing elements ot automatic
/ remote start is show on the screen (ON/OFF
in a drop-down menu):
Shown in the picture:
- Schedule: enabled (status ON)
- Freezing guard: enabled (status ON)
- External control: enabled (status ON)
- WiFi/CM GSM: enabled (status ON)
7
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
PP-2

THE PARAMETERS ADJUSTING
There are 4 different menu types for adjusting the parameters:
A - this menu is used to set the parameters that have numerical values (°C, RPM, time...)
example: adjust the burner fan rpm, adjusting the boiler temp. etc...
B - this menu is used to set parameters that must be selected (marked) to be enabled and there can be multiple selected
(enabled) items
NOTE: some enabled options disable another one (they can't be enabled at the same time)
example: enable additional equipment: flap, air cleaning, CM2K, Cm-WiFi-box...
C - this menu is used to set the parameters that must be selected but there can be only one selected item
example: set the type of the DHW sensor
D - this menu is used to set the parameters where are many items to be adjusted
example: adjust the burner working parameters on power P2
The parameters adjusting
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
8
A B
C D

The parameters adjusting methods (examples)
1 -parameter you are adjusting
2 - value adjustment box
3 - set value
4 - value type
5 - info button (displays factory, min. and max. values)
6 - resets the current value to the factory value
1 - parameter you are adjusting
2 - value adjustment box
3 - selected option (only one option can be selected)
4 - confirm button
5 - factory value
1 - parameter you are adjusting
2 - items that can be enabled
3 - next page button
4 - confirm button
5 - selected (enabled) item
6 - deselected (disabled) item
1 - parameter you are adjusting
2 - switch between sheets (only for parameters which
have multiple sheets)
3 - parameter description
4 - parameter current value (press 2 times to enter
adjusting mode)
5 - up/down scroll buttons
THE PARAMETERS ADJUSTING METHODS (examples)
NOTE: after parameter changing press the "CONFIRM" button to store new value. If you don't want to save the set
value, press "BACK" button.
9
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
1
2
34
5
6
1
2
4
3
5
1
5
3
2
46
1
2
3
4
5

BURNER STOP PROCEDURE / CONTROLLER STOP PROCEDURE
Correct ways to stop (turn off) the burner (get to the OFF phase):
- manual burner stop (turn off) by pressing ON/OFF button if burner is in any phase except the OFF phase (no matter if
external control is enabled or disabled)
- burner stop (turn off) by schedule (if enabled) (no matter if external control is enabled or disabled)
- burner stop (turn off) by WiFi or CM GSM (additional equipment) (no matter if external control is enabled or disabled)
Correct controller stop (turn off) procedure (main switch 0/1)
- first thing to do is to get the burner into the OFF phase – the burner is turned off (unless it is already in that phase)
- switch off the main switch 0/1 (put it into the 0 position)
- the main switch (0/1) on the controller is not intended for
switching the controller on and off
- the burner must be in the OFF phase before switching the
controller off on the main switch
IMPORTANT NOTES!!! !!!
Burner start and stop procedur / Switching off the controller
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
10
BURNER START PROCEDURE (START IS ENABLED)
The ways to activate ''start is enabled'' of the burner (burner goes from the OFF phase to the A0 phase (burner
starts) or to the S7-3 waiting phase (STANDBY)):
- manual activation by pressing the ON/OFF button
- activation by schedule (if enabled)
- activation by WiFi or CM GSM module (additional equipment) (if it is enabled in drop-down menu and in "Work
mode"/"Additional equipment"/"Internet supervision")
burner in the waiting phase s7-3 (standby) – causes:
- set boiler temperature is reached (controller waits the boiler temperature to drop below set difference)
- there is no heating demand (from heating circuits and/or DHW tank) (controller is set to start according to the heating
demands
- external control, that is enabled, turned the boiler off
Notes:
Burner may get into the S7-3 waiting phase right after start is activated (from the OFF phase) because one or more of
the S7-3 waiting phase causes are fulfilled.

Maintenance
1.0. MAINTENANCE
1.1. CLEANING THE BURNER
Under "CLEANING" menu are two options:
Cleaning: this option is used to start the burner fan on the set RPMs to
clean the burner grate (note: depending of the pellets quality grate will
be more or less clean. After this procedure, burner grate should be
removed and cleaned and the burner head should also be cleaned.)
Burner fan: this option sets the burner fan RPMs during cleaning
1.1.1. CLEANING – basic equipment
Press the "START" button to start the burner fan for 10 min.
After pressing the "START" button countdown is started for 10 min,
after which burner fan stops automaticaly
NOTE: Burner cleaning option is not a replacement for manual burner
and burner grate cleaning. Burner cleaning must be carried out regulary,
according to the technical manual.
1.1.1. CLEANING – installed additional equipment – burner air cleaning
Press "AIR VALVE" button to open the electro-magnetic valve and to
clean the burner with compressed air.
After pressing the "AIR VALVE" countdown ist started for 60 sec in
which time "AIR VALVE" button is disabled to alow compressor to fill its
tank.
11
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW

1.1.2. BURNER FAN
Maintenance
This option is used to adjust burner fan RPMs during cleaning
procedure.
Possible adjustment:
- Factory adjustment: 3000 rpm
- Minimal adjustment value: 500 rpm
- Maximal adjustment value: 3000 rpm
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
12

Temperature
2.0. TEMPERATURE
Temperature menu shows only items applicable to the set configuration. In next section of the manual all avalible
configurations and schemes are listed.
Availible temperature settings will be described at every individual configuration and scheme in "CONFIGURATIONS"
section of this manual.
NOTE: this is only representation picture, actual possible adjustment depends on set configuration.
Possible adjustment:
Factory: 20.0°C
Option: 5.0 - 30.0°C
This sets up the first heating circuit daily room temperature.
Possible adjustment:
Factory: 20.0°C
Option: 5.0 - 30.0°C
This sets up the first heating circuit night room temperature.
13
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW

3.0. SCHEDULE
This option is used to set a working time of the burner, DHW tank heating, DHW recirculation pump and to change
daytime and night time temperature of the first and the second heating circuit.
NOTE:
This manual shows the screen with the largest possible number of the basic boiler controller devices where
schedule is available. An actual number of the devices with ordinal device numbers depends on chosen a
selected configuration.
3.1. SCHEDULE - BOILER
This option is used to select a one of the three SCHEDULE tables you have set or to select Schedule: OFF
Possible adjustment: ’’SCHEDULE ’’ :
- Factory: OFF
- Table 1, Table 2, Table 3
NOTE:
You can adjust three differnet tables according to your needs, but one table can be active at the moment only.
3.1.2. TABLE 1/2/3
This option is used to set "SCHEDULE TABLES". Each table can be
set individualy. You can set ON/OFF 3 times during 1 day and every
day can be individualy set.
Schedule
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
14

Schedule
3.2. DHW
1 - current table you are adjusting (table 1 / table 2 / table 3)
2 - day of the week
3 - green - burner start (on)
red - burner stop (off)
Press the box to adjust the time
You can adjust 3 start and stop during 1 day
You can copy/paste from one day to another by pressing the "day box"
of the day which you want to copy, press the "COPY" button and press
the desired "day box" and press "PASTE" button.
This option is used to select a one of the three SCHEDULE tables you have set or to select Schedule: OFF
Setting up the table ’’SCHEDULE’’:
- Factory: OFF
- Table 1, Table 2, Table 3
NOTE:
You can adjust three differnet tables according to your needs, but one table can be active at the moment only. Each table
can be set individualy. You can set 3 starts and 3 stops of an active DHW period in a day.
3.3. RECIRCULATION
This option is used to select a one of the three SCHEDULE tables you have set or to select Schedule: OFF
Setting up the table ’’SCHEDULE’’:
- Factory: OFF
- Table 1, Table 2, Table 3
NOTE:
You can adjust three differnet tables according to your needs, but one table can be active at the moment only. Each table
can be set individualy. You can set 3 starts and 3 stops of an active DHW recirculation period in a day.
15
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
1
2
3
COPY
BUTTON
PASTE
BUTTON

Schedule
3.4. SCHEDULE – 1st heating circuit
This option is used for adjusting periods when room temperature is maintained. ’’Day temperature’’/’’Night
temperature’’ or ’’Table’’ where switching from ’’Day temperature’’ to ’’Night temperature’’ is defined.
Possible adjustment:
- Factory: Day temperature
- Day temperature, Night temperature, Table
NOTE:
It is possible to adjust one table with different settings.
In the table it is possible to set the three switch to "Day temperature" and three switch to "Night temperature" in one day..
3.5. SCHEDULE – 2st heating circuit
This option is used for adjusting periods when room temperature is maintained. ’’Day temperature’’/’’Night
temperature’’ or ’’Table’’ where switching from ’’Day temperature’’ to ’’Night temperature’’ is defined.
Possible adjustment:
- Factory: Day temperature
- Day temperature, Night temperature, Table
NOTE:
It is possible to adjust one table with different settings.
In the table it is possible to set the three switch to "Day temperature" and three switch to "Night temperature" in one day.
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
16

This option is used to see the
history of the occured "ERRORS"
and "WARNINGS»
This option is used to see the history of the occured "ERRORS".
1 - error code
2 - description of the error
3 - time and error of operation phase
Errors codes are marked with the letter ’’E’’.
List and the description of the errors can be found at the end of
these instructions.
This option is used to see the history of the occured "WARNINGS»
1 - error code
2 - description of the error
3 - time and working stage when warning occured
Warning codes are marked with letter ’’W’
List and the description of the warnings can be found at the end
of these instructions.
History, Operation mode
4.0. HISTORY
5. OPERATION MODE
This menu is used to set various parameters, enable/disable various additional equipment and functions, various work
modes, manual test etc.... This menu is designed for end user.
NOTE:
some of the options in this menu are GREYED OUT (disabled) and they can't be changed.
They are only shown to see settings/values of some options.
View in this menu depend of selected options and additional equipment.
17
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
3
1 2
3
1 2

Operation mode
5.1. FORCED SHUTDOWN
This option is used to forced shut down of the burner in any working
stage. Before pressing the "FORCED SHUTDOWN" you must switch
off the burner on the ’’ON/OFF’’ switch and confimt ’’STOP’’ action on
the main display.
NOTE: after "FORCED SHUTDOWN" you must open the boiler
door with burner, and clean the burner grate before starting the
burner again.
This menu is used to check the relay outputs, the connection to the electrical parts and the operation of the electrical
parts of the boiler. Pressing the Start button starts the selected component, pressing the Stop component button stops
functioning.
Parts:
- burner fan: you can check the operation of the burner fan in 2 speed (maximum RPM and 1700 rpm) - when you turn
on the test, the measured RPM is displayed on the screen. If max. RPM printed more than 3000, measurer RPM is not
well positioned or is defective
- pellet transporter: the operation of the pellet transporter can be checked
- el. Heater + burner fan: the burner heater function (igniter) can be checked - to protect the burner el . heater, the
burner fan is automatically switched on when the heater is switched on
- pump P1 / DHW / RECIRCULATION: the operation of all connected pumps can be checked
- 1.circuit / 2. circuit: it is possible to check the operation of all mixing heating circuit elements (pumps, opening / closing
of actuator)
- mixing valve (with actuator (backflow protection))- it is possible to check the operation of the mixing valve actuator
(backflow protection)
- when in the manual test ( mixing valve ) is pushed button “START“ (close MV!)" valve must close the water flow
from the heating installation into boiler and open the bypass (case1 and case 3 or mirror image if the mixing valve is
installed on the left side of the boiler).
- when in the manual test ( mixing valve ) is pushed button “ START “ (open MV!)" valve must open the water flow
from the heating installation into boiler and close the bypass (case2 and case 4 or mirror image if the mixing valve is
installed on the left side of the boiler).
- additional equipment: menu for manual test of the installed additional equipment
5.2. MANUAL TEST
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
18
NOTE: The display in this menu and the "ADDITIONAL EQUIPMENT" menu depends on the configuration
selected and the installed additional equipment.

Operation mode
Case 3. 4–way mixing valve with actuator is 100% closed.
Boiler
flow
Installation
flow
Installation
backflow
Boiler
backflow
Case 4. 4–way mixing valve with actuator is 100% open
bar
M
19
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
Case 1. 3–way mixing valve with actuator is 100% closed.
Case 2. 3–way mixing valve with actuator is 100% open.
bar
M
bar
M
bar
M
Boiler
flow
Installation
flow
Installation
backflow
Boiler
backflow
OPENING DIRECTION
CLOSING DIRECTION
OPENING DIRECTION
CLOSING DIRECTION

Operation mode
5.3. PELLET TRANSPORTER
Filling feeder screw:
This option is used to initially filling of the transporter. It can also be used if the transporter is emptyed. We recommend
that you start the procedure and wait for the process to complete to make sure the transporter is full (20 min.).
Before starting this option, disconnect the plastic flexible tube from the burner and place the bucket / bag underneath.
After finishing the process, empty the pellet / bucket bag into the pellet tank and connect the plastic flexible tube back to
the burner.
Filling at start check:
This option is used to control the initially filling of the burner. By pressing the "START" key the transporter will start
working and continue continuously until the set time has elapsed (the counter starts to count down). The specified time is
set in the Initial Charge parameter in the "INSTALLATION" menu. After the transporter has stopped working it is
necessary to open the burner door and check if the pellets are covered. El. heater for correct ignition (open the lower
door and close them after checking (microswitch)) - follow the instructions on the screen. After completion of the control
and eventual correction of the initial charge time (+ 10%), the control automatically records the done change, the boiler
starts automatically without initial charge! (so you do not need to clean the pellet grate manually). If you do not want to
start automatically after the control, the "5. Operation mode-> 5.1.Forced Shutdown" may turn off the burner, but after
that you must clean the burner grate.
Possible Reasons for Correction:
If the pellets are not covered the el. heater, the pellet transporter may be either insufficiently filled or the initial filling time
should be extended (in steps of 10 seconds).
This option is used to check pellet delivery amount.
You can set the transporter working time (1) after which you want to weight the pellet.
On screen is displayed factory amount and last measuring which can be done only by authorized serviceman (if has
been done, if not factory and last weighning is the same).
In order to weigh more precisely weighing must be repeated at least 3 times.
NOTE:
If the transporter is empty, it must be filled before the burner is started.
5.4. WEIGHING CHECK
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
20
1
This manual suits for next models
5
Table of contents
Popular Heating System manuals by other brands

THERMAL INTEGRATION
THERMAL INTEGRATION DATA Extra HIU installation instructions

biawar
biawar ME 0015 Installation and operating manual

Aqua-Hot
Aqua-Hot 400 series Service manual

Benchmark
Benchmark Gledhill BoilerMate 2000 125 Design, installation and servicing instructions

Aqua-Hot
Aqua-Hot 200 Series Use and care guide

Froling
Froling Turbomat TM 400 installation instructions