CET PMC-1302 User manual

PMC-1302
Ethernet Serial Gateway
User Manual
Version: V1.1
February 28, 2020

2
CET Electric Technology
This manual may not be reproduced in whole or in part by any means without the express
written permission from CET Electric Technology (CET).
The information contained in this Manual is believed to be accurate at the time of
publication; however, CET assumes no responsibility for any errors which may appear here
and reserves the right to make changes without notice. Please consult CET or your local
representative for latest product specifications.

3
CET Electric Technology
Limited warranty
CET Electric Technology (CET) offers the customer a minimum of 12-month
functional warranty on the device for faulty parts or workmanship from the date
of dispatch from the distributor. This warranty is on a return to factory for
repair basis.
CET does not accept liability for any damage caused by device malfunctions.
CET accepts no responsibility for the suitability of the device to the application
for which it was purchased.
Failure to install, set up or operate the device according to the instructions
herein will void the warranty.
Only CET’s duly authorized representative may open your device. The unit
should only be opened in a fully anti-static environment. Failure to do so may
damage the electronic components and will void the warranty.

4
CET Electric Technology
Table of Contents
Chapter 1 Introduction ............................................................................................................................. 5
1.1 Overview ....................................................................................................................................5
1.2 Features......................................................................................................................................5
1.3 Applications................................................................................................................................5
1.4 Getting more information ..........................................................................................................5
Chapter 2 Installation ............................................................................................................................... 6
2.1 Appearance ................................................................................................................................6
2.2 Mounting....................................................................................................................................6
2.3 RS-485 Wiring.............................................................................................................................7
2.4 Ethernet Port (10/100BaseT)......................................................................................................7
2.5 Power Supply Wiring ..................................................................................................................7
Chapter 3 Operating the PMC-1302 ESG .................................................................................................. 8
3.1 Front Panel LED Indicators .........................................................................................................8
3.2 Reset Button...............................................................................................................................8
3.3 Typical Application .....................................................................................................................8
Chapter 4 Configuring the PMC-1302 ESG via Web Interface ..................................................................9
4.1 Web Console Login.....................................................................................................................9
4.2 Ethernet....................................................................................................................................10
4.3 Serial Port .................................................................................................................................10
4.4 Change Password .....................................................................................................................11
4.5 Device Information...................................................................................................................11
4.6 Exit ...........................................................................................................................................12
4.7 Reboot......................................................................................................................................12
Chapter 5 Communications through the PMC-1302 ESG .......................................................................13
5.1 Topological Graph.....................................................................................................................13
5.2 Configuring the PMC-1302 ESG................................................................................................13
5.3 Configuring PecStar iEMS .........................................................................................................14
Appendix A - Technical Specifications..................................................................................................... 17
Appendix B - Standards Compliance....................................................................................................... 18
Appendix C - Ordering Guide..................................................................................................................19

5
CET Electric Technology
Chapter 1 Introduction
This chapter provides an overview of the PMC-1302 ESG and summarizes many of its key features.
1.1 Overview
The PMC-1302 ESG is an Industrial Ethernet Serial Gateway which provides one 10/100BaseT Ethernet
port and two RS-485 ports. It is the ideal equipment for connecting RS-485 enabled serial devices to
an IP-based Ethernet LAN, making it possible to access serial devices over your Ethernet network for
any SCADA or Automation applications. The PMC-1302 ESG has been specifically designed with
industrial automation in mind and therefore provides un-surpassed performance and reliability under
the harshest industrial or commercial environments.
1.2 Features
1x10/100BaseT, 2xRS-485 port
8 kV ESD protection
1.5 kV isolation protection for Ethernet port
3kV isolation protection for RS-485
One-key reset to default factory
Simple configuration via its built-in web interface
DIN-Rail Mount
Extended operating temperature
1.3 Applications
The PMC-1302 ESG supports the efficient transfer of serial packets between the upstream
network-based applications and the downstream RS-485 serial devices via a TCP/IP connection.
Instead of using a Windows based "Virtual COM" driver with a port-mapping utility, which is often
plagued with driver incompatibility among the many different Windows versions, the PMC-1302 ESG
allows applications to directly connect to it via a TCP/IP connection for the transparent transfer of
serial packets inside TCP/IP frames to and from downstream serial devices. Perfectly suited for
communicating with industrial devices that have timing sensitive protocols, the PMC-1302 ESG
provides a reliable interface which allows SCADA or similar applications that already support direct
connection with Ethernet Gateway to communicate with serial devices independent of the serial
protocols used.
1.4 Getting more information
Additional information is available from CET via the following sources:
Visit www.cet-global.com
Contact your local representative
Contact CET directly via email at [email protected]

6
CET Electric Technology
Chapter 2 Installation
2.1 Appearance
Figure 2-1 Appearance
Figure 2-2 Upper Connector Arrangement Figure 2-3 Lower Connectors Arrangement
2.2 Mounting
The PMC-1302 ESG should be installed in a dry environment with no dust and kept away from heat,
radiation and electrical noise sources.
Installation steps:
Before installation, make sure that the DIN rail is already in place.
Move the installation clip at the back of the PMC-1302 downward to the “unlock” position.
Align the top of the mounting channel at the back of the PMC-1302 at an angle against the top of
the DIN rail as shown in Figure 2-4 below.
Rotate the bottom of the PMC-1302 towards the back while applying a slight pressure to make
sure that the device is completely and securely fixed on to the DIN rail.
Push the installation clip upward to the “lock” position to secure the PMC-1302 on to the DIN
Rail.

7
CET Electric Technology
Figure 2-4 DIN-Rail Mounting
2.3 RS-485 Wiring
The PMC-1302 ESG provides two RS-485 ports (P2 and P3). Up to 32 devices can be connected on a
RS-485 bus. The overall length of the RS-485 cable connecting all devices should not exceed 1200m.
If the master station does not have a RS-485 communications port, a RS-232/RS-485, USB/RS-485 or
Ethernet/RS-485 converter with optically isolated outputs and surge protection should be used.
The following figure illustrates the RS-485 communications connections on the PMC-1302 ESG:
Figure 2-5 RS485 Communications Connections
2.4 Ethernet Port (10/100BaseT)
The PMC-1302 ESG comes standard with an Ethernet Port (P1) using the MDI/MIDX Auto-detect RJ45
connector which means users can connect with a straight-through cable or an Ethernet cross-over
cable. The table below lists the meaning for each pin.
RJ45 Connector
Pin
Meaning
1
Transmit Data+
2
Transmit Data-
3
Receive Data+
4,5,7,8
NC
6
Receive Data-
Table 2-1 RJ45 Connector Pin Description for 10/100BaseT Applications
2.5 Power Supply Wiring
For AC supply, connect the live wire to the L/+ terminal and the neutral wire to the N/- terminal.
Figure 2-6 Power Supply Connections

8
CET Electric Technology
Chapter 3 Operating the PMC-1302 ESG
3.1 Front Panel LED Indicators
There are three LED indicators on the PMC-1302 ESG’s Front Panel as described in the following table.
LED Indicator
Color
Status
Function
Run
Green
On
System is running abnormally
Off
Power off or system is running abnormally
Blinking
Power is on and system is running normally
P2
Green
Blinking
P2 is receiving data
Yellow
Blinking
P2 is transmitting data
P3
Green
Blinking
P3 is receiving data
Yellow
Blinking
P3 is transmitting data
Table 3-1 LED Indicators
3.2 Reset Button
There is a Reset button at the lower right-hand corner of the PMC-1302’s front panel. Pressing and
holding the Reset button for 1 to 5 seconds will cause the PMC-1302 ESG to initiate a reboot
sequence. The reboot process would be completed in approximately 30 seconds. Pressing and holding
the Reset button for more than 5 seconds will reset the PMC-1302 ESG to default factory
configuration.
3.3 Typical Application
The following figure shows the typical application for the PMC-1302 ESG.
Figure 3-1 Typical Application

9
CET Electric Technology
Chapter 4 Configuring the PMC-1302 ESG via Web Interface
4.1 Web Console Login
1) Open your Internet Explorer with the scripting function enabled. To enable scripting for your
browser, right click on your Internet Explorer icon and then select Properties from the pop-up
dialog box. The Internet Options window appears. Select the Security tab and then click on the
Custom Level button near the bottom of the window. The Security Settings window appears.
Enable the three options as shown below and then click OK.
Figure 4-1 Internet Setting
2) The default IP Address of the PMC-1302 ESG’s Ethernet Port is 192.168.0.127. Configure the IP
Address and the Subnet Mask of the PC as 192.168.0.100 and 255.255.255.0 as shown below.
Figure 4-2 Setting IP Address
3) Enter the IP Address of the PMC-1302 ESG in the Address input box of the Internet Explorer and
then press <Enter>.
4) The PMC-1302’s Web Console Login page appears. Enter the User Name and Password and then
click Login. The default user name is “user”, and the default password is “123456”.

10
CET Electric Technology
Figure 4-3 Login Interface
5) Once the log-in credentials are confirmed, the following page appears.
Figure 4-4 Basic Settings
4.2 Ethernet
The P1 (Ethernet) port’s settings can be configured here based on the actual situation. Click Save to
confirm your changes. Please be reminded that the IP Address and Default Gateway for the Ethernet
port should be in the same subnet.
Figure 4-5 P1 Settings
4.3 Serial Port
The PMC-1302 comes standard with two RS-485 ports: P2 and P3. All setup parameters such as
Baudrate, Data Bits, Parity, Stop Bits, IP Port and Timeout can be configured here to match the
settings of the downstream RS485 devices. Please be reminded that the IP Port number of the Serial
Gateway feature for P2 (default = 20000) and P3 (default = 20001) should be different. Click Save to
confirm your changes. The following table shows the setup parameters for P2 and P3. Most setup
parameters are basic and self-explanatory. Please note that the Packet Timeout (ms) parameter refers
to the timeout setting for the IP connection instead of the serial connection, meaning that the IP
connection will be closed if there are no activities between the application software and the
PMC-1302 ESG for the specified amount of time. This is to prevent a potential lock up of the IP
connection at the PMC-1302 ESG if the application software fails to close the IP connection for some
unknown reasons. It is recommended that the default Packet Timeout of 300 seconds be used.

11
CET Electric Technology
Figure 4-6 P2 and P3 Settings
Parameters
Options/*Default
Parameters
Options/*Default
P2 (RS-485)
Baudrate
1,200 to 38400 bps, 9600*
Data Bits
8
Parity
None, Even*, Odd
Stop Bits
1
Packet Timeout(s)
0 to 60,000s, 300s*
Byte Timeout(ms)
0 to 60,000ms, 20ms*
Mode
TCP Sever, TCP Client
If the Mode is set to TCP Server, only the IP Port appears.
IP Port
1 to 60000, 20002*
P3 (RS-485)
Baudrate
1,200 to 38400 bps, 9600*
Data Bits
8
Parity
None, Even*, Odd
Stop Bits
1
Packet Timeout(s)
0 to 60,000s, 300s*
Byte Timeout(ms)
0 to 60,000ms, 20ms*
Mode
TCP Sever, TCP Client
The following parameters only appear when the Mode is set to TCP Client.
Please note that the TCP Client function is reserved for future applications.
Master IP Port
1 to 60000, 20001*
Master IP Address
192.168.0.100*1 to
Registration Packet
Null*
Heartbeat Packet
Null*
Heartbeat Interval(s)
0*
Reconnect Interval(s)
10*
Table 4-1 P2 and P3 Settings
4.4 Change Password
Click Change Password on the left-hand pane and the following screen appears on the right-hand
pane where the Username and Password can be changed. Click Save to save your changes.
Figure 4-7 Change Password Screen
4.5 Device Information
Click Device Information on the left-hand pane and the following screen appears on the right-hand
pane, which includes Model and Information of the PMC-1302.

12
CET Electric Technology
Figure 4-8 Device Information Screen
4.6 Exit
Click the Quit button near the top right-hand corner at any web interface to exit the Web Console. For
example, at the Device Information page, click Quit and then Confirm to exit when the dialog box
appears.
Figure 4-9 Quit from Device Information Screen
4.7 Reboot
Configuration changes will not take effect until the Reboot operation has been executed. Click Reboot
on the left-hand pane and the following screen appears on the right-hand pane. Click the Reboot
button to initiate the restart sequence. After restart, the user needs to log in again to re-gain access to
the PMC-1302 ESG’s Web Console.
Figure 4-10 Reboot Screen

13
CET Electric Technology
Chapter 5 Communications through the PMC-1302 ESG
This section provides details on how to communicate with a PMC-660 meter (Unit ID = 100) via the
PMC-1302 ESG.
5.1 Topological Graph
In this example, P2 on the PMC-1302 ESG is used. The default IP address for P1 is 192.168.0.127.
Figure 5-1 Topological Graph
5.2 Configuring the PMC-1302 ESG
To configure the PMC-1302 ESG, the user can log on to its Web Console page via the Internet Explorer
by entering the IP address of the PMC-1302 ESG’s Ethernet port in the browser’s address bar. For
example, type http://192.168.0.127/ at the address bar and then press <Enter>. Enter the default user
name “user”, the default password “123456” and then click Login to open the PMC-1302 ESG’s Web
Console.
Figure 5-2 Login Interface
In this example, P2 of the PMC-1302 ESG is used. The PMC-660’s serial port has been configured with
the following parameters:
1. Baud rate = 9600
2. Data Bits = 8
3. Parity = Even
4. Stop Bits = 1
5. Mode = TCP Server
6. IP Port = 20001

14
CET Electric Technology
It is important for the communications parameters of the PMC-1302 ESG’s P2 to be programmed to
match those of the PMC-660. The IP Port Number for P2 is 20001.
Figure 5-3 P2’s Setting
After the P2 settings of the PMC-1302 ESG has been correctly configured, click Reboot on the
left-hand pane and then click the Reboot button on the right-hand pane to save the settings. The
PMC-1302 ESG will perform a reboot operation with the new configuration. When the Log-In page
returns, the PMC-1302 ESG is now ready.
Figure 5-4 Reboot Page
5.3 Configuring PecStar iEMS
In PecStar iEMS’s PecConfig interface, select Site 1 on the left-hand pane and then click on the
Properties icon to bring up the Site Properties dialog box.
Figure 5-5 Systemconfig Interface

15
CET Electric Technology
In this example, P1 of the PMC-1302 ESG is used, and Site 1 has been configured with the following
parameters:
1. Drive Type = MODBUS Protocol Master Site Driver,
2. Polling Mode = Serial
3. Port Type = Ethernet
4. IP = 192.168.0.127
5. Port = 20001 (for P2 of PMC-1302ESG)
Figure 5-6 Site Node Properties
Select PMC-660 on the right-hand pane under the Device Name column and then click the Properties
icon on the Tool Bar to bring up the Device Properties dialog box. Change Device Type to PMC-660,
Comm ID to 100 and then click OK to save and exit the dialog box.
Figure 5-7 Device Node Properties

16
CET Electric Technology
Right click on PMC-660 on the left-hand pane, click Import SNF file and select the appropriate SNF file
from the pop-up dialog box.
Figure 5-7 Import SNF File
Click the Save icon on the Tool Bar to save the current configuration into PecStar iEMS’s database. The
PecStar iEMS software is now ready to communicate with the PMC-660 via P2 of the PMC-1302 ESG.

17
CET Electric Technology
Appendix A - Technical Specifications
10/100BaseT Ethernet Port (P1)
Speed
Connector
Cable
10/100 Mbps
RJ45
CAT5, CAT5e with a maximum 100m distance
Serial Ports (P2, P3)
P2, P3
Baudrate
RS-485 (D+, D- SH)
1200/2400/4800/9600/19200/38400 bps
Front Panel LED Indicators
Run (Green)
Blinking - System is running normally
P2, P3 (Green)
Blinking - Receiving activity
P2, P3 (Yellow)
Blinking - Transmitting activity
Protocol
Protocol
TCP, UDP, HTTP
Power Supply (L/+, N/-)
Standard
Burden
95-250VAC/DC, 47-440Hz
<3W
Protection
ESD Protection
Isolation Protection
8kV
3kV for RS485
1.5kV for Ethernet Port
Environmental Conditions
Operating Temp.
Storage Temp.
Humidity
Atmospheric pressure
-25°C to +70°C
-40°C to +85°C
5% to 95% non-condensing
70 kPa to 110kPa
Mechanical Characteristics
Unit Dimensions
Shipping Weight
Shipping Dimensions
Mounting
IP Rating
72x65x95mm
TBD
TBD
DIN-Rail Mounting
20

18
CET Electric Technology
Appendix B - Standards Compliance
Safety Requirements
Insulation
Dielectric Test
Insulation Resistance
Impulse Voltage
IEC 60255-5-2000
2kV @ 1 minute
>100MΩ
5kV, 1.2/50µs
Electromagnetic Compatibility
Electrostatic Discharge
IEC 61000-4-2:2008 Level III
Radiated Fields
IEC 61000-4-3:2008 Level III
Fast Transients
IEC 61000-4-4:2004 Level III
Surges
IEC 61000-4-5:2005 Level III
Conducted Disturbances
IEC 61000-4-6:2008 Level IV
Magnetic Fields
IEC 61000-4-8:2009 Level IV
Oscillatory waves
IEC 61000-4-12:2006 Level IV
Radio Disturbances
CISPR 22:2006, Level B
Mechanical Tests
Spring Hammer Test
IEC 255-21-1:1988 Level I
Vibration Test
IEC 255-21-1:1988 Level I
Shock Test
IEC 255-21-1:1988 Level I

19
CET Electric Technology
Appendix C - Ordering Guide
Table of contents
Other CET Gateway manuals
Popular Gateway manuals by other brands

Ericsson
Ericsson E1 quick start guide

Johnson Controls
Johnson Controls TL-MAP1810-OP installation guide

Wintec
Wintec WB-7823 Connection guide

Moxa Technologies
Moxa Technologies MGate MB3480 Quick installation guide

Samsung
Samsung WEC8500 Operation manual

AudioCodes
AudioCodes Mediant 800 Hardware installation manual

ZyXEL Communications
ZyXEL Communications 802.11g HomePlug AV ADSL2+ Gateway... user guide

STIEBEL ELTRON
STIEBEL ELTRON ISG WEB Operation and installation

MSA
MSA ProtoAir FPA-C4X Startup guide

AudioCodes
AudioCodes MediaPack 1 Series Hardware installation manual

Delta Energy Systems
Delta Energy Systems SOLIVIA Gateway M1 G2 Operation and installation manual

Arris
Arris Touchstone TG9452 user guide