Chamberlain Elite CSW/SL User manual

DO NOT USE WITH:
• OMNICONTROL BOARD OR
• ROBO CONTROL BOARD
• OMNICONTROL BOARD OR
• ROBO CONTROL BOARD
CSW / SL Surge Protection Modulefor Non-OmniControl Commercial Gate Operators
This Surge Protection Module will provide protection for the following input commands.
Please read this entire manual before installation
Chamberlain Professional Products strongly recommends the installation
of this Surge Protection Module to protect the gate operator from harmful
surges caused by lightning strike phenomenon.
It is important to recognize that the surge protection module may not
prevent damage to the gate operator in the event of a direct lightning
strike.
The success of the surge protection will be based in the proper installation
of the Surge Protection Module and the proper grounding of both the
surge protector module and the gate operator itself.
Name of Lines Protected
External Safety Loop “Command” input
External Exit Loop “Command” input
Fire Department or Key switch “Open” command
Strike Open or Push Button to open command
Radio receiver “Command” input
Ground reference and +24 VDC supply
1
1
1
1
1
2
Number of Lines Protected
Earth Ground Rod Installation
The earth ground rod must be located within 3 feet from the gate
operator. Use the proper type earth ground rod for your area.
The ground wire must be a single, whole piece of wire. Never
splice two wires for the ground wire. If you should cut the
ground wire too short, break it, or destroy its integrity, replace it
with a single wire length.
12 gauge wire
Proper grounding gives an electrical charge, such as from an
electrical static discharge or a near lightning strike, a path from
which to dissipate its energy safely into the earth.
Without this path, the intense energy generated by lightning could be
directed towards the gate operator. Although nothing can absorb the
tremendous power of a direct lightning strike, proper grounding can
protect the gate operator in most cases.
8 ft
Chamberlain Professional Products, Inc. is not responsible
for improper installation or failure to comply with all
necessary local building codes.
Part # Q411
Before digging more than 18" deep, contact local underground utility locating companies.
Avoid damaging gas, power, or other underground utility lines.
P/N Q411 – PATENT PENDING
P/N Q411 – PATENT PENDING
®
STRIKE OPEN
PUSH BUTTON
STRIKE OPEN
PUSH BUTTON
FIREDEPT
KEYSWITCH
FIREDEPT
KEYSWITCH
CLASS2
SUPPLY
CLASS2
SUPPLY
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW / SL
SURGE
SUPPRESSOR
®
™
CSW / SL Surge Protection Module
Step-by-Step instructions (con't)
STEP 13
Test all the accessories in combination with the gate operator to corroborate proper installation and functionality.
For additional protection against surges, ensure that the cables or wires going to your accessories comply
with the following rules:
All wires going the accessories must be shielded wires.
The shield must be connected as follows:
A) At the gate operator: To the chassis of the gate operator
B) At the accessories: To their chassis (Earth grounding at the accessories will be even more beneficial)
Ensure that the connections to the chassis are made secure to create good contact.
For Technical Support: 1-800-528-2806
845 Larch Avenue Elmhurst, Illinois 60126
www.chamberlain.com
© 2005 The Chamberlain Group, Inc.
All Rights Reserved
01-50739
®
™

765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
CSW / SL Surge Protection Module
Step-by-Step instructions
STEP 2
Remove J1 plug.
STEP 1
STEP 9
STEP 11
Use supplied wire nuts to connect the AC wire coming from
the outlet (through the channel in the electrical box) to the
plug (black to black and white to white wires 16 AGW).
STEP 12
STEP 10
Connect the plug of the Surge Protector to the J1 connector on
the control board.
STEP 7
Place the Surge Protector module in place of the terminal
block. Use a nut driver to secure the 2, 1 inch long hex nuts
that came with the module.
STEP 8
Remove the control board
and unscrew the lower left
hex nut under the board.
Slip the ring terminal on
the screw stud. Make sure
ring is in contact with the
control box. Re-screw the
hex nut and re-attach the
control board.
STEP 5
Use a nut driver and remove the 2 hex nuts holding the
terminal block connector (10 terminals) on the electrical box.
STEP 6
Remove the terminal block connector from the electrical box.
STEP 3
Remove the wire nuts from the black and white wires (16 AGW)
coming from the plug .
STEP 4
Remove all the accessory wires attached to the terminal block.
Make sure to mark all the wires you are removing to reconnect
them later.
OffOff
OffOff
OnOn
OnOn
OnOn
OffOff
OffOff
OffOff
OnOn
OffOff
OffOff
Gate
Operator
Main
Room
Eug. Rm
Oper. Rm
Eug. Dept.
Manu. 1 Rm
Main Dept.
Manu. 2 Rm
Air (1)
Conditioner
Air (2)
Conditioner
Conference
Room 1
Conference
Rm 2, 3
Refer.
Bus 1, 2, 3
Conference
Room 2
Comp.
Serve 2
Comp.
Serve 1
Turn the gate operator off by turning off the building/facility
breaker for the 120 Vac supply to the gate operator.
P/N Q411– PATENTPENDING
P/N Q411– PATENTPENDING
®
STRIKEOPEN
PUSHBUTTON
STRIKEOPEN
PUSHBUTTON
FIRE DEPT
KEY SWITCH
FIRE DEPT
KEY SWITCH
CLASS2
SUPPL
Y
CLASS2
SUPPL
Y
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW/ SL
SURGE
SUPPRESSOR
P/NQ411 – PATENTPENDING
P/NQ411 – PATENTPENDING
®
STRIKEOPEN
PUSHBUTTON
STRIKEOPEN
PUSHBUTTON
FIRE DEPT
KEYSWITCH
FIRE DEPT
KEYSWITCH
CLASS2
SUPPL
Y
CLASS2
SUPPL
Y
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW/ SL
SURGE
SUPPRESSOR
P/NQ411– PATENTPENDING
P/NQ411– PATENTPENDING
®
STRIKEOPEN
PUSHBUTTON
STRIKEOPEN
PUSHBUTTON
FIREDEPT
KEY SWITCH
FIREDEPT
KEY SWITCH
CLASS2
SUPPL
Y
CLASS2
SUPPL
Y
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW/ SL
SURGE
SUPPRESSOR
P/NQ411–PATENTPENDING
P/NQ411–PATENTPENDING
®
SAFTEY
LOOP
SAFTEY
LOOP
EXIT
LOOP
EXIT
LOOP
CSW / SL
SURGE
SUPPRESSOR
There is a green wire with a ring terminal coming out of the
Surge Protection module, This ring terminal MUST make good
contact with the chassis of the gate operator.
Reconnect the accessory wires to the Surge Protector. Match
them up with the label on the module. All the connectors on
the module are removable for easy wiring.
P/N Q411 – PATENTPENDING
P/N Q411 – PATENTPENDING
®
STRIKEOPEN
PUSHBUTTON
STRIKEOPEN
PUSHBUTTON
FIRE DEPT
KEY SWITCH
FIRE DEPT
KEY SWITCH
CLASS2
SUPPL
Y
CLASS2
SUPPL
Y
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW/ SL
SURGE
SUPPRESSOR
®
CSW/ SL
SURGE
SUPPRE
OffOff
OffOff
OnOn
OnOn
On
On
OffOff
OffOff
OffOff
OnOn
OffOff
OffOff
Gate
Operator
Main
Room
Eug. Rm
Oper. Rm
Eug. Dept.
Manu. 1 Rm
Main Dept.
Manu. 2 Rm
Air (1)
Conditioner
Air (2)
Conditioner
Conference
Room 1
Conference
Rm2, 3
Refer.
Bus 1, 2, 3
Conference
Room 2
Comp.
Serve2
Comp.
Serve 1
Turn the gate operator back on by turning on the
building/facility breaker for the 120 Vac supply to the gate
operator.
®
™

765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
765432189
+
10
Exit LoopSafety Loop
Or Photocell
Strike Open or
Push Button
Fire Dep
Key Switch Radio Receiver
-
CSW / SL Surge Protection Module
Step-by-Step instructions
STEP 2
Remove J1 plug.
STEP 1
STEP 9
STEP 11
Use supplied wire nuts to connect the AC wire coming from
the outlet (through the channel in the electrical box) to the
plug (black to black and white to white wires 16 AGW).
STEP 12
STEP 10
Connect the plug of the Surge Protector to the J1 connector on
the control board.
STEP 7
Place the Surge Protector module in place of the terminal
block. Use a nut driver to secure the 2, 1 inch long hex nuts
that came with the module.
STEP 8
Remove the control board
and unscrew the lower left
hex nut under the board.
Slip the ring terminal on
the screw stud. Make sure
ring is in contact with the
control box. Re-screw the
hex nut and re-attach the
control board.
STEP 5
Use a nut driver and remove the 2 hex nuts holding the
terminal block connector (10 terminals) on the electrical box.
STEP 6
Remove the terminal block connector from the electrical box.
STEP 3
Remove the wire nuts from the black and white wires (16 AGW)
coming from the plug .
STEP 4
Remove all the accessory wires attached to the terminal block.
Make sure to mark all the wires you are removing to reconnect
them later.
OffOff
OffOff
OnOn
OnOn
OnOn
OffOff
OffOff
OffOff
OnOn
OffOff
OffOff
Gate
Operator
Main
Room
Eug. Rm
Oper. Rm
Eug. Dept.
Manu. 1 Rm
Main Dept.
Manu. 2 Rm
Air (1)
Conditioner
Air (2)
Conditioner
Conference
Room 1
Conference
Rm 2, 3
Refer.
Bus 1, 2, 3
Conference
Room 2
Comp.
Serve 2
Comp.
Serve 1
Turn the gate operator off by turning off the building/facility
breaker for the 120 Vac supply to the gate operator.
P/N Q411– PATENTPENDING
P/N Q411– PATENTPENDING
®
STRIKEOPEN
PUSHBUTTON
STRIKEOPEN
PUSHBUTTON
FIRE DEPT
KEY SWITCH
FIRE DEPT
KEY SWITCH
CLASS2
SUPPL
Y
CLASS2
SUPPL
Y
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW/ SL
SURGE
SUPPRESSOR
P/NQ411 – PATENTPENDING
P/NQ411 – PATENTPENDING
®
STRIKEOPEN
PUSHBUTTON
STRIKEOPEN
PUSHBUTTON
FIRE DEPT
KEYSWITCH
FIRE DEPT
KEYSWITCH
CLASS2
SUPPL
Y
CLASS2
SUPPL
Y
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW/ SL
SURGE
SUPPRESSOR
P/NQ411– PATENTPENDING
P/NQ411– PATENTPENDING
®
STRIKEOPEN
PUSHBUTTON
STRIKEOPEN
PUSHBUTTON
FIREDEPT
KEY SWITCH
FIREDEPT
KEY SWITCH
CLASS2
SUPPL
Y
CLASS2
SUPPL
Y
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW/ SL
SURGE
SUPPRESSOR
P/NQ411–PATENTPENDING
P/NQ411–PATENTPENDING
®
SAFTEY
LOOP
SAFTEY
LOOP
EXIT
LOOP
EXIT
LOOP
CSW / SL
SURGE
SUPPRESSOR
There is a green wire with a ring terminal coming out of the
Surge Protection module, This ring terminal MUST make good
contact with the chassis of the gate operator.
Reconnect the accessory wires to the Surge Protector. Match
them up with the label on the module. All the connectors on
the module are removable for easy wiring.
P/N Q411 – PATENTPENDING
P/N Q411 – PATENTPENDING
®
STRIKEOPEN
PUSHBUTTON
STRIKEOPEN
PUSHBUTTON
FIRE DEPT
KEY SWITCH
FIRE DEPT
KEY SWITCH
CLASS2
SUPPL
Y
CLASS2
SUPPL
Y
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW/ SL
SURGE
SUPPRESSOR
®
CSW/ SL
SURGE
SUPPRE
OffOff
OffOff
OnOn
OnOn
On
On
OffOff
OffOff
OffOff
OnOn
OffOff
OffOff
Gate
Operator
Main
Room
Eug. Rm
Oper. Rm
Eug. Dept.
Manu. 1 Rm
Main Dept.
Manu. 2 Rm
Air (1)
Conditioner
Air (2)
Conditioner
Conference
Room 1
Conference
Rm2, 3
Refer.
Bus 1, 2, 3
Conference
Room 2
Comp.
Serve2
Comp.
Serve 1
Turn the gate operator back on by turning on the
building/facility breaker for the 120 Vac supply to the gate
operator.
®
™

DO NOT USE WITH:
• OMNICONTROL BOARD OR
• ROBO CONTROL BOARD
• OMNICONTROL BOARD OR
• ROBO CONTROL BOARD
CSW / SL Surge Protection Modulefor Non-OmniControl Commercial Gate Operators
This Surge Protection Module will provide protection for the following input commands.
Please read this entire manual before installation
Chamberlain Professional Products strongly recommends the installation
of this Surge Protection Module to protect the gate operator from harmful
surges caused by lightning strike phenomenon.
It is important to recognize that the surge protection module may not
prevent damage to the gate operator in the event of a direct lightning
strike.
The success of the surge protection will be based in the proper installation
of the Surge Protection Module and the proper grounding of both the
surge protector module and the gate operator itself.
Name of Lines Protected
External Safety Loop “Command” input
External Exit Loop “Command” input
Fire Department or Key switch “Open” command
Strike Open or Push Button to open command
Radio receiver “Command” input
Ground reference and +24 VDC supply
1
1
1
1
1
2
Number of Lines Protected
Earth Ground Rod Installation
The earth ground rod must be located within 3 feet from the gate
operator. Use the proper type earth ground rod for your area.
The ground wire must be a single, whole piece of wire. Never
splice two wires for the ground wire. If you should cut the
ground wire too short, break it, or destroy its integrity, replace it
with a single wire length.
12 gauge wire
Proper grounding gives an electrical charge, such as from an
electrical static discharge or a near lightning strike, a path from
which to dissipate its energy safely into the earth.
Without this path, the intense energy generated by lightning could be
directed towards the gate operator. Although nothing can absorb the
tremendous power of a direct lightning strike, proper grounding can
protect the gate operator in most cases.
8 ft
Chamberlain Professional Products, Inc. is not responsible
for improper installation or failure to comply with all
necessary local building codes.
Part # Q411
Before digging more than 18" deep, contact local underground utility locating companies.
Avoid damaging gas, power, or other underground utility lines.
P/N Q411 – PATENT PENDING
P/N Q411 – PATENT PENDING
®
STRIKE OPEN
PUSH BUTTON
STRIKE OPEN
PUSH BUTTON
FIREDEPT
KEYSWITCH
FIREDEPT
KEYSWITCH
CLASS2
SUPPLY
CLASS2
SUPPLY
SAFTEY
LOOP
SAFTEY
LOOP
RADIO
RECEIVER
RADIO
RECEIVER
EXIT
LOOP
EXIT
LOOP
–– ++
CSW / SL
SURGE
SUPPRESSOR
®
™
CSW / SL Surge Protection Module
Step-by-Step instructions (con't)
STEP 13
Test all the accessories in combination with the gate operator to corroborate proper installation and functionality.
For additional protection against surges, ensure that the cables or wires going to your accessories comply
with the following rules:
All wires going the accessories must be shielded wires.
The shield must be connected as follows:
A) At the gate operator: To the chassis of the gate operator
B) At the accessories: To their chassis (Earth grounding at the accessories will be even more beneficial)
Ensure that the connections to the chassis are made secure to create good contact.
For Technical Support: 1-800-528-2806