Charge Amps Amp Guard User manual

chargeamps.com
Charge Amps Amp Guard
Installation
Manual
English

2
English
Table of contents
1 Safety 4
2 Technical data 5
3 Product overview 7
3.1 Parts 7
3.2 Package contents 9
3.3 Status indicators 9
3.4 Reset 11
4 Before installation 11
4.1 Recommended tools 11
4.2 Internet access 12
5 Installation 13
5.1 Mount Charge Amps Amp Guard 13
5.2 Connect the current sensors 14
5.3 Connect voltage measurement 15
5.4 Mount and connect the power supply 16
5.5 Connect the Wi-Fi antenna 17
5.6 Connect the LAN cable 17
5.7 Overview of the electrical installation 18
6 Configuration 19
6.1 Connect to the Charge Amps Amp Guard Wi-Fi hotspot 19
6.2 Electrical settings 21
6.3 Wi-Fi configuration 22
6.4 Verify Charge Amps Amp Guard configuration 22
6.5 Cloud configuration 24

3
English
Failure to follow and carry out the directions, instructions and safety precautions in this Installation
Manual will invalidate the warranty and subsequently release Charge Amps AB from any and all
liability claims in connection with any injuries/damage or incidents that result from said failure
either directly or indirectly.
The manufacturer makes no warrant as to the accuracy or completeness of this document and
shall have no liability for the consequences of using such information. The manufacturer reserves
the right to make changes to information published in this document without notice.
Visit www.chargeamps.com for the latest document releases.
© Charge Amps AB. All rights reserved. Copying, amending or translating this document is strictly
forbidden without prior written approval from Charge Amps AB.
Respect the environment! Do not dispose of with household
waste! This product contains electrical or electronic components.
When this product reaches its end of life, take it to a collection
point designated by your local authority for separate recycling.
Approved in accordance with the relevant EU directives and UK legislation.

4
English
• Improper use may result in personal injury.
• The product must only be installed by a qualified electrician in
accordance with this Installation Manual.
• National installation requirements and restrictions apply.
• Inspect the product for visible damage before use.
• Never attempt to repair or use the product if it is damaged.
• Do not immerse the product in water, subject it to physical
abuse or insert foreign objects in any part of the product.
• Never attempt to disassemble the product in any way.
• Charge Amps Amp Guard is a power monitor. Only use the
product for its intended use.
WARNING! Read all instructions before use
1 Safety

5
English
2 Technical data
Measuring range (current) ± 0-63 A
Measuring range (voltage) 85-256 VAC, single to 3-phase, 50 Hz
Network LAN, Wi-Fi 802.11b/g/n 2.4 GHz
Freq. range: 2400-2500 MHz
Max power output: 20 dBm
Power supply Rated voltage: 12 VDC 0.5 A, provided
by the supplied 230 VAC (+/-15%)
50 Hz power supply
Installation DIN rail mounting in a cabinet:
1M Charge Amps Amp Guard
1M power supply
Dimensions (W x D x H) Charge Amps Amp Guard:
17.5 x 73 x 100 mm
Power supply:
17.5 x 58 x 90 mm
Current sensor cable length
Must not be tampered with to maintain
measurement accuracy.
80 cm
Maximum cable diameter for
current sensors
10 mm
Current sensors’ rated
secondary current
30(36) mA
PMD classification PMD-x, I and U, SD, Kx
Safety rating CAT III 300 V

6
English
Function characteristics according to IEC 61557-12
Function symbols Function
performance class
Measuring range Other
complementary
characteristics
I 2 ± 0-63 A
V 2 85-256 VAC
Climatic conditions Operating temperature:
-35°C to +55°C
Relative humidity: 0 - 90%
Altitude: 0 - 2000 m
Pollution Degree: 2
Ingress protection: IP2X
Indoor meter: Yes

7
English
3 Product overview
3.1 Parts
WARNING! Note the marking on the power supply.
A
B
G
C
F
D
H
I
L3
L2
L1
E

8
English
K
J
A Monitoring module
with current sensors
B Charge Amps Amp
Guard
C Wi-Fi antenna
D LAN port
E Serial number and
PIN
F Terminal block for
voltage measurement
G 12 V power cable
H 12 VDC power supply
I Power supply AC
input
J Status indicators
K Reset button (at the
top of Charge Amps
logo)

9
English
3.2 Package contents
• Charge Amps Amp Guard
• 12 VDC power supply, which powers the Charge Amps Amp Guard
• Monitoring module, consisting of a sensor cartridge and three
connected current sensors including cables
• Terminal block for voltage measurement
• Wi-Fi antenna
• 12V power cable
• Quick Guide Installation
3.3 Status indicators

10
English
Communication status:
Green light – Connected to cloud
Blue light – Connected to network
No light – No network connection
Voltage measurement status:
Green light – Ok
Red light – Error, incorrect phase order
No light – Voltage measurement not connected
Current measurement status:
Green light – Ok
Red light – Error, incorrect phase order
No light – Current measurement not connected
Charge Amps logotype:
Lights On – Power On
Lights Off – Power Off

11
English
3.4 Reset
If necessary, the Charge Amps Amp Guard can be restarted using
the reset button. Data stored in the Charge Amps Cloud will not
be affected.
1. Gently press the reset button at the top of the Charge Amps
logo.
2. All lights will turn off briefly once the reset has been initiated.
4 Before installation
4.1 Recommended tools
• Smart phone, tablet or computer on Wi-Fi network
• Flat head screwdriver, max width 3 mm
• Multimeter, wire stripper
• Phase sequence tester

12
English
4.2 Internet access
IMPORTANT!
The Charge Amps Amp Guard must be connected to the
internet to transmit data to the load balancing function which
communicates with the charging station(s).
The customer must therefore provide an internet connection via a
network cable (LAN) or Wi-Fi (802.11b/g/n 2.4 GHz).
• LAN connection, if available, is preferred for a more secure
connection to the internet. The network cable must be at least
Cat6.
• Normally, no firewall changes are necessary.
• Wi-Fi signal strength needs to be -80dBm or better (-30dBm
equals very good signal, -90dBm equals very poor signal).
• The network needs to have DHCP enabled to ensure an IP
address is automatically assigned to the Charge Amps Amp
Guard.

13
English
5 Installation
Install the Charge Amps Amp Guard directly downstream of the
building’s main circuit breaker panel to monitor all power usage.
For single-phase installations, L2 and L3 shall not be used.
5.1 Mount Charge Amps Amp Guard
1. Pull the DIN-rail lock downwards and twist the Charge Amps
Amp Guard onto the DIN-rail.
2. Secure in place by pushing the DIN-rail lock back in place.
Please note that an additional slot will be needed for the power
supply.

14
English
5.2 Connect the current sensors
Charge Amps Amp Guard comes with three current sensors, one
for each phase.
1. Clamp the current sensor around the incoming phase.
The mounting direction is marked on the current sensor.
The arrow must point in the current direction.
IMPORTANT!
The current sensors must be connected to the correct phase and
properly positioned around the main power cables according to
the direction indicators on the clamps.
2. Connect the sensor cartridge to the top of the Charge Amps
Amp Guard.
L3
L2
L1

15
English
5.3 Connect voltage measurement
For installations with power-generating equipment
Solar panels, wind power, or plans to introduce such equipment
require the voltage measurement to be connected.
For installations without power-generating equipment
Connection of the voltage measurement is optional.
Do not remove the terminal block in the bottom of the Charge
Amps Amp Guard as it may be needed if voltage measurement is
connected in the future.
IT grid networks
IT grid is used in parts of Norway, Belgium and Albania.
In IT grid installations, L2 must be connected to both L2 and N.
The network type must also be configured, see chapter Electrical
Settings.
IMPORTANT!
Each phase must be connected to the correct terminal connector
for voltage measurement to function correctly. L1, L2 and L3 must
be protected by circuit breakers in the normal way.
1. Turn the power off at the main circuit breaker panel.
2. Connect phases and neutral to the supplied terminal block.

16
English
3. Connect the terminal block to the bottom of the Charge Amps
Amp Guard.
5.4 Mount and connect the power
supply
The power supply provides 12V to the Charge Amps Amp Guard.
The power supply is pre-configured to 12V. If needed, voltage can
be adjusted using the adjustment screw on the front of the power
supply.
1. Connect the power supply to the mains (L, N) according to the
labels on the power supply, i.e. N to AC(N) (left side) and L1 to
AC(L) (right side).
2. Insert the supplied 12V power cable into the power supply
according to the label on the power supply, i.e. marked cable to
+Vo (left side) and black cable to -Vo (right side).
3. Mount the power supply onto the DIN-rail.
4. Connect the 12V power cable to the sensor cartridge.

17
English
5. Turn the power on at the main circuit breaker panel.
5.5 Connect the Wi-Fi antenna
1. Mount the supplied Wi-Fi antenna to the Charge Amps Amp
Guard.
2. NB: Depending on the type of cabinet, an external Wi-Fi
antenna may be needed. The external antenna must be of non-
grounded type.
5.6 Connect the LAN cable
If applicable, connect the network cable to the LAN port.
The cable must be Cat6.
WARNING! Note the marking on the power supply.

18
English
5.7 Overview of the electrical
installation
WARNING! Note the marking on the power supply.
Optional, see chapter Connect voltage
measurement.

19
English
6 Configuration
Once the electrical installation has been completed, Charge Amps
Amp Guard needs to be properly configured.
6.1 Connect to the Charge Amps Amp
Guard Wi-Fi hotspot
IMPORTANT!
Only 2.4GHz Wi-Fi is supported.
The Wi-Fi hotspot is only active for 10 minutes after power up.
To restart Charge Amps Amp Guard, see chapter Reset.
1. Connect to the Charge Amps Amp Guard Wi-Fi hotspot using
a smartphone, tablet or a computer. To avoid conflicting Wi-
Fi, set to airplane mode, turn on Wi-Fi, then connect to the
hotspot.
2. The network name, i.e. the SSID, is AG_******* (* = The last 7
digits/letter of the Charge Amps Amp Guard’s serial number).
The serial number can be found on the front label of the
Charge Amps Amp Guard (the one with a QR-code) and on the
front page of the Quick Guide.
Enter the Charge Amps Amp Guard PIN as the Wi-Fi password
to sign in to the Wi-Fi hotspot.
The PIN is an 8-digit code that can be found on the Charge
Amps Amp Guard front label and on the front page of the
Quick Guide.

20
English
3. When connected to the Wi-Fi hotspot, open a web browser
and type in 192.168.251.1 as the URL.
4. Enter the Charge Amps Amp Guard PIN to sign in.
5. Click Login.
Other manuals for Amp Guard
6
Table of contents
Popular Audio & Video Accessories manuals by other brands

Delta Electronics
Delta Electronics AFE075A43A user manual

BBC Bircher
BBC Bircher Hyperion 3D Quick installation guide

ELM
ELM EDR ECOSmart instruction manual

South-Tek Systems
South-Tek Systems Quick-Check 6 manual

Lutron Electronics
Lutron Electronics Energi Savr Node QSN-4T16-S installation guide

FSR
FSR BMS 1032 Installation and operating manual