CIAT 99DA-SEI-EC01 Quick start guide

Wiring diagram 99DA-SEI-EC01
Content Page
2-pipe units 2
2-pipe units change over 3
4-pipe units 4
2-pipe units with elecric heater 5
Connecting multiple fan coil units 6
Various settings are possible with this type of thermostat. Read the installation manual carefully before installation. For proper
operation, check the parameters indicated per system and adjust them if necessary.
To access the configuration menu, simultaneously press the and buttons for a few seconds until “COn”
(configuration) appears on the display. Once entered in configuration menu, pressing scrolls through the
various parameters, identified with P and the parameter number, from P01 to P25.
When scrolling the parameters pressing button or or displays its current value.
To change the value, when it is displayed, press button or .
The configuration end is displayed with “End”. Press again to save the configuration and return to normal operation.
The extended parameters C01-C23 allow an advanced thermostat configuration. When the display shows “COn“ at
configuration start or “End“ at configuration end, press the button to access the extended parameters.
APPLICATION
Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V –on/off
REMARKS
1: All electrical connections must be made in accordance with the local regulations
2: ---------- External cables (not supplied by CIAT)
3: Minimum cable diameter 1,5 mm2(230V~)
4: Use shielded cable for 0-10V signal cable of the fan motor
5: For other connections/information, see the electrical wiring diagram of the relevant unit 18-05-2022

L
N
3
4
5
6
7
8
9
10
11
12
13
14
15
16
L
3
8
5
14
A+
A-
CF
SA
E / I
RDC
5
5
GND
V HEAT
V COOL
V FAN
12
10
Major
Line
Ph
N
Ph
6
V1
V2
Ph
Ph
6
C
Comfort
Line
Ph
N
Ph
6
V1
V2
Ph
Ph
6
C
PE
N
Ph
PE
N
Ph
PE
N
L
PE
N
L
JP1
TB
A1F / X2
TB
TB
XB
XB
XB
XB
XB
XB
XB
XB
SM
/
/
99DA-SEI-EC01
Coadis
Line
XB
XB
Controlbox on the motor
XB
Various settings are possible with this type of thermostat. Read the
installation manual carefully before installation. For proper operation,
please check the parameters below and adjust if necessary:
P01: 0 (system type)
P02: 1 (manual change-over heat/cool) *
C15: 2 V (minimum fan speed)
C16: Maximum fan speed (V) **
* Heating or cooling modes are selected by keeping the button
depressed for some seconds, until the display shows one of the
following texts which indicates the current mode:
HEA : Heating mode
COO : Cooling mode
Then, by pressing the arrow keys, the user can change the desired
operating mode.
** With the Comfort Line and the Major Line with ducting: the capacity (air
volume) depends on the resistance in the duct and the grilles. In
most cases, the maximum speed should be set between 5V and 8V.
Explanations:
E/I = Change-over contact heating/cooling *
RDC = Contact to activate the “Economy” function (set P18) *
SM = Supply water sensor **
SA = Room sensor (if applied P11 = 1) **
CF = Window contact * and **
XB, TB, A1F / X2 = terminals fan coil unit
* The functions of these outputs can be changed with parameters C17,
C18 en C19. See for more information the installation manual.
** Use a separate shielded cable (see for more information the
installation manual)
Melody 2
POWER SUPPLY 230V~
Ph
N
Ph
6
+
-
Ph
Ph
6
C
PE
N
Ph
NOTE: Check whether the unit is
suitable for 0-10V control of the
fan motor
2-PIPE FAN COIL UNITS
APPLICATION
Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V –on/off
REMARKS
1: All electrical connections must be made in accordance with the local regulations
2: ---------- External cables (not supplied by CIAT)
3: Minimum cable diameter 1,5 mm2(230V~)
4: Use shielded cable for 0-10V signal cable of the fan motor
5: For other connections/information, see the electrical wiring diagram of the relevant unit
Coadis Line 600
6 = w/o condensate pump
12 = with condensate pump
Remark 4
18-05-2022

L
N
3
4
5
6
7
8
9
10
11
12
13
14
15
16
L
CF
SA
E / I
RDC
GND
V HEAT
V COOL
V FAN
Ph
N
Ph
6
V1
V2
Ph
Ph
6
C
PE
N
Ph
N
L
JP1
TB
A1F / X2
TB
TB
XB
XB
XB
XB
SM
/
/
99DA-SEI-EC01
Various settings are possible with this type of thermostat. Read the
installation manual carefully before installation. For proper operation,
please check the parameters below and adjust if necessary:
P01: 0 (system type)
P02: 1 (automatic change-over heat/cool)
C01: 17 (if water temp. lower than this value →cool) *
C02: 30 (if water temp. higher than this value →heat) *
C15: 2 V (minimum fan speed)
C16: Maximum fan speed (V) **
* Install a water temperature sensor (SM ***) on a pipe where the
water supply can be measured and connect it to terminals 13 and 14.
** With the Comfort Line and the Major Line with ducting: the capacity (air
volume) depends on the resistance in the duct and the grilles. In
most cases, the maximum speed should be set between 5V and 8V.
*** Accessory, 99DA-SEI-SEN01
Explanations:
E/I = N/A *
RDC = Contact to activate the “Economy” function (set P18) *
SM = Supply water sensor (change-over based on C01 and C02) **
SA = Room sensor (if applied P11 = 1) **
CF = Window contact * and **
XB, TB, A1F / X2 = terminals fan coil unit
* The functions of these outputs can be changed with parameters C17,
C18 en C19. See for more information the installation manual.
** Use a separate shielded cable (see for more information the
installation manual)
PE
3
8
5
14
A+
A-
5
5
12
10
PE
N
L
Major
Line Melody 2
Coadis
Line
XB
XB
XB
Ph
N
Ph
6
Ph
Ph
6
C
PE
N
Ph
Ph
N
Ph
6
V1
V2
Ph
Ph
6
C
PE
N
Ph XB
XB
XB
XB
Comfort
Line
+
-
NOTE: Check whether the unit is
suitable for 0-10V control of the
fan motor
POWER SUPPLY 230V~
2-PIPE FAN COIL UNITS CHANGE-OVER HEAT/COOL
WITH WATER SENSOR
APPLICATION
Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V –on/off
REMARKS
1: All electrical connections must be made in accordance with the local regulations
2: ---------- External cables (not supplied by CIAT)
3: Minimum cable diameter 1,5 mm2(230V~)
4: Use shielded cable for 0-10V signal cable of the fan motor
5: For other connections/information, see the electrical wiring diagram of the relevant unit
Controlbox on the motor
Coadis Line 600
6 = w/o condensate pump
12 = with condensate pump
Remark 4
18-05-2022

L
N
3
4
5
6
7
8
9
10
11
12
13
14
15
16
L
CF
SA
E / I
RDC
GND
V HEAT
V COOL
V FAN
Ph
N
Ph
7
6
V1
V2
Ph
Ph
PE
N
Ph
N
L
JP1
TB
TB
XB
XB
XB
99DA-SEI-EC01
Various settings are possible with this type of thermostat. Read the
installation manual carefully before installation. For proper operation,
please check the parameters below and adjust if necessary:
P01: 1 (system type)
P02: 0 or 1 (1 = automatic change-over heat/cool)
C15: 2 V (minimum fan speed)
C16: Maximum fan speed (V) *
* With the Comfort Line and the Major Line with ducting: the capacity (air
volume) depends on the resistance in the duct and the grilles. In
most cases, the maximum speed should be set between 5V and 8V.
Explanations:
E/I = N/A *
RDC = Contact to activate the “Economy” function (set P18) *
SM = Supply water sensor **
SA = Room sensor (if applied P11 = 1) **
CF = Window contact * and **
XB, TB, A1F / X2 = terminals fan coil unit
* The functions of these outputs can be changed with parameters C17,
C18 en C19. See for more information the installation manual.
** Use a separate shielded cable (see for more information the
installation manual)
SM
PE
A1F / X2
6
N
7
TB
XB
C
3
8
5
15
A+
A-
5
5
10
10
PE
N
L
12
15
14
Major
Line Melody 2
Coadis
Line
XB
XB
Ph
N
Ph
7
Ph
Ph
PE
N
Ph
6
N
7
XB
C
Ph
N
Ph
7
V1
V2
Ph
Ph
PE
N
Ph XB
XB
XB
Comfort
Line
6
N
7
XB
C
+
-
6
6
NOTE: Check whether the unit is
suitable for 0-10V control of the
fan motor
POWER SUPPLY 230V~
4-PIPE FAN COIL UNITS
APPLICATION
Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V –on/off
REMARKS
1: All electrical connections must be made in accordance with the local regulations
2: ---------- External cables (not supplied by CIAT)
3: Minimum cable diameter 1,5 mm2(230V~)
4: Use shielded cable for 0-10V signal cable of the fan motor
5: For other connections/information, see the electrical wiring diagram of the relevant unit
Controlbox on the motor
Coadis Line 600
6 = w/o condensate pump
12 = with condensate pump Remark 4
18-05-2022

L
N
3
4
5
6
7
8
9
10
11
12
13
14
15
16
L
CF
SA
E / I
RDC
GND
V HEAT
V COOL
V FAN
Various settings are possible with this type of thermostat. Read the
installation manual carefully before installation. For proper operation,
please check the parameters below and adjust if necessary:
P01: 2 (system type)
P02: 0 or 1 (1 = automatic change-over heat/cool)
C14: 30 % (minimum fan speed when the electric heater is
switched on) *
C15: 2 V (minimum fan speed)
C16: Maximum fan speed (V) **
* With the Comfort Line and the Major Line with ducting: check
minimum airflow, see installation manual of the relevant unit.
** With the Comfort Line and the Major Line with ducting: the capacity (air
volume) depends on the resistance in the duct and the grilles. In
most cases, the maximum speed should be set between 5V and 8V.
Explanations:
E/I = N/A *
RDC = Contact to activate the “Economy” function (set P18) *
SM = Supply water sensor **
SA = Room sensor (if applied P11 = 1) **
CF = Window contact * and **
XB, TB, A1F / X2 = terminals fan coil unit
* The functions of these outputs can be changed with parameters C17,
C18 en C19. See for more information the installation manual.
** Use a separate shielded cable (see for more information the
installation manual)
Ph
N
Ph
7
6
V1
V2
Ph
Ph
6
C
PE
N
Ph
N
L
JP1
1TB
TB
1TB
XB
XB
XB
XB
SM
99DA-SEI-EC01
PE
A1F / X2
3
8
5
15
A+
A-
5
5
12
10
PE
N
L
14
Major
Line Melody 2
Coadis
Line
XB
XB
XB
Ph
N
Ph
7
Ph
Ph
6
C
PE
N
Ph
Ph
N
Ph
7
V1
V2
Ph
Ph
6
C
PE
N
Ph XB
XB
XB
XB
Comfort
Line
6
+
-
6
NOTE: Check whether the unit is
suitable for 0-10V control of the
fan motor
POWER SUPPLY 230V~
2-PIPE FAN COIL UNITS WITH ELECTRIC HEATER(S)
APPLICATION
Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V –on/off
REMARKS
1: All electrical connections must be made in accordance with the local regulations
2: ---------- External cables (not supplied by CIAT)
3: Minimum cable diameter 1,5 mm2(230V~)
4: Use shielded cable for 0-10V signal cable of the fan motor
5: For other connections/information, see the electrical wiring diagram of the relevant unit
Controlbox on the motor
Coadis Line 600
6 = w/o condensate pump
12 = with condensate pump Remark 4
18-05-2022

15
14
A+
A-
7
6
V1
V2
6
7
V1
V2
PE
N
Ph
PE
N
Ph
PE
N
LTB
XB
XB
XB
XB A1F / X2
15
14
A+
A-
7
6
V1
V2
6
7
V1
V2
PE
N
Ph
PE
N
Ph
PE
N
LTB
XB
XB
XB
XB A1F / X2
N
L
PE
NPE
L
N
3
4
5
6
7
8
9
10
11
12
13
14
15
16
GND
V HEAT
V COOL
V FAN
JP1
99DA-SEI-EC01
+
-L
NPE
+
-L
Maximaal 4
units op 1
thermostaat
aansluiten
Major
Line
Comfort
Line
Coadis
Line Melody 2
7
+
-
PE
N
Ph XB
7
6
+
-
PE
N
Ph XB
6
NOTE: Check whether the unit is
suitable for 0-10V control of the
fan motor
POWER SUPPLY 230V~
Connecting multiple fan coil units
APPLICATION
Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V –on/off
REMARKS
1: All electrical connections must be made in accordance with the local regulations
2: ---------- External cables (not supplied by CIAT)
3: Minimum cable diameter 1,5 mm2(230V~)
4: Use shielded cable for 0-10V signal cable of the fan motor
5: For other connections/information, see the electrical wiring diagram of the relevant unit
PAY ATTENTION:
•When connecting multiple units to 1 thermostat, apply 1 central
power supply. DO NOT apply a separate power supply per unit.
•Connect up to 4 units to 1 thermostat
•Connect units with electric heating ONLY if the electric heating is
switched with a relay.
•For other connections, see the unit electrical wiring diagram
To next units
Controlbox on the motor
Controlbox on the motor
Coadis Line 600
6 = w/o condensate
pump
12 = with condensate
pump
Coadis Line 600
6 = w/o condensate
pump
12 = with condensate
pump
Remark 4
18-05-2022
Table of contents