14 AWR MTD - AWR MTD/B GB 01/2009
ELECTRICAL CONNECTIONS I A
The heat pumps must be installed downstream of a main
switch (QF1, see wiring diagram), as required by the stan-
dards in force in the country where the unit is installed. Con-
nection to the mains power supply and the connection of the
flow switch to the corresponding terminals must be per-
formed by authorised personnel in compliance with the stan-
dards in force.
For all electrical work, refer to the electrical wiring diagrams
in this manual.
It is also recommended to check that:
- The characteristics of the mains electricity supply are ade-
quate for the power ratings indicated in the electrical spec-
ifications below, also bearing in mind the possible use of
other equipment at the same time.
Power to the unit must be turned on only after installa-
tion work (plumbing and electrical) has been completed.
All electrical connections must be carried out by quali-
fied personnel in accordance with legislation in force in
the country concerned
Respect instructions for connecting phase, neutral and
earth conductors..
The power line should be fitted upstream with a suitable
device to protect against short-circuits and leakage to
earth, isolating the installation from other equipment.
Voltage must be within a tolerance of ±10% of the rated
power supply voltage for the unit (for three phase units,
the unbalance between the phases must not exceed 3%).
If these parameters are not respected, contact the elec-
tricity supply company.
For electrical connections, use double insulation cable
in conformity with legislation in force in the country con-
cerned..
A thermal overload switch and a lockable mains dis-
connect switch, in compliance with the CEI-EN stan-
dards (contact opening of at least 3mm), with ade-
quate switching and residual current protection
capacity based on the electrical data table shown
below, must be installed as near as possible to the
appliance.
An efficient earth connection is obligatory.
The manufacturer cannot be held liable for any damage
caused by the failure to correctly earth the unit.
In the case of three phase units, ensure the phases
are connected correctly.
Do not use water pipes to earth the unit.
Electrical data at maximum conditions allowed (full load)
Size Power Maximum values Max Max
Fuses (5x20T 250V)
supply Compressor Fan/fans Pump Total
Aux. heaters (3) values (1) values (2)
F.L.I. N.L.A. L.R.A. F.L.I. F.L.A. F.L.I. F.L.A. F.L.I. F.L.A. F.L.I. F.L.A. F.L.A. F.L.A. FU1 FU2 FU3 FU4 FU5
(V-Ph-Hz) (kW) (A) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)
AWR 0011 MTD 230~50 3,4 16,0 26 0,2 0,6 0,2 1,0 3,8 17,6 3,0 13,0 17,6 17,6 6.3A 8A 1A 1A 1A
AWR 0025 MTD 230~50 4,1 19,0 37 0,2 0,6 0,1 1,2 4,4 20,8 4,0 17,4 20,8 20,8 1.6A 8A 1A 1A 1A
AWR 0031 MTD 230~50 4,9 23,0 44 0,2 0,6 0,1 1,2 5,2 24,8 5,0 21,7 24,8 24,8 1.6A 8A 1A 1A 1A
AWR 0041 MTD 230~50 6,6 27,0 45 0,2 0,6 0,1 1,2 6,9 28,8 7,0 30,4 28,8 31,6 1.6A 8A 1A 1A 1A
AWR 0031 MTD 400-3N~50 4,5 8,0 48 0,2 0,6 0,1 1,2 4,8 9,8 9,0 13,0 9,8 14,2 1.6A 8A 1A 1A 1A
AWR 0041 MTD 400-3N~50 5,8 10,0 64 0,2 0,6 0,1 1,2 6,1 11,8 9,0 13,0 11,8 14,2 1.6A 8A 1A 1A 1A
AWR 0051 MTD 400-3N~50 6,9 11,8 64 0,2 0,6 0,1 1,2 7,2 13,6 9,0 13,0 13,6 14,2 1.6A 8A 1A 1A 1A
AWR 0061 MTD 400-3N~50 8,9 15,0 74 0,2 0,6 0,1 1,2 9,2 16,8 9,0 13,0 16,8 16,8 1.6A 8A 1A 1A 1A
F.L.I. Maximum power input
F.L.A. Maximum current input
L.R.A. Start-up current
(1) Maximum values for sizing the protection switches and power supply cables for AWR MTD/B and AWR MTD/S/B units
(2) Maximum values for sizing the protection switches and power supply cables for AWR MTD and AWR MTD/S units (with
electric heaters)
(3) Built-in heaters for versions AWR MTD and AWR MTD/S