
- 11 -
delay in order to protect the pump of the boiler. See Section 7.3 for more
information on the delay funcions.
When the two units of the thermostat can only be located on or outside the
boundary of the range due to the layout of the building or the shielding eect of
the building structures between the units then, in order to guarantee reliable RF
connection, please install a
COMPUTHERM
Q2RF type RF transmitter between
the two units.
7.2 Putting the receiving unit into operation
Turn on the power supply to the receiver unit. A few seconds after the LED
lights ash once, the receiver unit becomes ready for operation. This state is
indicated by the blue LED with the "A/M" sign. The thermostats and receiver in
the basic package are factory sychronized. If the receiver still does not receive
commands from one of the thermostat switches or you want to connect additional
thermostats to the receiver, you can synchronize a thermostat with the receiver
by following the steps below:
In the automatic mode of the receiver (blue LED is lit), press and hold one of the
buttons on the receiver (e.g. for zone number 1) (for about 3 seconds) until the
LED next to the button ashes red. If you want a thermostat to control more than
one zone, you must perform this step for each such zone. After the red LED for
each zone with which you want to synchronize the thermostat ashes, press and
hold the thermostat "LEARN" button located on the main panel of the thermo-
stat, and keep it depressed (approx. 10 seconds) until the red LED (s) on the re-
ceiver do not stop ashing (they go out or light up continuously depending on the
temperature set on the thermostat). The receiver then "learns" the transmitters'
(thermostats') security code. The safety code will not be lost even during a power
outage, the device memorizes it automatically.
After tuned together, the receiver unit receives switching signals from the
thermostats, controls the boiler (or air conditioner) and gives commands to open/
close the heating zone valves associated with the thermostats. The receipt of
switching signals is indicated by the switched on or o state of the red LED
associated with the thermostat on the receiver. By repeating the above steps,
tune all of the thermostats and the receiver together.
7.3 Delay of the outputs
When designing the heating zones - in order to protect the pumps - it is advisable
to keep at least one heating circuit that is not closed by a zone valve (e.g. bath-
room circuit). If there are no such zones, then in order to prevent the heating sys-
tem from an event in which all heating circuits are closed but a pump is switched
on, the zone controller has two types of delay functions.
Turn on delay
If this function is activated and the outputs of the receiver are switched o, then in