Cooper Controls Greengate OSW-P-0451-347-V User manual

Installation Instructions
IN TALLATION
RATING
COVERAGE
The OSW-P-0451-347 is a self-contained motion-sensing lighting control which
replaces a conventional wall switch for energy savings and convenience. Lights
turn off automatically after a room is vacated.
The OSW-P-0451-347 is designed to detect motion from a heat-emitting source
(such as a person entering a room) within its field-of-view and automatically
switch lights on and off. Lights will remain on until no motion is detected and a
preset time delay has expired.
The OSW-P-0451-347 includes a self-adjusting feature that will maintain opti-
mum performance by automatically self-adjusting sensitivity and time delay in
real time based on occupant activity.
Model OSW-P-0451-347 offers a choice of Automatic On or Manual On modes.
In the Automatic On mode, the lights turn on automatically when a person
enters the room. In the Manual On mode, lights are turned on by pressing the
touchplate on the switch. Modes can be changed by flipping the concealed
switch under the touchplate. (see Checkout & Adjustment)
In either mode, lights will remain on as long as motion is detected in the room.
When no motion is detected, the lights will turn off automatically after the pre-
set time delay. In Manual On mode, a “grace period” of approximately ten sec-
onds follows the lights turning off automatically. During that grace period, lights
can be turned on again by motion. In the Automatic On mode, lights will be
turned on by motion at any time.
At any time, lights may be turned off while the room is occupied by pressing the
touchplate. The OSW-P-0451-347 is fully self-resetting; lights turned off manu-
ally in Automatic On mode will stay off while the room remains occupied. After
the room is vacated and the pre-set time delay and grace period have elapsed,
the lights will remain off until turned on automatically the next time someone
enters the room.
The OSW-P-0451-347 can be used with a standard toggle switch to split the
lighting load for rooms that are wired for two switches as shown in the Wiring
Diagram. Control of a second circuit with a single switch is possible with use of
Greengate Model OSW-P-0451-D347 Dual Level Automatic Self-Adjusting Wall
Switch.
The Lighting Sweep feature forces an initial delay on “Power Up” to prevent
false activation in buildings with computer controls systems.
DE CRIPTION OF OPERATION
LOCATION
22'
16'
32'
26'
COVERAGE DIAGRAM
SuperSwitch®2 PIR Wall Switch
347 VAC
WIRING
• Read all instructions on both sides of this sheet first.
• Plan all component locations carefully.
• Install in accordance with all local codes.
• For use with 347 VAC only.
• ot for use where temperatures fall below 60oF or exceed 90oF.
• For indoor use only.
CAUTION: Before installing or performing any service on a Greengate system, the
power MUST e turned off at the ranch circuit reaker. According to NEC 240-
83(d), if the ranch circuit reaker is used as the main switch for a fluorescent light-
ing circuit, the circuit reaker should e marked “SWD.”
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact
fluorescent lamps (CFLs) is shortened y frequent automatic or manual switching.
Check with CFL and allast manufacturer to determine the effects of cycling.
GENERAL INFORMATION
Model # O W-P-0451-347-A
Model # O W-P-0451-347-V
Model # O W-P-0451-347-W
The OSW-P-0451-347 is designed for
offices up to 300 square feet. Although
total coverage of minor motion is 450
square feet, wall switches are normally
mounted off-center in a room which
reduces the coverage attainable.
The OSW-P-0451-347 can replace one switch in any standard single or
double gang box. It may be installed in the same manner as an ordinary
wall switch.
Wire the OSW-P-0451-347 as described in the wiring section.
Mount OSW-P-0451-347 in the junction box.
TYPICAL OFFICE LAYOUT
ONE CIRCUIT - ONE LIGHTING LOAD (FIGURE 1)
•Connect the blue wire to the switch leg for the load.
•Connect the ground wire. (Device must be grounded for proper operation)
•Connect the black wire to the hot lead.
•Connections are polarity sensitive.
ONE CIRCUIT - TWO LIGHTING LOAD (FIGURE 2)
FOR THREE-WAY WIRING (FIGURE 3)
CAUTIO : If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit to the sensor. Split one circuit
into two switch legs and cap the unused hot lead inside the box.
The combination of Load 1 and Load 2 must not exceed the maximum load rating. Consult with the building manager and occupant to determine which
lights should be off (Load 2) when the toggle switch adjacent to the sensor is open (off).
OSW-P-0451-347 must always control Load 1, while its control of Load 2 is selected manually by opening and closing the toggle switch. Connect the
blue wire to the switch leg for Load 1 and one side of the toggle switch for Load 2. Connect the other side of the toggle switch to the switch leg for Load
2. Connect ground lead. Finally, connect the black wire to the hot lead. Connections are polarity sensitive.
When installing OSW-P-0451-347 in a new junction box, choose
the switch location carefully to provide optimum coverage of the
occupied area. When replacing an existing wall switch, bear in
mind that there must be a clear line of sight between the sensor
and the area to be covered. Avoid pointing the OSW-P-0451-347
directly into the hallway where it may detect passers-by.
347 VAC Incandescent or Fluorescent Note: No minimum load requirement.
Maximum Load: 1.7 amps, 600 Watts
CAUTION: For use with 347 VAC only. Do not use with any other voltage. Do not wire to control receptacle circuits. VERIFY that the connect-
ed load does not exceed the OSW-P-0451-347 ratings. Use twist-on wire connectors for all connections. All installations should be in compliance with
the ational Electric Code and all state and local codes. Model OSW-P-0451-347 can be wired to control both an exhaust fan and lighting provided the
total load does not exceed the maximum load rating (in Amps) for the automatic wall switch.
20'
3'
SIDE VIEW

CHECKOUT AND ADJU TMENT
TROUBLE HOOTING GUIDE
OVERRIDE WITCH
P/ 910-0466
REV C
All products manufactured by Cooper Controls and identified with the Greengate brand are warranted to be free from defects in material and workmanship and shall conform
to and perform in accordance with Seller’s written specifications for a period of :
Five (5) years from date of shipment for all occupancy sensors and Three (3) years from date of factory invoice for our hardware and software on Lighting Control Panels.
We warranty all our standard relays for a period of 10 years from date of factory invoice. We guarantee the performance of our system to specifications or your money back.
This warranty will be limited to the repair or replacement, at Seller’s discretion, of any such goods found to be defective, upon their authorized return to Seller. This limited
warranty does not apply if the goods have been damaged by accident, abuse, misuse, modification or misapplication, by damage during shipment or by improper service.
There are no warranties, which extend beyond the hereinabove-limited warranty, I CLUDI G, BUT OT LIMITED TO, THE IMPLIED WARRA TY OF MERCHA TABILITY
A D THE IMPLIED WARRA TY OF FIT ESS. o employee, agent, dealer, or other person is authorized to give any warranties on behalf of the Seller or to assume for the
Seller any other liability in connection with any of its goods except in writing and signed by the Seller. The Seller makes no representation that the goods comply with any pre-
sent or future federal, state or local regulation or ordinance. Compliance is the Buyer’s responsibility. The use of the Seller’s goods should be in accordance with the provision
of the ational Electrical Code, UL and/or other industry or military standards that are pertinent to the particular end use. Installation or use not in accordance with these
codes and standards could be hazardous.
An Override switch is located under the OSW-P-0451-347 touchplate.
This switch should remain in the OFF position at all times, except in the
event of unit malfunction. Move the DIP switch to O to override the
Sensor and turn the lights on.
347 VAC
BLACK
BLUE
GREEN
347 VAC GROUND
NEUTRAL
LOAD 1
Single Level Switching
BARE WIRE
GROUND
347 VAC
BLACK
BLUE
GREEN
347 VAC GROUND
NEUTRAL
LOAD 1 LOAD 2
TOGGLE SWITCH
LOAD 2 SWITCHLEGLOAD 1 SWITCHLEG
Dual Level Switching
Using Additional Toggle Switch
BARE WIRE
GROUND
347 VAC
BLACK
BLUE
GREEN
347 VAC GROUND
NEUTRAL
LOAD 1
BLACK
BLUE
GREEN
347 VAC GROUND
NEUTRAL
Three-way wiring diagram:
Lights will turn-o automatically when
sensor that detected motion last, times out.
TRAVELLERS
BARE WIRE
GROUND
BARE WIRE
GROUND
FIGURE 2
FIGURE 3
FIGURE 1
1. Immediately after applying power to the lighting circuit, wait approximately one to two minutes for the switch to power up and stabilize.
2. The “Self Adjust” feature is set to on. The switch will continually adjust time delay and sensitivity to ensure maximum performance. o adjustments are
necessary at installation. Coverage and sensitivity can be confirmed by watching the LED indicator on the front of the Sensor while moving around the
room. The LED lights only when the Sensor is detecting motion.
3. In preparation for the Installer Test, the time delay has been set to 15 seconds (refer to the chart
below to see Time Delay settings) and the Auto/Manual switch is in the OFF position to allow for
Auto Operation (lights will turn on automatically when the switch detects movement). Leave the
room. The lights should go out in approximately 15 seconds. Wait at least 12 seconds after the
lights go out. Walk normally back into the room and verify that the lights turn on automatically.
There is no immediate need to make further adjustments to the Time Delay. When the Time Delay
is set at the installer setting, it will reset itself to the 10-minute delay one hour after the lights are shut
off automatically or manually. A 10-minute Time Delay is ideal in most applications. To disable this
self-resetting feature, move the Self-Adjust DIP switch (6) to O .
4. People who remain very still for long periods may need a longer Time Delay than the default setting
of 10 minutes. As long as the Self-Adjust feature is enabled, the switch will respond to each pair of
false offs with no normal off in between, by alternately making slight adjustments to either time delay
or sensitivity so there should be no need for manual adjustment. If manual adjustment is desired,
refer to the chart at right and use the dip switches to increase the time delay slightly, repeating if
necessary, until an optimum interval is obtained. OTE: To reset the wall switch to the factory set-
tings for sensitivity and time delay, move the Override DIP switch (8) to the O and then the OFF
settings.
5. If the LED blinks when there is no movement in the room, it is possible that the Sensor is being acti-
vated by air flow from the HVAC system or other climate control device. If possible, relocate the
Sensor at least six feet away from any climate control device.
6. If the sensor is activated by passers-by in the hallway, decrease the sensor’s field-of-view using the
tape strips provided. There are two strips that are 0.25” long and two strips that are 0.35” long.
Each strip is 0.5” wide, allowing the strip to completely cover the sensor window from top to bottom.
Start with one of the longer tape strips. Place the strip against the outermost edge of the sensor window, so that it completely covers the window, and wrap
the tape around the sensor toward the center of the window. If this does not completely prevent activation by passers-by, layer one of the remaining strips of
tape over the piece you have already placed on the sensor window, so that you cover slightly more of the sensor’s field of view. Repeat, if necessary.
7. For maximum energy savings, Model OSW-P-0451-MV can be set to Manual On by moving the “Auto/Manual On” DIP switch (5) to the O position. In this
setting, the occupant must push the touchplate to turn on lights upon entering the room.
8- OVERRIDE
4- TIME DELAY
3 - TIME DELAY
2- TIME DELAY
1 - TIME DELAY
7- ENERGY SAVER (DUAL LEVEL ONLY)
6- SELF ADJUST DISABLE
5 - AUTO/MANUAL ON
DIP SWITCH CONTROL LEGEND:
2
0.25
SWITCH NUMBER
6
4
TIME DELAY
123
8
10
12
14
(MINUTES) 4
30
18
24
26
28
22
20
16
TIME DELAY LEGEND
=On = O
Once installation is complete, restore power to the lighting circuit. Proper operation must be verified. Each unit is shipped with all DIP switches in the
default OFF position. For most applications, this is the ideal configuration and no further adjustments will be necessary. Simply complete the installer
test described below to confirm. If adjustments are necessary, DIP switches are under the touchplate. Adjustments should be made with the HVAC
system on so that the installer will be able to detect the effect of airflow on the operation of the OSW-P-0451-MV. Use only insulated tools to make
adjustments.
BEFORE PROCEEDING WITH ANY TROUBLE HOOTING: Confirm the
Override DIP switch (8) is in the OFF or down position. If it is in the O or up
position, switch it to the OFF position and wait two minutes before proceed-
ing.
LED will not turn ON: Verify that the lighting circuit has power.
Immediately after power is applied to the lighting circuit, it takes approximate-
ly one to two minutes for the OSW-P-0451-MV to stabilize. Once the switch
has had time to stabilize, verify that OSW-P-0451-MV is properly adjusted.
Press the touchplate to manually turn on the lights. If the LED does not light,
replace the Sensor.
Lights will not turn ON: Immediately after power is applied to the lighting
circuit, it takes approximately one to two minutes for the OSW-P-0451-MV to
stabilize. Once the switch has had time to stabilize, if the lights will not turn
on automatically after someone enters the room, press the touchplate. If
lights come on, the OSW-P-0451-MV could be set to the Manual On mode.
Check under the touchplate to verify the setting. If OSW-P-0451-MV is set to
Automatic On mode, it may have been overridden by someone pressing the
touchplate; allow Sensor to time out to verify normal operation. If the lights
do not turn on after pressing the touchplate, confirm that no other switches or
equipment are interrupting or bypassing power to the Sensor or the load. If
lights still do not turn on, replace the Sensor.
Lights will not turn OFF: Immediately after power is applied to the lighting
circuit, it takes approximately one to two minutes for the OSW-P-0451-MV to
stabilize. Once the switch has had time to stabilize, if the lights will not turn
off after the selected time delay, and the LED has not lit during the time peri-
od, press the touchplate to manually turn off the lights. If lights turn off,
refer to items 5 and 6 above under “Checkout and Adjustment.” Confirm
that no other switches or equipment are interrupting or bypassing power
to the Sensor or the load. If lights still do not turn off, replace the Sensor.
WIRING DIAGRAM
This manual suits for next models
2
Table of contents
Other Cooper Controls Switch manuals
Popular Switch manuals by other brands

Versitron
Versitron S72450 installation guide

Guntermann & Drunck
Guntermann & Drunck miniMUX8 Installation and operation

NETGEAR
NETGEAR FSM7352PS - ProSafe 48 Port 10/100 L3 Managed Stackable... installation guide

IPGARD
IPGARD SDVN-8D user manual

Comtrol
Comtrol ROCKETLINX ES7110-VB Quick installation guide

TAXON TOOLS
TAXON TOOLS Scart Switch manual

Becker
Becker Centronic EasyControl EC62S operating instructions

Dunarri
Dunarri THR3-24 installation instructions

NVT Phybridge
NVT Phybridge FLEX24-10G Quick install guide

Lantronix
Lantronix SM4T4DPA install guide

schmersal
schmersal TFH 232-11UEDR operating instructions

H3C
H3C S9500 Series Operation manual