CyberPower XL Series User manual

User’s Manual
Professional Rack Mount LCD XL Series
PR3000ELCDRTXL2U
K01-0000140-02
EN

1 Copyright © 2015 CyberPower Systems, Inc.
This manual contains important instructions. Please read and follow all instructions carefully during installation
and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the
UPS.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection.
DO NOT plug the UPS into an outlet that is not grounded. If you need to power-drain this equipment, turn off
and unplug the unit.
CAUTION! The battery can power hazardous components inside the unit, even when the AC input power is
disconnected.
CAUTION! The UPS should be near the connected equipment and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor
area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity
range).
CAUTION! To reduce the risk of an electric shock, do not remove the cover, except to service the battery.
There are no user serviceable parts inside, except for the battery.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing
the battery or installing a computer component.
CAUTION! To reduce the risk of fire, connect the UPS to a circuit with 16 amperes maximum over-current
protection in accordance to CE requirement.
CAUTION! The AC outlet where the UPS is connected should be close to the unit and easily accessible.
CAUTION! Please use only VDE-tested, CE-marked mains cable, (e.g. the mains cable of your equipment),
to connect the UPS to the AC outlet.
CAUTION! Please use only VDE-tested, CE-marked power cables to connect any equipment to the UPS.
CAUTION! When installing the equipment, ensure that the sum of the leakage current of the UPS and the
connected equipment does not exceed 3.5mA.
CAUTION! This is permanently connected equipment and only qualified maintenance personnel may carry
out installations.
CAUTION! Do not unplug the unit from AC Power during operation, as this will invalidate the protective
ground insulation.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances this
unit should be used for medical applications involving life support equipment and/or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near
aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause
the machine to short out.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A
STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS OUTPUT SOCKETS.
IMPORTANT SAFETY INSTRUCTIONS

Copyright © 2015 CyberPower Systems, Inc. 2
UNPACKING
The box should contain the following:
(1) UPS unit x 1; (2) User manual x 1; (3) Phone line x 1; (4) PowerPanel
®
Business Edition software CD x 1; (5)
USB A+B type cable x 1; (6) Rack mount Brackets x 2; (7) Skids x 2; (8) Emergency Power Off Cable (gray) x 1;
(9) Serial Interface Cable (DB-9) x 2; (10) Power cord x 4
AUTOMATIC VOLTAGE REGULATOR(AVR)
The PR3000ELCDRTXL2U can stabiliz the consistent utility power. The utility
power may be damaging to important data and hardware, but Automatic Voltage
Regulation helps the computer not experience dangerous voltage levels.
Automatic Voltage Regulator automatically regulates low or high voltages to keep
equipment working at safe AC power levels (220/230/240V) without switching to
battery. Your equipment can operate normally even meet the power problems,
such as, shout brownouts and blackouts. The unit’s powerful sealed lead-acid
batteries will provide power only if the incoming voltage drops below 150V or
increases above 300V.
SYSTEM BLOCK DIAGRAM
HARDWARE INSTALLATION GUIDE
1. Battery charge loss may occur during shipping and storage. For the first time the UPS is used, it’s strongly
recommended to charge batteries for at least 12 hours is recommended to ensure that the batteries’ maximum
charge capacity. To recharge the batteries, simply make the UPS plugs into an AC outlet.
2. When you use the included software, connect either the serial or the USB cable between the computer and
the corresponding port on the UPS. Note: If the USB port is used, the serial port will be disabled. They cannot
be used simultaneously. The computer with the PowerPanel
®
Business Edition S/W connects to the USB port
or the Serial port on the UPS. It can control the operating schedule, battery test, outlet, etc. and get information
on the UPS status. However, other computers with PowerPanel
®
Business Edition S/W can only get UPS
status information via a LAN connection.
3. With the UPS off and unplugged, connect your computer, monitor, and any externally powered data storage
device (Hard drive, Tape drive, etc.) into the outlets. DO NOT plug a laser printer, copier, space heater,
vacuum, paper shredder or other large electrical device into the UPS. The power demands of these devices will
overload and possibly damage the unit.
4. To protect a fax, telephone, modem line or network cable, connect the telephone or network cable from the
wall jack outlet to the jack marked “IN” of the UPS. Then, connect a telephone cable or network cable from the
jack marked “OUT” on the UPS to the modem, computer, telephone, fax machine, or network device.
INSTALLING YOUR UPS SYSTEM
(continued)
INSTALLING YOUR UPS SYSTEM

3 Copyright © 2015 CyberPower Systems, Inc.
5. Press the power switch to turn the UPS on. The Power-On indicator light will illuminate. If an overload is
detected, an audible alarm will sound and the UPS will emit one long beep. In order to reset it, turn the unit off
and unplug some equipment from outlets. Make sure your equipment carry a load current within the unit’s safe
range, (refer to the technical specifications), and then turn the unit on.
6. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery
will be automatically charging, even when the unit is switched off!
7. To always maintain an optimal battery charge, leave the UPS plugged into an AC outlet at all times.
8. Before storing the UPS for an extended period of time, turn the unit OFF. Then cover it and store it with the
batteries fully charged. Recharge the batteries every three months or so, to ensure good battery capacity and
long battery life; further, this might also prevent damage to the unit from an unlikely battery leakage.
9. The unit provides one Primary Serial Port (I), Secondary Serial Port (II), and one USB port, (paired with the
Primary Serial Port), to allow connection and communication between the unit and any attached computers.
The Primary Serial Port (I) as well as its paired USB port allow for bi-directional communication among the UPS
and the primary connected computer running the PowerPanel
®
Business Edition S/W provided. The UPS can
control the computer’s shutdown in case of an emergency, and at the same time, the computer can monitor the
UPS and alter its various programmable parameters. On the other hand, secondary Serial Port II, only allows
the UPS to initiate the connected computer’s graceful auto-shutdown in case of an emergency.
10. EPO (Emergency Power Off) Port:
Use the provided gray cable to connect to a special EPO contact switch. Follow the appropriate circuit
diagram below to wire the cable to your EPO configuration. The EPO remote switch is a switch installed in an
outside area, connected to the unit via an ordinary RJ-11 phone line. In case of an emergency, it can be used to
immediately cut-off power from the UPS unit.
1
2
3
43-4 JUMPER
N.C.EPO SWITCH
OPTION 2: USER SUPPLIED NORMALLY CLOSED SWITCH
RJ11
PLUG
1
2
3
4
NO CONNECTION
N.O.EPO SWITCH
OPTION 1: USER SUPPLIED NORMALLY OPEN SWITCH
(RECOMMENDED)
NO CONNECTION
INSTALLING YOUR UPS SYSTEM
(continued)

Copyright © 2015 CyberPower Systems, Inc. 4
1
2
43
FRONT / REAR PANEL DESCRIPTION
1.Power Switch
Master on/off switch for equipment connected to the UPS.
2. Power On Indicator
Indicate that the AC utility input power’s condition is normal and that the UPS outlets are providing power, free
of surges and spikes.
3. Multifunction LCD Readout
An LCD that shows various UPS information using icons and messages.
4.LCD Readout Toggle Button
Used to select among a variety of information the LCD can display.
BASIC OPERATIO
N

5 Copyright © 2015 CyberPower Systems, Inc.
Provides SNMP Card Communication
Expansion Port
6
14
897
13
1012111615
5
OUT
AC INPUT
EPO
Serial Port II
(PRIMARY)
Serial Port I IN
PR3000ELCDRTXL2U
5. Battery Backup, Surge Protected and AVR protected Outlets
This unit provides a total of nine outlets with battery backup and surge protection. They ensure that connected
equipment will keep an uninterrupted operation over a period of time, during a power failure.
Critical /Non-critical
It is possible to program the unit in a way so that the outle block marked as “non-Critical”, (6 ports), will stop the
provision of power to connected equipment after a certain period of time, thus making more runtime available
for the equipment connected on the outlets marked as “Critical”, (3 ports). In other words, the user can
establish runtime priority for certain connected equipment, maximizing its “availability” during a prolonged
power outage. This type of control takes place with the use of the provided PowerPanel
®
Business Edition S/W.
6.AC Inlet
Connect the AC Power cord to a properly wired and grounded outlet.
7. Output Circuit Breaker
The circuit breaker serves to provide output overload and fault protection.
8.Input Circuit Breaker
The circuit breaker serves to provide input overload and fault protection.
9. USB port to PC
This is a connectivity port allowing communication and control among the UPS and the connected computer.
You should install on your computer the PowerPanel
®
Business Edition software appropriate to the operating
system you are using.
10. Surge Protected Communication Ports - RJ11/RJ45
These ports are being used to protect from various surge-conditions the standard RJ-45/RJ-11 based, (ADSL,
LAN, Phone/Modem-Lines), cabling systems.
11. Serial Port I (Primary)
Serial port I allow for bi-directional communication among the UPS and the computer. The UPS can control the
computer’s shutdown in case of an emergency, and at the same time, the computer can monitor the UPS and
alter its various programmable parameters.
12. Serial Port II (Secondary)
Serial Port II allows the UPS to initiate the connected computer’s graceful auto-shutdown in case of an
emergency.
13. SNMP/HTTP Network slot
Remove the cover panel to install optional SNMP, allowing your UPS be controlled and monitored via a network
connection.
14. EPO (Emergency Power Off) Port
Allow for an emergency UPS Power-Off from a remote location.
15. External Battery Pack Connector
Provides a connection for additional CyberPower external battery packs for extended runtime.
16. Ground Stud
Use the Ground Stud to ground the UPS.
BASIC OPERATIO
N (continued)

Copyright © 2015 CyberPower Systems, Inc. 6
Rackmount Installation
Step 1: Rackmount ear and handle installation
Step 2: Rackmount Rail Installation
Each Rackmount Rail (Left and Right) consists of two (2) pieces that must be assembled together before
installing into the rack.
Step 3: Adjust rack mount rails to fit your rack
Take the Rackmount Rail inscribed with an “L” (Left) and attach it to the rear bracket of the Rackmount Rail
using three (3) of the six (6) Rackmount Rail Screws. Do not fully tighten the Rackmount Rail screws, as the
Rackmount Rails will need to be adjusted to fit your rack. Once complete, perform the same steps for
assembling the Rackmount Rail inscribed with an “R” (Right).
Step 4: Adjust rack mount rails to fit your rack
Slide the UPS on top of the newly installed Rackmount Rails, and secure the UPS to your existing rack system
[via the Rackmount Ears] using fasteners that are designed for your rack system.
HARDWARE INSTALLATION
Attach the two Rackmount Ears to
the UPS using the provided screws.
Attach the Rackmount Rails to your
rack using fasteners that are
designed for your rack system.
Attach the Rackmount Handles to the
Rackmount Ears using the provided
screws.

7 Copyright © 2015 CyberPower Systems, Inc.
VERTICAZL/TOWER INSTALLATION
Step 1: Attach Dust Covers
Insert Dust Covers into the Rackmount Ear screw holes that are not being used.
Step 2: Attach the base stands
Simply slide the base stands onto the bottom of the UPS, roughly 8-10” apart.
Step 3: Rotate the Multifunction LCD Readout
HARDWARE INSTALLATION
Insert a small straight-slot screwdriver into
the notch and gently lift the LCD out.
Switch back and forth lifting one side then
the other to gently work it out far enough
that you can grasp it with your fingers and
pull it out.
The LCD is out.
Push it back in with
your fingers.
Rotate it to the
preferred orientation.

Copyright © 2015 CyberPower Systems, Inc. 8
Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the batteries:
Servicing the batteries should only be performed by professionals. Please Contact your dealer. Make a note for
the replacement battery pack number, (RBP0040), regarding PR3000ELCDRTXL2U.
CAUTION! Use only the specified type of battery: HR9-12FR(BB) for PR3000ELCDRTXL2U. Contact your
dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries on fire, since they
may explode. Follow all local ordinances regarding the proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and
may be toxic.
CAUTION! A battery can present a high risk of short-circuits and electrical shocks.
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects from your hands.
2. Only use tools with insulated handles.
3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4. Wear rubber gloves and shoes.
5. Determine if the battery is grounded. If so, remove source of ground. CAUTION: CONTACT WITH A
GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such a shock will be
greatly reduced if such grounding is removed during installation and maintenance.
BATTERY REPLACEMENT

9 Copyright © 2015 CyberPower Systems, Inc.
BATTERY REPLACMENT PROCEDURE:
REMINDER! The used batteries are hazardous wastes and must be disposed through recycling. Most retailers
that sell lead-acid batteries collect used batteries for recycling, as required by the local regulations.
BATTERY REPLACEMEN
(continued)
6. Put the new battery packs back into the
compartment. Tighten up the screws and
replace the cable protection cover and th
e
front panel. Recharge the unit for 12
hours to ensure the UPS performs
expected runtime.
1. Remove the front panel on the
right side.
2. Remove the one
retaining screw of
the cable protection cover.
3. Remove the cable
protection
cover.
5. Remove t
he three retaining
screws.
4. Disconnect the black wire and red
wire from the battery.

Copyright © 2015 CyberPower Systems, Inc. 10
The LCD displays detailed information on
the UPS status and current power
conditions to alert you to potential power
problems before the affect your
equipment. Note! All related UPS
information is based on that you should
turn on the UPS.
1. Input voltage meter: This meter measures the AC voltage from
the wall outlet. The INPUT voltage readout is used to identify the
input voltage information. This can be used as a diagnostic tool to
identify poor-quality input power. Units are listed in V (Volts).
When the UPS connect to any equipment, the AVR can provide a
stable 220/230/240V power output. In the event of a complete
loss of power, severe brownout, or over voltage, the UPS relies on
its internal battery to back up to supply a consistent 220/230/240V
output.
2. Output voltage meter: The Output Voltage screen measures, in
real time, the AC voltage that the UPS is providing to your
connected equipment via the UPS outlets. Units are listed in V
(Volts).
3. Estimate run time: The Estimated Runtime Screen displays how
many minutes of runtime can be expected of the UPS if it were to
experience a power outage. When runtime becomes shorted, the
battery capacity will decrease; (battery capacity bar indicator will
be falling.) Note: The number displayed may be less than actual
runtimes for low loads.
4. Normal icon: This icon illuminates when the UPS is working under normal conditions.
5. Battery icon: When there is a severe brownout or blackout, this icon will appear followed by an alarm,
(two short beeps), indicating that the UPS is now working using its internal batteries. Once the batteries
are run out of power, (over a period of time), a constant alarm will sound. If this happens and main power
has not been restored, it is recommended that you save your files and turn off your equipment manually
as soon as possible.
6. Automatic Voltage Regulation (AVR) icon: This icon will appear when the unit is automatically
regulating low or high AC input line voltage conditions, without resulting to the use of battery power.
7. Silent mode icon: This icon appearing indicates that the buzzer will not be beeping while in battery
operating mode. During Silent mode, the unit’s alarm does not sound until the Battery Capacity falls to <
20%.
8. Over load icon: This icon will appear followed by an alarm, indicating that an overload condition has
been reached. To recover from the overload condition, start unplugging your equipment from the UPS
outlets until the icon disappears and the alarm stops.
9. Fault icon: When activated indicates a system fault error. Please refer to the troubleshooting table for
possible causes and solutions.
10. BATT. CAPACITY: BATT. CAPACITY is shown as a bar chart; each segment indicates approximately a
20% of battery capacity.
11. LOAD CAPACITY: Load CAPACITY is shown as a bar chart; each segment indicates approximately a
20% of load capacity.
□
11
□
1
□
2
□
3
□
4
□
5
□
6
□
7
□
8
□
9
□
10
DEFINITION
FOR ILLUMINATED
LCD
INDICATORS

11 Copyright © 2015 CyberPower Systems, Inc.
1. General Mode:
a. Press the “Display-Toggle” button to check the status of the UPS status:
b. Press and hold the “Display-Toggle” button for 4 seconds,
If the machine is in the Battery Mode with active alarm, it will become silent.
If the machine is in the Line Mode, a self- diagnostic test will take place.
c. If the “Display-Toggle” button remains untouched for over 30 seconds, the LCD backlight will turn off
automatically.
2. Set-up Mode
Step 1: Hold the “Display-Toggle” button for 10 seconds to enter the UPS Set-Up Mode.
Step 2: By pressing the Display toggle, users can switch between setup functions. Some User Configurable
functions are as follows:
a. Delay Time: The time delay between switching from Battery Mode to Line Mode. There are 9 different
settings. The default setting is 0 minutes.
b. Battery Pack Numbers: This function provides the estimated UPS runtime using various numbers of
battery packs. The default setting is 0.
c. Static Frequency Tolerance: There are 4 settings (1, 2, 4, 6 %), and the default setting is +/-6%.
Functional description: The setting may be adjusted to the quality of the electricity in use.
d. Slew rate: Also known as Dynamic Frequency Tolerance. There are 5 different settings (0.25, 0.5, 1, 2, 4
Hz/Sec). The fault value is 4Hz/sec. Functional Description: “Slew Rate” indicates the tolerance of a
device in accepting frequency variance. Lower “Slew Rate” results in less tolerance but better protection
for the connected load and vice versa.
e. Low Battery Shutdown Voltage: This function will adjust the UPS shutdown point according to the
battery’s remaining capacity.
These programmable items are sorted by unit as in the following table
:
Item Unit
1 Input Voltage V
2 Output Voltage V
3 Output Frequency Hz
4 Load Kw
5 Estimate Run Time Min
6 Load Capacity %
7 Battery Capacity %
8 Centigrade °C
9 Fahrenheit °F
Items Unit
Delay Time Min
Battery Pack Numbers A
Voltage Mode (220/230/240) V
Static Frequency Tolerance %
Slew Rate Hz
Low Battery Shutdown Voltage V
Firmware Version None
LCD SETUP FUCTIONS

Copyright © 2015 CyberPower Systems, Inc. 12
Step 3: Press and hold the display-toggle for 4 seconds. When the icons blink, the value of each item is
changed by slightly pressing the toggle.
Step 4: To save the value and return to general mode, press and hold the toggle for 4 seconds.
Note! If the UPS is left idle for over 30 seconds during setup, it will turn off the backlight and return to
general mode automatically.
Note! If the user does not want to save the new settings and return to the general mode, there are two
methods:
(1) Wait for the backlight to turn off, or,
(2) By pressing and holding the “Display-toggle” key for 10 second.
GreenPower UPS™
CyberPower's GreenPower UPS™ Circuit Design is a solution to this problem "Power Loss."
When the Utility Power is operating normally, Green Power UPS™ works in Bypass Mode.
Our GreenPower UPS™ design conducts power only through the Relay and still provides
normal output voltage. Bypassing the transformer reduces power consumption thereby
conserving energy and saving money. When the utility power is abnormal the UPS will
operate under Battery or AVR Mode. Under this condition Green Power UPS™ and a
traditional UPS would operate about the same.
On average utility power operates 88% of the time and the CyberPower GreenPower Technology will work in its
money/ energy saving Bypass Mode.
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
LCD SETUP FUCTIONS

13 Copyright © 2015 CyberPower Systems, Inc.
Model PR3000ELCDRTXL2U
Capacity (VA) 3000
Capacity (Watts) 2400
Input
Input connections IEC 320 C20
Nominal Input Voltage 230Vac
Input Voltage Range 150Vac – 300Vac
Input Frequency Range
50/60Hz +/- 3Hz (Auto Sensing)
Output
On Battery Output
Voltage 220 / 230 / 240 Vac +/-5%
On Battery Output
Frequency 50/60Hz +/- 0.1Hz
Transfer Time (Typical)
4ms
Overload Protection On Utility: Circuit Breaker, On Battery: Internal Current Limiting
Surge Protection and Filtering
Lightning / Surge
Protection Yes
Internet Ready (DSL /
Phone / FAX / Modem
Protection) RJ11/RJ45 ( One In/ One Out )
Physical
Output Receptacles (8) IEC C13, (1) IEC C19
Dimensions(cm) 2U Rack, 43.3 x 8.8 x 60
Weight (kg) 41.8
Battery
Sealed Maintenance
Free Lead Acid Battery
12V / 9.0AH x4
Hot Swappable
External Battery Yes
Warning Diagnostics
Indicators Power On, LCD Display (Using Battery, AVR, Load Level, Battery Level)
Audible Alarms On Battery, Low Battery, Overload
Environmental
Operating Temperature
32°F to 104°F ( 0°C to 40°C)
Operating Relative
Humidity 0 to 95% Non-Condensing
Communication
PowerPanel
®
Business
Edition Software Windows 10 / 8 / 7 / Vista / XP / 2000 / 2003 / Server 2008 / Server 2003
Management
Self -Test Manual Self-Test
Auto-Charger
/Auto-Restart Yes
COM Interface True RS232 x 1+ Contact Closure x 1
Built- in USB interface Yes
SNMP/HTTP
Networking Optional
TEC
HNICAL SPECIFICATIONS

Copyright © 2015 CyberPower Systems, Inc. 14
For more information, contact us at:
CyberPower Systems, Inc
Website: www.cyberpower.com
Entire contents copyright ©2015 CyberPower Systems, Inc. All rights reserved. Reproduction in whole or in
part without permission is prohibited. PowerPanel
®
and PowerPanel
®
Plus are trademarks of CyberPower
Systems (USA) Inc.
Problem Possible Cause Solution
Outlet does not
provide power to
equipment
Circuit breaker has tripped
due to an overload.
Turn the UPS off and unplug at least one piece of
equipment. Wait 10 seconds, reset the circuit breaker
and then turn the UPS on.
Batteries are discharged. Recharge the unit for at least 4 hours
Unit has been damaged by
a surge or spike. Contact CyberPower Systems about replacement
batteries at www.cyberpower.com
Uncritical outlets have
turned off automatically due
to an overload.
Push the toggle button to make the uncritical outlets
turn on.
The UPS does not
perform expected
runtime.
Batteries are not fully
charged. Recharge the batteries by leaving the UPS plugged in.
Batteries are degraded Contact CyberPower Systems about replacement
batteries at www.cyberpower.com
The UPS will not
turn on.
The on/off switch is
designed to prevent
damage by rapidly turning it
off and on.
Turn the UPS off. Wait 10 seconds and then turn the
UPS on.
The unit is not connected to
an AC outlet. The unit must be connected to a 220/230/240v outlet.
The batteries have
degraded.
Contact CyberPower Systems about replacement
batteries at www.cyberpower.com
Mechanical problem. Contact CyberPower Systems at
www.cyberpower.com
PowerPanel
®
Business
Edition is inactive.
The serial cable or USB
cable is not connected.
Connect the cable to the UPS unit. You must use the
cable that came with the unit.
The cable is connected to
the wrong port. Try another port of your computer.
The unit is not providing
power of batteries.
Shutdown your computer and turn the UPS off. Wait
10 seconds and turn the UPS back on. This should
reset the unit.
The serial cable is not the
cable that was provided
with the unit.
You must use the cable included with the unit for the
software.
TROUBLE SHOOTING

Manual de usuario
Professional Rack Mount LCD Series
PR3000ELCDRTXL2U
ES

Copyright © 2015 CyberPower Systems, Inc. 16
Este manual contiene instrucciones importantes que deben respetarse durante la instalación y el
mantenimiento del SAI y las baterías. Por favor, lea y respete las instrucciones siguientes durante la
instalación y el uso de la unidad. Lea completamente este manual antes de intentar desembalar, instalar o
utilizar el equipo.
¡PRECAUCIÓN! El SAI debe conectarse a una toma de suministro eléctrico AC conectada a masa protegida
por un fusible o interruptor de circuito. NO enchufe el SAI a una toma que no se encuentre conectada a masa.
Si necesita desactivar por completo el sistema SAI, apáguelo y desenchúfelo de la toma de suministro
eléctrico.
¡PRECAUCIÓN! ¡NO UTILICE EL SAI CON IMPRESORAS LÁSER! Los requisitos de alimentación de las
impresoras láser son demasiado altos para un SAI.
¡PRECAUCIÓN! La batería podría mantener activos determinados componentes en el interior de la unidad,
incluso aunque se haya desconectado la alimentación AC.
¡PRECAUCIÓN! Para evitar el riesgo de incendio o descarga eléctrica, instale el equipo en una zona interior
con niveles controlados de humedad y temperatura, y libre de contaminantes conductores. (Consulte las
especificaciones para conocer los límites admisibles de temperatura y humedad).
¡PRECAUCIÓN! Con el fin de reducir el riesgo de descarga eléctrica, no retire la cubierta, excepto para
realizar operaciones de mantenimiento sobre la batería. El equipo no contiene componentes que el usuario
pueda reparar.
¡
¡¡
¡
PRECAUCIÓN! Para evitar descargas eléctricas, apague la unidad y desenchúfela de la fuente de
alimentación AC antes de realizar operaciones de mantenimiento sobre la batería o instalar un componente
informático.
¡
¡¡
¡
PRECAUCIÓN! Para reducir el riesgo de incendio, conecte el sistema SAI a un circuito con protección contra
sobrecarga de corriente con un límite máximo de 16 amperios, de acuerdo con los requisitos de la CE.
¡
¡¡
¡
PRECAUCIÓN! La toma de suministro eléctrico AC a la que se encuentra conectado el sistema SAI deberá
encontrarse cerca de la unidad y ser fácilmente accesible.
¡
¡¡
¡
PRECAUCIÓN! Utilice únicamente cables de alimentación eléctrica con homologación VDE y que ostenten la
marca CE (por ejemplo, el cable de alimentación de su equipo) para conectar el sistema SAI a la toma de
suministro eléctrico AC.
¡
¡¡
¡
PRECAUCIÓN! Utilice únicamente cables de alimentación con homologación VDE y que ostenten la marca
CE para conectar cualquier equipo al sistema SAI.
¡
¡¡
¡
PRECAUCIÓN! Durante la instalación del equipo, asegúrese de que la suma de las corrientes de fuga del
sistema SAI y los equipos conectados no supere los 3,5 mA.
¡
¡¡
¡
PRECAUCIÓN! Este es un equipo de conexión permanente y únicamente se permite su instalación a
personal de mantenimiento cualificado.
¡
¡¡
¡
PRECAUCIÓN! No desenchufe la unidad de la toma de suministro eléctrico AC durante su funcionamiento.
Dicha acción invalidará el aislamiento de masa protectora.
¡
¡¡
¡
PRECAUCIÓN! ¡NO UTILIZAR CON DISPOSITIVOS MÉDICOS O DE SUPERVIVENCIA! NO utilice el
equipo en circunstancias en las que pudiera resultar afectado el funcionamiento de un equipo de seguridad o
supervivencia, ni tampoco conectado a aplicaciones médicas o de asistencia a pacientes.
¡
¡¡
¡
PRECAUCIÓN! ¡NO ENCHUFE ACUARIOS A LA UNIDAD NI LA UTILICE CERCA DE ELLOS! Con el fin de
reducir el riesgo de incendio, no enchufe acuarios a la unidad ni la utilice cerca de ellos. La condensación del
acuario podría entrar en contacto con los contactos eléctricos metálicos del SAI y provocar un cortocircuito en
la máquina.
INSTRUCCIONES IMPORTANTES DE SEGURIDAD

17 Copyright © 2015 CyberPower Systems, Inc.
¡
¡¡
¡
NO INSTALE EL SISTEMA SAI EN LUGARES EN LOS QUE PUDIERA QUEDAR EXPUESTO A LA LUZ
SOLAR DIRECTA O CERCA DE UNA FUENTE DE CALOR INTENSO!
¡
¡¡
¡
NO BLOQUEE LOS ORIFICIOS DE VENTILACIÓN SITUADOS ALREDEDOR DE LA CARCASA!
NO CONECTE APARATOS DOMÉSTICOS, COMO SECADORES DE PELO, A LAS TOMAS DE SALIDA
DEL SISTEMA SAI.
DESEMBALAJE
La caja debe contener los siguientes artículos:
(1) Unidad de sistema SAI x 1; (2) Manual de usuario x 1; (3) Línea telefónica x 1; (4) CD con la aplicación
PowerPanel
®
Business Edition x 1; (5) Cable de tipo USB A+B x 1; (6) Abrazaderas de montaje en bastidor x 2;
(7) Raíles x 2; (8) Cable de apagado de emergencia (gris) x 1; (9) Cable de interfaz serie (DB-9) x 2; (10) Cable
de alimentación x 4
REGULADOR AUTOMÁTICO DE VOLTAJE (AVR)
El equipo PR3000ELCDRTXL2U puede estabilizar el nivel de voltaje de la red
eléctrica. El voltaje de la red eléctrica podría resultar perjudicial para los datos y
el hardware de carácter crítico. Sin embargo, el regulador automático de voltaje
evita que lleguen al equipo los niveles peligrosos de voltaje. El regulador
automático de voltaje nivela automáticamente los niveles altos o bajos de voltaje
para mantener el equipo en funcionamiento a un nivel de alimentación AC seguro
(220 / 230 / 240 V), sin necesidad de conmutar a la alimentación de la batería. Su
equipo continuará funcionando normalmente incluso si se enfrenta a problemas
con el suministro eléctrico, como caídas de tensión o apagones. Las potentes
baterías selladas de plomo y ácido con las que cuenta la unidad actuarán
únicamente si el voltaje de entrada cae por debajo de 150 V o aumenta por encima de 300 V.
1. Podría producirse una pérdida de carga de la batería durante el transporte y el almacenamiento de la
unidad. Si es la primera vez que utiliza el sistema SAI, se recomienda encarecidamente cargar las baterías
durante al menos 12 horas para garantizar que disfruten de su máxima capacidad de carga. Para recargar las
baterías, tan sólo necesitará conectar el enchufe del sistema SAI a la toma de suministro eléctrico AC.
2. Durante el uso de la aplicación suministrada, conecte el cable serie o USB entre el equipo y el puerto
correspondiente del sistema SAI. Nota: Si se utiliza el puerto USB, el puerto serie se deshabilitará. Su uso
simultáneo no es posible. El equipo en el que se encuentra instalada la aplicación PowerPanel
®
Business
Edition debe conectarse al puerto serie o USB del sistema SAI. Ello le permitirá controlar el programa de
funcionamiento, las pruebas de la batería, las tomas de salida, etc. y obtener información acerca del estado
del sistema SAI. Sin embargo, si existen otros equipos con la aplicación PowerPanel
®
Business Edition
instalada, únicamente podrán obtener información acerca del estado del sistema SAI a través de una conexión
de red LAN.
3. Con el equipo SAI apagado y desenchufado, conecte su equipo, monitor y cualquier dispositivo de
almacenamiento de datos que requiera alimentación externa (disco duro, unidad de cinta, etc.) a las tomas de
alimentación a batería. NO enchufe una impresora láser, copiadora, calefactor, aspirador, trituradora de papel
u otro dispositivo eléctrico de gran tamaño al SAI. Los requisitos de alimentación de este tipo de dispositivos
podrían sobrecargar y dañar el equipo.
INSTALAR SU SISTEMA SAI
GUÍA DE INSTALACIÓN DEL HARDWARE
INSTRUCCIONES IMPORTANTES DE SEGURIDAD

Copyright © 2015 CyberPower Systems, Inc. 18
4. Para proteger un fax, un teléfono, una línea de módem o un cable de red, conecte un cable telefónico o de
red entre la toma de pared y el conector IN del SAI. Conecte entonces un cable telefónico o de red entre el
conector OUT del SAI y el módem, PC, teléfono, fax o dispositivo de red.
5. Pulse el interruptor de encendido para encender el sistema SAI. Se iluminará entonces el indicador
luminoso de Encendido. Si se detecta una sobrecarga, sonará una alarma y el sistema SAI emitirá un sonido
largo. Para restaurarlo, apague la unidad y desenchufe algunos equipos de las tomas. Asegúrese de que su
equipo transporta una corriente de carga que se encuentre dentro del rango seguro de la unidad (consulte las
especificaciones técnicas) y vuelva a encenderla.
6. Su SAI se encuentra equipado con una función de carga automática. Si se enchufa el SAI a una toma AC, la
batería se recargará automáticamente.
7. Para conservar el nivel de carga óptimo en la batería, mantenga el SAI enchufado a una toma AC en todo
momento.
8. Antes de almacenar el sistema SAI durante un periodo prolongado de tiempo, APÁGUELO. A continuación,
cúbralo y almacénelo con las baterías completamente cargadas. Recargue las baterías aproximadamente
cada tres meses con el fin de garantizar su óptima capacidad y prolongar su vida útil; ello, además, le permitirá
evitar posibles daños en la unidad en el caso improbable de una fuga de batería.
9. La unidad contiene un Puerto serie principal (I), un Puerto serie secundario (II) y un Puerto USB (asociado al
Puerto serie principal) que permiten la conexión y comunicación entre la unidad y los equipos conectados. El
Puerto serie principal (I), al igual que su Puerto USB asociado, permiten la comunicación bidireccional entre el
sistema SAI y el equipo principal conectado en el que se encuentra instalada la aplicación PowerPanel
®
Business Edition. El sistema SAI puede controlar el apagado del equipo en caso de emergencia y, al mismo
tiempo, el equipo puede controlar el sistema SAI para modificar la configuración de sus distintos parámetros
programables. Por otra parte, el Puerto serie secundario (II) únicamente permite al sistema SAI iniciar el
apagado correcto del equipo en caso de emergencia.
10. Puerto EPO (apagado de emergencia):
Utilice el cable gris suministrado para conectar la unidad a un interruptor de contacto especial de tipo EPO.
Consulte a continuación el diagrama de circuito correspondiente para conectar el cable a su configuración
EPO. El interruptor remoto EPO es un interruptor que se instala en un área exterior y se conecta a la unidad
por medio de una línea telefónica RJ-11 común. En caso de emergencia, se puede utilizar para desactivar
inmediatamente la alimentación de la unidad de sistema SAI.
1
2
3
43-4 JUMPER
N.C.EPO SWITCH
OPTION 2: USER SUPPLIED NORMALLY CLOSED SWITCH
RJ11
PLUG
1
2
3
4
NO CONNECTION
N.O.EPO SWITCH
OPTION 1: USER SUPPLIED NORMALLY OPEN SWITCH
(RECOMMENDED)
NO CONNECTION
GUÍA DE INSTALACIÓN DEL HARDWARE

19 Copyright © 2015 CyberPower Systems, Inc.
1
2
43
DESCRIPTION
1. nterruptor de encendido
Se utiliza como interruptor de encendido / apagado principal del equipamiento conectado a las tomas de
alimentación a batería.
2. Indicador de encendido
Este indicador confirma que el estado del suministro eléctrico AC de entrada es normal y que las tomas del
SAI están suministrando energía, libres de sobrecargas o picos de tensión.
3. Pantalla LCD multifunction
La pantalla LCD inteligente de alta resolución muestra toda la información del SAI por medio de iconos y
mensajes. Si desea obtener más información, consulte la sección “Definición de los indicadores LCD
luminosos”.
4. Botón de conmutación de la pantalla LCD
Utilice este botón para seleccionar la información que desee que muestre la pantalla LCD.
FUNCIONAMIENTO BÁSICO
This manual suits for next models
1
Table of contents
Languages:
Other CyberPower Rack & Stand manuals