DAAB OUTPUT CARD DB410 INSTRUCTION MANUAL
4
Functions using add-in card DB410
With DB410 installed there is access to six programmable relay outputs. ese outputs are grouped into three groups with
two common positions. Note that the positions located closest to the printed circuit board on each terminal are the common
positions. ese positions are marked i1, i2 and i3. e outputs are the upper terminal positions. Display of the o-channels in
EP105 is determined by the setting in channels C707 and C710.
Functions of programmable outputs 1 - 6
e instructions are identical for all six programmable outputs, apart from the channel number – output 1 has
channel number o1nn, output 2 has channel number o2nn, etc.
e settings below are for output 1.
Activate programmable output 1 by setting o100 to the desired function. A value of 0 means that the output is
disabled (open) regardless of the settings of other channels.
If you set the value to 1, the output can be used as a trac light signal based on the position indication. Movement
and warning time signals are also available with this setting. e value 2 is for presence detection in the vehicle loop,
the value 3 is for motor locks, and the value four turns the output into an alarm output.
Channel o110 Open position
Set to 1 for a constant signal in the open position.
Channel o111 Mid position
Set 1 to obtain constant signal in mid position.
Channel o112 Closed position
Set 1 to obtain constant signal in closed position.
Example for a green light: o110 = 1, o111 = 0, o112 = 0.
Example for a red light: o110 = 0, o111 = 1, o112 = 1.
Channel o113 Movement
Use this channel to specify function during movement. e function will be active as soon as the door starts moving.
See the channel reference for the available options. Only output 4 is able to send a ashing signal.
Channel o114 Delayed switch-o
Indicated time delays disabling of the output. Can be used to let lighting be on for a certain time aer the door has le
the open position. Let o110 turn on the lighting when the door has reached the open position. When the door closes
and leaves the open position, the lighting will remain on during the time in o114.
Channel o120 Warning time before start.
Settable time 0.0 – 600.0 seconds, 0.0 means closed. Which function is to be warned is selected in o121.
Channel o121 Warning function in combination with channel o120
Set value 1 to obtain constant signal before automatic close, 2 to obtain constant signal before park and automatic
close, 3 to obtain constant signal before close signal, park and automatic close, 4 for signal before all control signals.
Channel o122 Function during warning
Select 1 if the output signal is to be disabled during storing in any output.
Select 2 if the output is to continue to indicate position or movement regardless of warning.
Channel o130 Delay for alarms specied in o131 and o132. e alarm is delayed by the set time of 0.0 – 600.0 seconds.
e factory setting is 0.0. When errors according to o131 - o142 cases, the output signal, the alarm, also ceases. ere
is no alarm acknowledgement.
Channel o131-o142 Alarm in dierent conditions
If it is set to 1, the output gives a signal when the condition, according to the channel specication, has been fullled
for longer than the time set in o130.
Select the output to be normally open or normally closed by setting channel o183 to:
e value 1 is for normally open (NO) and the value 2 is for normally closed (NC).
Channel o191 Function when LOOP1, LOOP2 or PHOTO are activated:
Used to set the presence detection required from the vehicle loop. See the channel reference for the available options.
Function of programmable output 4
ere is an alternative in channel o410-o413 for ashing function for this output, but together with this card, DB410,
these alternatives may not be programmed, as the relay is not designed for ashing function. If this alternative is
nevertheless selected, the card will suer permanent damage! DB407 must be selected for ashing function.