
207.10.15 en / 477
Setting of the Module
The module is assigned to the start inputs and the safety outputs via the
DIP switches.
The combinations of individual functions are set via the rotary switches.
To prevent accidently adjustments, these elements are covered by a front
plate and are redundant.
M8941_b
02
3
4
7
8
9
012
5
6
79
1
2
3
4
5
6
7
8
output
Mod3
Mod2
Mod1
Base
Mod3
Mod2
Mod1
Base
S1 S2
1
2
3
4
5
6
7
8
start
T1
T2
T3
T4
T1
T2
T3
T4
green LED "en 1"
green LED "en 2"
white LED
"run 1"
white LED
"run 2"
off on
• Settings to the unit must be performed by skilled personnel while
the unit is disconnected.
• Before the front cover is removed, antistatic precautions must be
observed.
Note:
Setting of the Modules
Sw. Function at Terminals Start behavior of the LC
/ E-Stop
S12-S14 S22-S24 S32-S34 S22-S24
0 Gate Gate E-Stop LC Autostart
1 Gate Gate E-Stop LC Manual Start
2 E-Stop E-Stop E-Stop E-Stop Autostart Enabling
only
when
all other
modules
permit
enabling
3 E-Stop E-Stop E-Stop E-Stop Manual Start
4 E-Stop E-Stop E-Stop E-Stop Autostart
5 E-Stop E-Stop E-Stop E-Stop Manual Start
6 E-Stop E-stop Two-hand IIIC Autostart
7 E-Stop E-stop Two-hand IIIC Manual Start
8 Gate Gate Two-hand IIIC Autostart
9 Gate LC Two-hand IIIC Autostart
Function of the Two-Hand Control
Each function activates an enabling signal in the module software. The
control unit is permitted to enable the assigned safety outputs only after
all 3 (for two-hands control) or 4 enablings have been given.
With the exception of two-hand control, each function works indepen-
dently. The assigned safety outputs are enabled if the precondition for
enabling has been met for all functions.
Functional Principle of Combined Inputs
This function will only work when the other two functions have already per-
mitted enabling. To provide for enabling, the two buttons must be pressed
within 0.5 s. As soon as one of the other function reacts, the two buttons
must turn inactive before the others can be enabled again. Only after that,
the buttons can be activated once more from an inactivated state.
The unit must be connected as specified in the application examples.When
the operating contacts are connected in parallel or in series, safe functioning
of the unit is cancelled.
The two-hand buttons must be designed and arranged in such a way as to
ensure that they cannot be disabled with easily, or pressed unintentionally.
The safety distance between the push buttons and the place of danger must
be large enough to make sure that after releasing a button, the place of
danger can only be reached after the dangerous movement has stopped.
The safety distance “S” is calculated according to the following formula:
S = V x T + C, where
a) gripping velocity V = 1 600 mm/s
b) overtravel time T (s)
c) and safety factor C = 250 mm.
When any access into the danger area, with operating keys pressed, is
safely prevented, e.g. by a protective cover for the keys, the safety factor
C may be set to the value 0. Generally, the minimum safety distance must
be 100 mm. In this respect, also see DIN/EN 574.
The two-hand control must be released when another function module
which affects the same outputs does not permit enabling.
The system may comprise only one function module with two-hand control.
Safety Gate Function
The safety gate function always permits enabling if both contacts change
from inactive to active state within 3 seconds. If the second contact reacts
later, both changeover contacts must turn inactive before they can be
enabled again.
When activating the system, press the start button to simulate the compul-
sory opening and re-closing of safety gates which have been kept closed
since the system has started.
This simulation is possible only before enabling has been permitted for
the first time, and as long as both safety gate contacts remain closed as
well. As soon as a contact opens, simulation of the safety gate function is
no longer possible.