Daikin DCS002A71 User manual

Thanks for your having purchased our product, Power Proportional Distribution Card.
This operation manual contains notes for safe use of the product.
For correct use, be sure to read this manual carefully before use.
When you have read this manual, be sure to store it in a place where the operator can conve-
niently refer to at anytime.
In case of personnel change, be sure to give the manual to the new operator.
MODEL
DCS002A71
Power Proportional Distribution Software
OPERATION MANUAL
The above intelligent Touch
Controller is available separately.
00_CV_EM06A043.fm Page 1 Tuesday, September 12, 2006 1:27 PM

1English
Power Proportional Distribution Software Operation manual
CONTENTS
1. SAFETY CONSIDERATIONS ..........................................1
2. FUNCTIONS AND OUTLINE...........................................2
3. PREPARATION ................................................................3
4. SIMPLIFIED CHART........................................................3
5. INITIAL SETUP................................................................3
6. POWER PROPORTIONAL DISTRIBUTION REPORT
OUTPUT PROCEDURES ................................................5
7. HOW TO OUTPUT POWER PROPORTIONAL
DISTRIBUTION REPORT................................................6
8. TROUBLESHOOTING ...................................................10
9. AFTER-SALES SERVICE..............................................11
1. SAFETY CONSIDERATIONS
Please read these “SAFETY CONSIDERATIONS” carefully
before installing air conditioning equipment and be sure to
install it correctly.
After completing the installation, make sure that the unit oper-
ates properly during the start-up operation.
Please instruct the customer on how to operate the unit and
keep it maintained.
Also, inform customers that they should store this installation
manual along with the operation manual for future reference.
This air conditioner comes under the term “appliances not
accessible to the general public”.
Meaning of danger, warning, caution and note symbols.
DANGER .......... Indicates an imminently hazardous situa-
tion which, if not avoided, will result in
death or serious injury.
WARNING
........Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
CAUTION ........ Indicates a potentially hazardous situation
which, if not avoided, may result in minor
or moderate injury. It may also be used to
alert against unsafe practices.
NOTE ............... Indicates situation that may result in
equipment or property-damage-only acci-
dents.
Keep these warning sheets handy so that you can refer to
them if needed.
Also, if this equipment is transferred to a new user, make sure to
hand over this operation manual to the new user.
DANGER
•
Any abnormalities in the operation of the air conditioner
such as smoke or fire could result in severe injury or death.
Turn off the power and contact your dealer immediately for
instructions.
•Do not install the unit in an area where flammable mate-
rials are present due to risk of explosion resulting in
serious injury or death.
•Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden
parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that
children will not play with them. Children playing with plastic
bags face the danger of death due to suffocation.
WARNING
•Ask your dealer for installation of the air conditioner.
Incomplete installation performed by yourself may result in a
water leakage, electric shock, and fire.
•Ask your dealer for improvement, repair, and mainte-
nance.
Incomplete improvement, repair, and maintenance may
result in a water leakage, electric shock, and fire.
•Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Be sure
only to use accessories made by Daikin which are spe-
cifically designed for use with the equipment and have
them installed by a professional.
•Ask your dealer to move and reinstall the air conditioner
or the remote controller.
Incomplete installation may result in a water leakage, electric
shock, and fire.
•Never let the indoor unit or the remote controller get wet.
It may cause an electric shock or a fire.
•Never use flammable spray such as hair spray, lacquer
or paint near the unit.
It may cause a fire.
•Do not allow children to play on or around the unit as
they could be injured.
•Never replace a fuse with that of wrong ampere ratings
or other wires when a fuse blows out.
Use of wire or copper wire may cause the unit to break down
or cause a fire.
•Never inspect or service the unit by yourself.
Ask a qualified service person to perform this work.
•Cut off all electric waves before maintenance.
•Do not wash the air conditioner or the remote controller
with excessive water.
Electric shock or fire may result.
•Do not touch the switch with wet fingers.
Touching a switch with wet fingers can cause electric shock.
•Never touch the internal parts of the controller.
Do not remove the front panel because some parts inside are
dengerous to touch. In addition, some parts may be dam-
aged by touching. For checking and adjusting internal parts,
contact your dealer.
•Check the unit stand for damage on a continuous basis,
especially if it had been in use for a long time.
If left in a damaged condition the unit may fall and cause
injury.
•Placing a flower vase or other containers with water or
other liquids on the unit could result in a shock hazard or
fire if a spill occurs.
CAUTION
•Avoid placing the controller in a spot splashed with
water.
Water coming inside the machine may cause an electric leak
or may damage the internal electronic parts.
•Do not operate the air conditioner when using a room
fumigation - type insecticide.
Failure to observe could cause the chemicals to become
deposited in the unit, which could endanger the health of
those who are hypersensitive to chemicals.
01_EM06A043_EN.fm Page 1 Monday, October 16, 2006 11:25 AM

English 2
•Do not turn off the power immediately after stopping
operation.
Always wait at least five minutes before turning off the power.
Otherwise, water leakage and trouble may occur.
•The appliance is not intended for use by young children
or infirm persons without supervision.
•The remote controller should be installed in such a way
that children cannot play with it.
NOTE
•Never press the button of the remote controller with a
hard, pointed object.
The remote controller may be damaged.
•Never pull or twist the electric wire of the remote control-
ler.
It may cause the unit to malfunction.
•Do not place the controller exposed to direct sunlight.
The LCD display may get discolored, failing to display the
data.
•Do not wipe the controller operation panel with benzine,
thinner, chemical dustcloth, etc.
The panel may get discolored or the coating peeled off. If it is
heavily dirty, soak a cloth in water-diluted neutral detergent,
squeeze it well and wipe the panel clean. And wipe it with
another dry cloth.
•Dismantling of the unit, treatment of the refrigerant, oil
and eventual other parts, should be done in accordance
with the relevant local and national regulations.
2. FUNCTIONS AND OUTLINE
Power Proportional Distribution Card, in combination with an
existing intelligent Touch Controller, enables to proportionally
calculate and display electricity amount used by air conditioner
per indoor unit.
[Main Functions]
Power proportional distribution results data can be saved for 12
months. (max. 12 months and 30 days)
• Per intelligent Touch Controller, power proportional distribu-
tion can be calculated for 64 indoor units at maximum.
• 3 Electric power meters at maximum can be connected to an
intelligent Touch Controller.
• Power proportion distribution results data can be saved into a
PCMCIA card.
Data is saved CSV format generally applied to personal com-
puters, so bills can be issued by use of a general purpose
table calculation software package in easy manners.
(A personal computer and a general purpose table calcula-
tion software package can be available separately.)
• The above functions of power proportional distribution are
available to the optional website function software as well.
[Precautions]
This system calculates electricity consumptions by size of
indoor units, run time, expansion valves open gap, suction rate
and the number of pulses from the power meters installed at the
Outdoor Units.
This method is not calculated by direct measurement alone.
Maximum of 3 Electric
power meter
Outdoor
unit
Indoor unit
123 123 123
Power Proportional
Distribution Card
Bills
Electric power meter
with pulse output
intelligent Touch Contoroller
(DCS601C71)
Maximum of 64
Indoor unit
PCMCIA card slot
DIII-NET×1
An existent personal
computer of a user
can be available.
By use of a general purpose
appplication, a form of bills
can be set by a user.
General
purpose
software
01_EM06A043_EN.fm Page 2 Monday, October 16, 2006 11:25 AM

3English
3. PREPARATION
3-1 Checking Attachments
Power Proportional Distribution Card includes the following
attachments.
3-2 How to Connect
To distribute power proportionally, a test run must be performed
for the main controller.
Contact your dealer before use.
4. SIMPLIFIED CHART
CAUTION
As for how to set current clock time, refer to the manual
attached to intelligent Touch Controller.
5. INITIAL SETUP
5-1 Power Proportional Distribution Main Menu
Settings of power proportional distribution is made via the sys-
tem setup menu.
To display the system setup menu, press the S button at the
bottom on the screen.
NOTE
• Before initial setup, be sure to set the current clock time.
Software ID LIMITED
WARRANTY
Power proportional
distribution main menu
• Exclusion Periods (Normal Type)
• Special Calculation Days (Normal Type)
• Power Proportional Distribution Report
See page [4]
• Case to time limit set up
• Case to designate month
• Display in unit of indoor unit
• Display in unit of zone
• Total sum display
See page [5]
See page [6]
See page [6]
See page [7]
See page [7]
See page [7]
Press S button of the
fundamental screen.
When the S button is pressed,
the screen shown below
will appear.
Press “Pwr Prp Dist” in the
system setup menu to display
it inverted, and then press
Execute button.
To set Exclusion Periods
(Normal Type), press this
button on the screen.
To set Special Calculation
Days (Normal Type), press
this button on the screen.
To get back to the
previous screen,
press this button
on the screen.
To set Power
Proportional Distribution
Report, press this button
on the screen.
01_EM06A043_EN.fm Page 3 Monday, October 16, 2006 11:25 AM

English 4
5-2 How to set Exclusion Periods (Normal Type)
This function is only for normal type, and exclusion periods where power proportional distribution calculation is not carried out and
week days can be set. For example, it can be used when to collect fixed charges during day time in week days and carry out power
proportional distribution calculation only for overtime work and holiday work. Time zone can be set per week day. By the way, this setup
is of all systems, and it is impossible to make different settings in unit of zone.
[The numeric keyboard]
[How to set End Time]
When end time is set at 24:00 (at midnight),
enter 00:00.
When Exclusion Periods is set in the above setup, the following
setting contents appear.
CAUTION
When end time is set over 24:00, it is considered it is set from
0:00 of the day.
Press Exclusion Periods
(Normal Type).
4.
When to end setup, press OK button.
1. How to set Begin Time
Press Begin button of the week day you want to
set, and set the begin time in exclusion periods
where power proportional distribution calculation
is not carried out.
∗
The numeric keyboard appears. Set Begin Time.
2. How to set End Time
Press End button of the week day you want to
set, and set the end time in exclusion periods
where power proportional distribution
calculation is not carried out.
∗
The numeric keyboard appears. Set End Time.
3. How to cancel time setting
When to cancel Exclusion Periods
where power proportional distribution
calculation is not carried out , press
Disabled button.
5. When to cancel setup, press Cancel button.
(Settings remain same as previous.)
Fri.Tue. Wed. Thu.
08:30 17:00 08:30 19:30
Exclusion Periods
Power
proportional
distribution
Power
proportional
distribution
Power
proportional
distribution
Power proportional
distribution
Sun. Mon. Tue.
22:0007:00
Ex.)
22:00
End time
7:00
Mon.
Exclusion Periods
Begin time
01_EM06A043_EN.fm Page 4 Monday, October 16, 2006 11:25 AM

5English
5-3 Special Calculation Days (Normal Type)
Even in the case where Exclusion Periods (Normal Type) is set,
it is available to set a day when power proportional distribution
calculation is specially carried out all the day (0:00 - 24:00).
Setting is made for one year in unit of day.
For example, it is used when to carry out power proportional dis-
tribution for all the day in irregular holidays.
You can make settings on a year basis, and the month and date
that are set will be valid in the next year as well.
If settings are made for February 29 of a leap year, the same
setting will be effective on February 29 in the next leap year.
This function has a setting range up to December 2037.
6. POWER PROPORTIONAL DISTRIBU-
TION REPORT OUTPUT PROCEDURES
Here are descriptions of procedures to output monthly Power
Proportional Distribution Report.
CAUTION
Monthly Power Proportional Distribution data will not be col-
lected unless initial setup has been carried out.
[Screen Display Procedures]
Press Special Calculation
Days (Normal Type).
3
.
When to end setup, press OK button.
2
.
Select the day
you want to set.
∗When the day
portion is pressed,
a is displayed.
∗When the day
portion with a is
pressed, the
disappears and
setup is cleared.
1
. Select the month you want to set.
When << is pressed, the previous month is displayed.
When >> is pressed, the next month is displayed.
4
. When to cancel setup, press Cancel button.
(Settings remain same as previous.)
1Insert Power Proportional Distribution Card into PCMCIA
card slot of intelligent Touch Controller.
2Press S button in the default screen of intelligent Touch
Controller.
3Select the Pwr Prp Dist in the System Setup menu, and
press Execute button.
4Press Result output button in the Pwr Prp Dist menu.
5
Select either period designation or month designation.
In the case of period designation, enter calculation start
day and calculation end day.
In the case of month designation, designate the calcula-
tion day since calculation is made in unit of month.
6Press Execute button.
7Power Proportional Distribution Report is displayed on the
screen.
01_EM06A043_EN.fm Page 5 Monday, October 16, 2006 11:25 AM

English 6
7. HOW TO OUTPUT POWER PROPOR-
TIONAL DISTRIBUTION REPORT
7-1 Display of Power Proportional Distribution Report
There are 2 methods to display Power Proportional Distribution
Report, the method to designate a period and the one to desig-
nate a month.
•Case to Time Limit Setup
In Time Limit Setup, the period for power proportional distri-
bution calculation can be designated optionally.
For example, it can be used when zone is changed in middle
of a month and you want to see Power Proportional Distribu-
tion Report divided into the period before change and the
period after change.
•Case to designate month
In month designation, Power Proportional Distribution Report
can be read in unit of one month. And by designating the cal-
culation days, Power Proportional Distribution Report for a
month from the designated calculation day of previous month
to that of next month can be displayed.
Summary period is from 0:00 of the calculation day of one
month before to 0:00 of that of this month.
Ex.) When the calculation day is set to “1” and the day of
operating displays is 1 February, the power proportional
distribution result of 1 to 31 January is summed up.
•Display of Power Proportional Distribution Report
After selecting either Time Limit Setup or Month, when Exe-
cute button is pressed, the following screen appears.
Press the Power
Proportional Distribution
Report button.
1. Select Time Limit Setup.
Press the portion.
When selected, the is displayed.
2.
Designate the starting day of calculation period.
Set the starting day of proportional distribution calculation.
∗
The numeric keyboard appears, and set the starting day.
3.
Designate the ending day of calculation period.
Set the ending day of proportional distribution calculation.
∗
When Modify button is pressed, the numeric keyboard
appears. Set the ending day.
5.
When to cancel setup, press Cancel button.
(Settings remain same as previous.)
4. After setting period,
press Execute button.
1
. Select Month.
Press the portion.
When selected, the is displayed.
2
. Designate the Calculation Day.
When Modify button is pressed, the numeric
keyboard appears.
Set the starting day of proportional distribution
calculation.
3
. After setting period,
press Execute button.
4
. When to cancel setup, press Cancel button.
(Settings remain same as previous.)
1/1 1/31 2/1
Summary period
01_EM06A043_EN.fm Page 6 Monday, October 16, 2006 11:25 AM

7English
In case the power proportional distribution report is missing,
the display indicates the list of missing data (day / month /
year / time). The list indicates up to a maximum of 100 cases.
If the missing data exceed 100 cases, the list indicates only
the first 100 cases. If OK button is pressed, the display indi-
cates the power proportional distribution report.
•Display in unit of indoor unit
[Cautions]
Display of In/Unit Name
1:1-00 ~ 1:4-15 display indoor units connected to intelligent
Touch Controller (DCS601C71).
•Display in unit of zone
When Zone is selected, the total of Power Proportional Distri-
bution Report of indoor units registered in zone is displayed.
•Total sum display
When All is selected, the total of Power Proportional Distribu-
tion Report of all the indoor units is displayed.
Insert the Power Proportional Distribution Card all the way
into the insertion mouth on the left-hand side of the intelligent
Touch Controller.
Check that the Power Proportional Distribution Card is
seated in the right direction as shown below.
Display of Power
Proportional
Distribution Report
In/Unit Name
1:1-0 205.35702.915
Idling PowerUsed Power
[Display contents
explanation]
1
. When to display Power Proportional Distribution
Report per indoor unit, select In/Unit.
∗Press the portion.
When selected, it turns to .
[Used Power] [Idling Power]
Used to
scroll left.
Used to scroll right.
The display is toggled in the order
of Used Power and Idling Power.
1. When to display Power Proportional
Distribution Report per zone, select the Zone.
∗Press the portion.
When selected, it turns to .
Used to
scroll left.
Used to scroll right.
The display is toggled in the order
of Used Power and Idling Power.
1. When to display the total of Power
Proportional Distribution Report of all the indoor
units, select All.
∗Press the portion.
When selected, it turns to .
32MB
Compact Flash
R
01_EM06A043_EN.fm Page 7 Monday, October 16, 2006 11:25 AM

English 8
7-2 Saving Files
Power Proportional Distribution Report can be saved. When to
print out Power Proportional Distribution Report, when to dis-
play electric power amount in unit of tenant, and when to con-
vert electric power amount into charges, edit these files in your
general purpose spread sheet software.
[Cautions]
Display of In/Unit Name
1:1-00 ~ 1:4-15 display indoor units connected to intelligent
Touch Controller (DCS601C71).
CAUTION
The minimum of 12 months to the maximum of 12 months and
30 days of the power proportional distribution results data can
be retained.
When the month changes, the data of the previous month of
the previous year will be zero cleared.
(Example)
1.When reading the power proportional distribution results on
31 May 2005, the data from 1 May 2004 to 30 May 2005 can
be read.
2.When reading the power proportional distribution results on 1
June 2005, the data from 1 June 2004 to 31 May 2005 can be
read.
7-3 File Format
When Power Proportional Distribution Report is saved, a zone
information file, an electric power information file and detailed
information file are created.
1.Zone information file
This contains zone name and information of air conditioners
in the zone.
1.File name : ZONE.CSV
2.File format:
(Example)
[Cautions]
Zone ID is automatically assigned. Do not change it.
2.Electric power information file
This file contains Power Proportional Distribution Report and
information of air conditioners.
1
.
Insert the Power Proportional
Distribution Card (PCMCIA card)
into the intelligent Touch Controller,
and press To File button.
2
. Power Proportional Distribution Report
is saved into the PCMCIA card.
And the saved file name is displayed.
Zone ID, Zone Name Index
0, “ ’ All” Zone ID, zone name
1, “ ’ Z-000”
2, “ ’ Z-001”
3, “ ’ Z-002”
One line space
zone ID, A/C Unit No Zone ID, air conditioner
number
0, 0
0, 1
1, 2
1, 3
1.File name : YYYYMMDD _YYYYMMDD. CSV
Month and date of calculation
completion
Year, month and date of calculation start
5 / 2004 6 / 2004 7 / 2004 5 / 2005 6 / 2005
1.
The data of maximum 12 months and 30 days
2.
The data of minimum 12 months
01_EM06A043_EN.fm Page 8 Monday, October 16, 2006 11:25 AM

9English
(Example)
When the data from 25 Oct. 2000 to 24 Nov. 2000 are
totalled, the results are indicated as
“20001025_20001124. CSV”. If the file of the same name
already exists, it overwrites.
2.File format :
(Example)
Start Date, Nb of Days, A/C Type, Undistributed Power
Amount,Period Type
20050101,31,0,0,200501
A/C Unit No,In/Unit Name,HP Code,Daytime Used
Pwr,Nighttime Used Pwr,Daytime Idle Pwr,Nighttime Idle
Pwr,Gas Amount
0,“’1:1-00”,38,2459,0,0,0,0
1,“’1:1-01”,38,2718,0,0,0,0
2,“’1:1-02”,38,3105,0,0,0,0
3,“’1:1-03”,38,3494,0,0,0,0
4,“’1:1-04”,38,4141,0,0,0,0
60,“’1:4-12”,70,489,0,0,0,0
61,“’1:4-13”,8c,779,0,0,0,0
62,“’1:4-14”,2d,779,0,0,0,0
63,“’1:4-15”,47,1115,0,0,0,0
[Cautions]
Meaning of each data
Start Date : The starting day of sum
Nb of Days : Number of days of sum
A/C Type : 0 fixed
Undistributed Power Amount
: 0 fixed
Period Type : Period designation system (0 : Period
designation system, Date : Month desig-
nation system)
A/C Unit No : Number of indoor unit (0 ~ 63.)
In/Unit Name : Name of indoor unit
HP Code : Horsepower of indoor unit
Daytime Used Pwr : Power amount used
Nighttime Used Pwr : Not used
Daytime Idle Pwr : Electric power amount at stoppage (The
amount is displayed, only when power
proportional distribution calculation is
not carried out at stoppage.)
Nighttime Idle Pwr : Not used
Gas Amount : Not used
3.Detailed information file
1.File name : HOURLY.CSV
If the detailed information already exists, it will
overwrite.
Therefore, it is necessary to backup the data
to a PC at every data output.
The data of the period designated by the power propor-
tional distribution report (from 01:00 of the day the tabula-
tion started to 0:00 of the next day the tabulation ended)
are output. Regardless of whether the registration exists
or not in the commissioning tool, the results of 64 (or 128)
units of air conditioners are output.
2.File format:
(Example)
PPD Hourly Data (Wh)
Note:,Date and Time mean the calculation time of PPD.
,The value of 3:00 is a result between the calculation time
just before 3:00 and 3:00.
Date,Time,’1:1-00,’1:1-01,’1:1-02,’1:1-03, --- ,’1:4-15,
2006.9.10 1:00
50,21,15,21,20,21,30, --- 45,53,18,41,15, --- 15
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
45,20,31,20,21,21,30, --- 15,14,13,23,25, --- 18
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
2006.9.10 2:00
24,31,15,14,13,10,10, --- 45,32,14,19,18, --- 16
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
31,24,25,15,16,17,32, --- 15,10,21,15,18, --- 16
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
2006.9.10 3:00
50,21,15,21,20,21,30, --- 45,53,18,41,15, --- 15
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
45,20,31,20,21,21,30, --- 15,14,13,23,25, --- 18
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
2006.9.10 4:00
24,31,15,14,13,10,10, --- 45,32,14,19,18, --- 16
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
31,24,25,15,16,17,32, --- 15,10,21,15,18, --- 16
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
2006.9.10 5:00
50,21,15,21,20,21,30, --- 45,32,14,19,18, --- 16
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
45,20,31,20,21,21,30, --- 15,10,21,15,18, --- 16
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
2006.10.10 0:00
45,32,14,19,18,21,16, --- 24,31,15,14,13, --- 10
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
15,10,21,15,18,21,16, --- 31,24,25,15,16, --- 15
0, 0, 0, 0, 0, 0, 0, --- 0, 0, 0, 0, 0, --- 0
[Cautions]
View of data
Indoor Unit No. 1-00
The data shown covers a
period from 1:00 to 3:00 on
August 1, 2006.
Used Power 10kw
Not Used
Idling Power 5kw
Not Used
01_EM06A043_EN.fm Page 9 Monday, October 16, 2006 11:25 AM

English 10
8. TROUBLESHOOTING
Symptom Cause and counter
measures
“Pwr Prp Dist” is not displayed. Power Proportional Distribu-
tion function is not set yet.
Contact your supplier.
When power proportional distribu-
tion calculation is carried out, the
following message is displayed.
There is a time zone when
power proportional distribu-
tion calculation is not made in
the designated collection
period. The cause for non
availability of power propor-
tional distribution calculation
can be power failure.
Press OK button to continue
collection.
∗Collection is made by other
period excluding the day.
When Power Proportional Distri-
bution Report is to be saved into a
file, “No memory card” is dis-
played.
PCMCIA card is not inserted
correctly into the intelligent
Touch Controller.
Check whether PCMCIA card
is inserted, and whether it is
inserted correctly or not.
I can’t display electric power
amount in unit of tenant.
When electric power propor-
tional distribution is carried
out by the intelligent Touch
Controller mainframe, electric
power amount is displayed in
unit of air conditioner or in unit
of zone.
To display electric power
amount in unit of tenant, edit
the data of CSV format saved
in PCMCIA card by use of
your general purpose table
calculation software.
How do I convert electric power
amount into charges?
It is not available to convert
electric power amount into
charges by the intelligent
Touch Controller. To convert
electric power amount into
charges, edit the data of CSV
format saved in PCMCIA card
by use of your general pur-
pose table calculation soft-
ware.
How to print out Power Propor-
tional Distribution Report?
The intelligent Touch Control-
ler does not have printing
function. To print out Power
Proportional Distribution
Report, print out the data of
CSV format saved in PCM-
CIA card by use of your per-
sonal computer and printer.
Symptom Cause and counter
measures
How to change zone registration? To change zone registration
for change of insertion and so
forth in the middle of month,
read out once Power Propor-
tional Distribution Report for
the days to the previous day
of change.
(By period designation, it is
possible to designate and
read an optional period.)
For the month with change,
read the reports for days
before change and those for
days after change.
Exclusion Periods (Normal Type)
setup and Special Calculation
Days (Normal Type) setup
Exclusion Periods (Normal
Type) setup and Special Cal-
culation Days (Normal Type)
setup are not to be set when
to carry out power propor-
tional distribution of ice stor-
age type.
And setting is for only one
pattern, and it is not available
to make different setting per
zone.
Electric power amount at stop-
page
“Electric power amount at
stoppage” in the display of
Power Proportional Distribu-
tion Report is the total value
of electric power amount
when it is set not to propor-
tionally distribute electric
power of crank case heater
consumed at stoppage of air
conditioner since the electric
power amount cannot be
divided to any air conditioner.
The electric power amount in
this case must be handled as
common service fees and so
forth.
“Time Zone Setup” is not dis-
played.
“Time Zone Setup” can be
displayed in SE Mode. Con-
tact your supplier.
When the S button is presed,
“Password for administrator” is
displayed.
Confirm your administrator to
enter the password.
01_EM06A043_EN.fm Page 10 Monday, October 16, 2006 11:25 AM

11 English
9. AFTER-SALES SERVICE
After-sales Service
•To have the product repaired, prepare the following
information
• Model
• Date of installation
• Circumstances - as detailed as possible
• Address, name, phone number
•Transfer
Transfer requires professional technique. Be sure to contact
the supplier you purchased the product from or service sta-
tion.
The customer will be charged for the expense required for
transfer work.
•Questions
For after-sales service, contact the supplier you purchased
the product from or the nearest service center.
01_EM06A043_EN.fm Page 11 Monday, October 16, 2006 11:25 AM




(0609) HT
EM06A043
00_CV_EM06A043.fm Page 2 Tuesday, September 12, 2006 1:27 PM
Table of contents
Popular Software manuals by other brands

McAfee
McAfee STUDENT SURVIVAL KIT 1.0-GETTING STARTED Getting started

Netscape
Netscape NETSCAPE MANAGEMENT SYSTEM 4.5 - PLUG-IN manual

Novell
Novell ZENWORKS PATCH MANAGEMENT 6.4 - AGENT installation guide

ADS Technologies
ADS Technologies RDX-155-EF Getting started

Adobe
Adobe 65030083 - Technical Communication Suite manual

Nortel
Nortel V2.3 release note

APPLIED ACOUSTICS SYSTEMS
APPLIED ACOUSTICS SYSTEMS TASSMAN user manual

Novell
Novell ZENWORKS APPLICATION VIRTUALIZATION - V8.0.3 INTEGRATION AND STREAMING... user guide

Yamaha
Yamaha Studio Manager v.2 installation guide

Autodesk
Autodesk AUTODESK MUDBOX 2011 - SYSTEM REQUIREMENTS manual

Canon
Canon PowerShot A310 Software user's guide

AVIRA
AVIRA WEBPROTECTOR user manual