Data Aire LonWorks dap4 User manual

Data Aire
dap4
LonWorks Interface Instructions
Data Aire, Inc.
230 West BlueRidge Ave.,
Orange, CA 92865
Document number: 600-000-966
April 2014
Revision 3.0

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
2
Table of Contents
1. Introduction....................................................................................................3
2. Physical channels..........................................................................................3
3. Layout of the boards......................................................................................3
4. Meanings of the LEDs ...................................................................................3
5. Installation......................................................................................................4
6. Connection to the LonWorks® network .........................................................5
7. XIF and NXE file for dap4..............................................................................6
8. dap4 LonWorks Point list...............................................................................6

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
3
1. Introduction
The dap4 LonWorks card (Data Aire P/N 160-700-020) is an optional network card
which allows the dap4 controller to be connected directly to a LonWorks®network.
The use of these boards requires knowledge of and experience with the LonWorks®
network installation and maintenance tools. The LonWorks card can be factory
installed or field installed.
2. Physical channels
The LonWorks card uses an Echelon®FTT-10 transceiver, approved for use on the
TP/FT-10 channel.
This channel has the following main characteristics:
Alllowing the connection of a maximum of 64 nodes for each network
segment;
The nodes can be connected without any restrictions in the topology: that is,
star, ring, on one bus only, or with any combination of these.
Communication speed: 78,125 kbps;
Maximum distance (Belden 85102 cable): 500m for connections between the
nodes with free topology.
3. Layout of the boards
Fig. 1 – LonWorks card
1. Connector to the dap4 controller BMS card.
2. Terminal block for LonWorks® network (GND, A, B).
3. Service pin.
4. Green service LED.
5. Red fault LED.
For details on the activation of the service pin, see Connection to the LonWorks®network.
4. Meanings of the LEDs
The green service LED:
Signals the status of the node, as per the LonWorks®protocol:
Hardware fault: always ON or always OFF;
Node configured (normal operation): ½ second ON, then always OFF;
Node NOT configured: flashing at ½ Hz;
Node without software application: 1 second ON, 2 seconds OFF, then always OFF;
Node in continuous reset: flashing;
Remains on during the activation of the service pin;

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
4
Remains on for one second when receiving a wink command via the network
(see Connection to the LonWorks® network).
The red fault LED:
Signals problems in the connection between the board and the dap4 controller.
WARNING
If the red LED comes on, make sure the instructions described under Installation have
been carefully followed. Network address must be greater than 1 (Use screw driver and
press button next to J3 connector to display the network address) and protocol must be
set to Lon on dap4 network config menu.
5. Installation
IMPORTANT WARNINGS: precautions in handling the board. Electrical damage
may occur to the electronic components as a result of electrostatic discharges from
the operator. Suitable precautions must be therefore be taken when handling these
components, specifically:
Before handling any electronic component or board, touch an earthed object
(simply not touching the component is not enough to prevent a spike, as static
electricity can produce a 10000V discharge, which can form an arc of about
1cm).
All materials must be kept inside their original package as long as possible. If
necessary, take the controller from its package and place it into antistatic
packaging, without touching the back of the board;
Absolutely avoid non-antistatic plastic bags, polystyrene or sponges;
Do not pass the electronic components or boards directly to other operators (to
prevent electrostatic induction and discharges).
Connect Lonworks card to the dap4 or Mini-dap4
With reference to Figs. 2- 5 below, insert the board in the dap4 or Mini-dap4 as
follows:
1. Disconnect the power supply to the controller.
2. Using a screwdriver, remove the BMS card cover (serial card cover on Mini-
dap4) (see Fig. 2).
3. With cutting nippers, remove the pre-cut plastic part from the cover, thus making
the opening for the 3-pin connector (see Fig. 3).
4. Insert the LonWorks card in the corresponding plug-in connector, initially holding
it diagonally and then making sure it is properly inserted and pushed up against
the two plastic supports on the case of the dap4 (see Fig. 4);
5. Close the cover again, aligning the connector on the card with the hole made in
the cover (see Fig. 5).
6. Reconnect the power supply to the controller; if the BMS 1 communication port
has been set to use the Lon protocol, the red LED on the board will come on for
a few seconds and then will go off immediately, indicating correct operation.

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
5
Fig. 2 Fig. 3
Fig. 4 Fig. 5
6. Connection to the LonWorks®network
The physical connection to the LonWorks®network is performed using the connector
with removable terminals fitted on the board, according to the Echelon®instructions
and specifications. For further information on installation, maintenance, the cross-
section and type of cable, refer to the LonWorks®literature.
Important Note: Data Aire Dap4 Lon interface uses a Carel Lonworks card; if there is
existing equipment provided by others that uses the same Carel Lonworks card then
the device interface file (XIF) of dap4 must be manually loaded during the
commissioning process otherwise Lon network may use an incorrect device interface
template on dap4 that leads to erroneous data.
Service pin
To activate the service pin, simply momentarily short-circuit the two pins on the
board (see Fig. 1 and no.3) with the tip of a screwdriver or a similar tool.
The service pin must only be activated during the installation of the node. When
the pin is activated, the node sends a broadcast message over the LonWorks®
network, containing the information required for identification. There is sticker on
the card to indicate the Lon card neuron ID, this neuron ID can be used to
manually commission the card if service pin does not work.
After you can commission the card and the red LED is lit, reset the dap4 (power off then
back on). The Red LED should go off after dap4 starts up. If dap4 does not get reset
after commissioning, the erroneous data may appear.
WINK event
A generic supervisor can send the WINK command to a specific node on the
LonWorks®network. This generates an event that the application on the specific
node can respond to with any action decided by the programmer.

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
6
In this specific case, the service LED on the interface comes on for one second,
thus making it possible to check the correct operation of the connection between the
interface and LonWorks® network.
7. XIF and NXE file for dap4
The XIF and NXE for dap4 can be downloaded from Data Aire website for
commissioning the dap4.
http://www.dataaire.com, go to System Controls/ dap4.
8. dap4 LonWorks Point list
Note: Read = NVO, write = NVI, some parameters can be read and written, in this
case these parameters have separate NVO point for read (monitor) and NVI point for
write a new value.
Description Read/
Write Variable Name Data
Type LONworks SNVT
Temperature of return air R Ret_Air_Tmp A nvoReturnTemp 105
Maximum Return air temp in
last 24hrs R Maximum A nvoHiTempHistory 105
Minimum Return air temp in last
24hrs R Minimum A nvoLoTempHistory 105
Temperature setpoint R/W Temp_Setpoint A nvoTempSetpoint /
nviTempSetpoint 105
Temperature of chilled water R CW_Tmp A nvoWaterTemp 105
Temperature of discharge air R Disch_Air_Tmp A nvoDischTemp 105
Value of the analog input 1 R Opt1_Analog A nvoOpt1_Analog 8
Value of the analog input 2 R Opt2_Analog A nvoOpt2_Analog 8
Value of the analog input 3 R Opt3_Analog A nvoOpt3_Analog 8
Value of the analog input 4 R Opt4_Analog A nvoOpt4_Analog 8
Lower limit alarm of discharge
air temp Write
only Disch_Air_Lo_SP I nviLoDiscLimit 105
Relative humidity displayed as
xx% R Humidity_dis I nvoHumidity 8
Cooling Stages On = Cooling
stages are currently on This
point applies to DX unit only
R Stages_On I nvoCoolStagesOn 8
Number of heat stages running R Heaters_On I nvoHeatStagesOn 8
Maximum humidity in last 24hrs R Maximum I nvoHiHumHistory 8
Minimum humidity in last 24hrs R Minumum I nvoLoHumHistory 8

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
7
Description Read/
Write Variable Name Data
Type LONworks SNVT
Cooling Utilization Over Last
Hour -Percentage of cooling is
used in the last hour of
operation; this point applies to
DX unit.
R Comp_duty I nvoCoolUtlz 8
Heating Utilization Over Last
Hour -Percentage of heating is
used in the last hour of
operation
R Heat_duty I nvoHeatUtlz 8
Humidifier Utilization Over Last
Hour -Percentage of humidifier
is used in the last hour of
operation
R Hum_duty I nvoHumUtlz 8
Compressor 1 Runtime -This
point applies to DX unit with one
compressor -high
R C1_Hours_H I nvoC1_Hours_H 8
Compressor 1 Runtime -This
point applies to DX unit with one
compressor -low
R C1_Hours_L I nvoC1_Hours_L 8
Compressor 2 Runtime -This
point applies to DX unit with
dual compressor - high
R C2_Hours_H I nvoC2_Hours_H 8
Compressor 2 Runtime -This
point applies to DX unit with
dual compressor - low
R C2_Hours_L I nvoC2_Hours_L 8
Heater 1 Runtime - high R Ht1_Hours_H I nvoHt1_Hours_H 8
Heater 1 Runtime - low R Ht1_Hours_L I nvoHt1_Hours_L 8
Humidity upper limit alarm Write
only Hum_Hi_SP I nviHiHumLimit 8
Upper limit alarm of return air
temp Write
only Ret_Air_Hi_SP I nviHiTempLimit 105
Humidity setpoint R/W Hum_setpoint I nvoHumSetpoint /
nviHumSetpoint 8
CW valve open % (0-100% with
10% increment) R CW_disp I nvoValve 8
Chilled Water Utilization Over
Last Hour - This applies to
Chilled water or Energy saver
units.
R WtrVlv_duty I nvoChillUtlz 8
Humidifier Runtime - high R Hum_Hours_H I nvoHum_Hours_H 8
Humidifier Runtime - low R Hum_Hours_L I nvoHum_Hours_L 8
Blower Runtime - high R Blower_Hours_H I nvoFan_Hours_H 8
Blower Runtime - low R Blower_Hours_L I nvoFan_Hours_L 8

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
8
Description Read/
Write Variable Name Data
Type LONworks SNVT
CW Fan speed (%) sent via
BMS Write
only CW_Fan_Speed_bms I nviCW_Fan_Speed 8
DX Fan speed (%) sent via
BMS Write
only DX_Fan_Speed_bms I nviDX_Fan_Speed 8
Heater 2 Runtime - high R Ht2_Hours_H I nvoHt2_Hours_H 8
Heater 2 Runtime - low R Ht2_Hours_L I nvoHt2_Hours_L 8
Heater 3 Runtime - high R Ht3_Hours_H I nvoHt3_Hours_H 8
Heater 3 Runtime - low R Ht3_Hours_L I nvoHt3_Hours_L 8
Chilled Water Runtime - This
applies to chilled water units
only - high
R CW_Hours_H I nvoCW_Hours_H 8
Chilled Water Runtime - This
applies to chilled water units
only - low
R CW_Hours_L I nvoCW_Hours_L 8
Zone Airflow Setpoint kcfm
(Enter Total airflow
setpoint/100)
Write
only ZM_Airflow_SP I nviZone_Air_Setp 8
Water under floor alarm R Floor_Wtr_alm D Alarm_1 . Bit0 83
No air flow alarm R Air_Flow_alm D Alarm_1 . Bit1 83
Dirty filter from digital input R Filter_alm D Alarm_1 . Bit2 83
Alarm from humidifier digital
input R Humidifier_alm D Alarm_1 . Bit3 83
Temperature of return air above
firestat alarm set point R Firestat_alm D Alarm_1 . Bit4 83
One or more comps has short
cycled R Shortcycle_alm D Alarm_1 . Bit5 83
Loss of power requires manual
reset of alarm R PwrUp_alm D Alarm_1 . Bit6 83
Sensor is out of range R Humidity_fail D Alarm_1 . Bit7 83
Sensor is out of range R Ret_Air_fail D Alarm_1 . Bit8 83
Maintenance Schedule Due
alarm R Maint_alm D Alarm_1 . Bit9 83
High pressure alarm R C1_HP_alm D Alarm_1 . Bit10 83
Low pressure alarm R C1_LP_alm D Alarm_1 . Bit11 83
High pressure alarm R C2_HP_alm D Alarm_1 . Bit12 83
Low pressure alarm R C2_LP_alm D Alarm_1 . Bit13 83
Smoke detected from digital
input R Smoke_alm D Alarm_1 . Bit14 83
No water flow alarm R Wtr_Flow_alm D Alarm_1 . Bit15 83
Sensor is out of range R Disch_Air_fail D Alarm_2 . Bit0 83
Temperature of return air above
alarm set point R RA_Tmp_hi_alm D Alarm_2 . Bit1 83

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
9
Description Read/
Write Variable Name Data
Type LONworks SNVT
Temperature of return air below
alarm set point R RA_Tmp_lo_alm D Alarm_2 . Bit2 83
Humidity above alarm set point R Hum_hi_alm D Alarm_2 . Bit3 83
Humidity below alarm set point R Hum_lo_alm D Alarm_2 . Bit4 83
Fan overload R Fan_Overload D Alarm_2 . Bit5 83
Local alarm #1: See tag inside
door =Optional alarm. External
alarm input required
R SeeTag_cust_alm1 D Alarm_2 . Bit6 83
Local alarm #2: See tag inside
door =Optional alarm. External
alarm input required
R SeeTag_cust_alm2 D Alarm_2 . Bit7 83
Local alarm #3: See tag inside
door =Optional alarm. External
alarm input required
R SeeTag_cust_alm3 D Alarm_2 . Bit8 83
Local alarm #4: See tag inside
door =Optional alarm. External
alarm input required
R SeeTag_cust_alm4 D Alarm_2 . Bit9 83
Standby pump on: Check
primary pump -Optional alarm.
Pump failure input signal
required
R Stdby_Pump_On D Alarm_2 . Bit10 83
Alarm: UPS power on: Check
main power -Optional alarm.
External alarm input required
R Ups_On_alm D Alarm_2 . Bit11 83
Custom alarm #1 -Optional
alarm. External alarm input
required. Factory programmed
custom message required
R Cust_msg_Sw1 D Alarm_2 . Bit12 83
Custom alarm #2 -Optional
alarm. External alarm input
required. Factory programmed
custom message required
R Cust_msg_Sw2 D Alarm_2 . Bit13 83
Custom alarm #3 -Optional
alarm. External alarm input
required. Factory programmed
custom message required
R Cust_msg_Sw3 D Alarm_2 . Bit14 83

Dap4 LonWorks Interface Instructions
Document number 600-000-966 Ver. 3
10
Description Read/
Write Variable Name Data
Type LONworks SNVT
Custom alarm #4 -Optional
alarm. External alarm input
required. Factory programmed
custom message required
R Cust_msg_Sw4 D Alarm_2 . Bit15 83
Humidifier stopped due to
custom alarm switch R HumSw_Inhibit D Alarm_3 . Bit0 83
Heat inhibited due to custom
switch alarm condition R Heat_inhibit D Alarm_3 . Bit1 83
Reheat and humidification
inhibited from operation R Rht_Hum_inhibit D Alarm_3 . Bit2 83
Temperature of discharge air
below alarm set point R Disch_Tmp_lo_alm D Alarm_3 . Bit3 83
Manual override: Check bypass
switches - Standard alarm.
Manual override switch is on
R Override_Alm D Alarm_3 . Bit4 83
High condensation from digital
input R Condensation_alm D Alarm_3 . Bit5 83
Unit in standby, all functions
held off - Optional alarm.
Control input signal required
Factory setting required
R Unit_In_Standby D Alarm_3 . Bit6 83
Cooling operation inhibited by
BMS R/W BMS_Cooling_inhibit D nvoBMSCool_In /
nviBMSCool_In 95
Heat inhibited due to bms R/W BMS_Heat_inhibit D nvoBMSHeat_In /
nviBMSHeat_In 95
Humidifier operation inhibited by
BMS R/W BMS_Humidifier_inhibit D nvoBMSHum_In /
nviBMSHum_In 95
Inhibit fan by bms R/W Fan_Inhibit_bms D nvoBMSFan_In /
nviBMSFan_In 95
Supervisor (BMS) On-Off. Show
the state OFFbyBMS in main
mask (1: Off; 0: On)
R/W Superv_Off D nvoSuperv_Off /
nviSuperv_Off 95
BMS-heartbeat is to confirm the
communication with BMS.
This variable must change at
least once every 5 minutes or
unit will revert on mode if it is
command to off
Write
only BMS_Heartbeat D nviBMS_Heartbeat 95
Table of contents
Other Data Aire Network Card manuals
Popular Network Card manuals by other brands

HP
HP Memory Modules user guide

ZyXEL Communications
ZyXEL Communications ZYWALL TURBO CARD user guide

Rosewill
Rosewill RC-NIC416Dual user manual

Huawei
Huawei Pocket WiFi 3G user manual

Socket
Socket 10/100 Ethernet CF Card user guide

MikroTik
MikroTik RouterBOARD 711UA-2HnD Quick setup guide and warranty information

Quanta Computer
Quanta Computer WMA1 user manual

MGE UPS Systems
MGE UPS Systems minislot 66244 user manual

Xerox
Xerox WNA-100 - Bridge installation guide

Allied Telesis
Allied Telesis CONVERTEON AT-CM2K0S installation guide

SUNRICH TECHNOLOGY
SUNRICH TECHNOLOGY N-480 user manual

Echelon
Echelon PCLTA-10 PC LonTalk Adapter 73401 product manual