Deif DCP2 User manual

DEIF A/S Tel.: (+45) 9614 9614
Frisenborgvej 33, DK-7800 Skive Fax: (+45) 9614 9615
DEIF A/
S
Installation instructions
Type DCP2
Battery chargers
4189320008D (UK)
•Easy installation - DIN-rail mounting
•Automatic recovery from overload conditions
•5-10-20-40A types
•Switch mode power technology
•Extremely low ripple <100mV
+-
-+

Pa
g
e 2 of 8 Tel.:
(
+45
)
9614 9614 •Fax:
(
+45
)
9614 9615 •E-mail: deif
@
deif.com
General data
Input voltage: 3 x 400/480V AC ±15% Type: DCP2-2420 and DCP2-2440
1 x 230V AC ±15% Type: DCP2-1210, DCP2-2410 and
DCP2-2420
1 x 115V AC ±15% Type: DCP2-2410/115V
1 x 230V AC ±15% Type: DCP2-1205 and DCP2-2405
Output voltage: 23.5-27.5V DC (type DCP2-24XX and -2410/115V)
11.8-13.8V DC (type DCP2-12XX)
Output current: DCP2-XX05:
5A (typical current limit 6A)
DCP2-XX10 and -2410/115V:
10A (typical current limit 12.5A)
DCP2-2420:
20A (typical current limit 25A)
DCP2-2440:
40A (typical current limit 45A)
Terminals: DCP2-1205, -1210, -2405, -2410 and -2410/115V:
Primary max. 2.5 mm²
Secondary 2.5 mm²
DCP2-2420:
Primary max. 2.5 mm²
Secondary 4.0 mm²
DCP2-2440:
Primary max. 2.5 mm²
Secondary 10.0 mm²
Indication: Green LED – operating indication
Housing:
Materials: All plastic parts are self-extinguishing to UL94 (V0)
DCP2-2440 is encapsulated in a metal housing
Dimensions: 147 x 123 x 86 mm (DCP2-1205, -2405)
L x W x H 205 x 123 x 86 mm (DCP2-1210, -2410, -2410/115V)
(Appendix) 240 x 153 x 86 mm (DCP2-2420)
292 x 185 x 130 mm (DCP2-2440)
Distance for con-
vection: 100 mm above and below the DCP2, 30 mm to each side
Mounting: DIN-rail, EN 50022-35

Installation instructions, DCP2
4189320008D
(
UK
)
Safety: VDE0805/EN60950/IEC950
Protection: Class I
Deg. of protection: IP20
Leakage current: <0.75mA (47-63Hz line frequency)
(DCP2-2420 3-phase supply and DCP2-2440: <3.5mA)
Weight: DCP2-1205 approx. 0.8 kg
DCP2-2405 approx. 0.8 kg
DCP2-1210 approx. 1.2 kg
DCP2-2410 approx. 1.2 kg
DCP2-2410/115V approx. 1.2 kg
DCP2-2420 approx. 1.9 kg
DCP2-2440 approx. 3.6 kg

Pa
g
e 4 of 8 Tel.:
(
+45
)
9614 9614 •Fax:
(
+45
)
9614 9615 •E-mail: deif
@
deif.com
Functions and settings
Besides the output terminals (secondary side) the DCP2 has a trim potentiometer for
setting of the output voltage. By means of an insulated slotted screwdriver or adjusting
pin the output voltage can be set in the range 23.5-27.5V respectively 11.8-13.8V.
Setting:
Lower output voltage = Counterclockwise rotation
Higher output voltage = Clockwise rotation
The LED on the front indicates that the unit is operational.
Illustration:
Terminals of the secondary side and setting potentiometer for output voltage.
DCP2-XX05 DCP2-XX10 and -XX10/115V
CAUTION:
For DCP2-2420 and DCP2-2440 the plugs on the secondary side have two terminals
for each pole (+/-). The current can be drawn by one single terminal for each pole.
DEIF recommends to use both terminals for each pole to avoid any unnecessary
heating of the connection.
DCP2-2420 DCP2-2440
Setting pot Setting pot
Setting pot Setting pot

Installation instructions, DCP2
4189320008D
(
UK
)
Mounting
To obtain optimum cooling it is imperative to comply with the specified installation
position, where the input terminals (L1, L2, L3, PE or L1, N, PE) are placed at the top
and the output terminals (+/-) at the bottom.
Distance:
Above and below the DCP2 100 mm
To each side 30 mm
The permissible ambient temperature must not be exceeded:
-10...70°C (operating, free convection)
-25...85°C (storage)
Connection:
See the cover of the unit (imprint). The phase sequence is indifferent.
Protection:
Units supplied by 1 x 230V AC are internally protected by a fuse and can be
connected directly to line.
The power cords for 3 x 400/480V AC units must be protected by a three-pole C-fuse
or a three-pole motor circuit breaker (only DCP2-2420 and DCP2-2440). Operating
with a disconnected phase is not permissible.
Fuse: DCP2-1205, -2405:
5 x 20 mm T3.15A/250V internal
DCP2-1210, -2410, -2410/115V:
5 x 20 mm T6.3A/250V internal
DCP2-2420:
5 x 20 mm T10A/250V internal
DCP2-2420, -2440:
Three poles, C-fuse or motor circuit breaker
Switch - external (setting 3A)
CE marking
All variants of the DCP2 are CE marked to the EMC Directive and the Low Voltage
Directive. However, the following comments concerning EN 61000-3-2 (limits for
harmonic current emissions) apply and must be observed upon installation of the 10A
and 20A variants:
If the 10A and 20A variants are used as part of an apparatus which has a rated AC
power of 1kW or more, there is no requirement for compliance with EN 61000-3-2.
If the 10A and 20A variants are used as part of an apparatus which has a rated AC
power less than 1kW, compliance with EN 61000-3-2 must be ensured by the maker
of the apparatus. In this case the maker of the apparatus containing the DCP2 must

Pa
g
e 6 of 8 Tel.:
(
+45
)
9614 9614 •Fax:
(
+45
)
9614 9615 •E-mail: deif
@
deif.com
carry out CE marking to the EN 61000-3-2 himself. All other parts of the CE marking
provided by DEIF A/S are still valid.
Alternatively, permission to connect the 10A and 20A variants must be given by the
local power supply authority of the place of installation of the DCP2, as stipulated by
EN 61000-3-2, clause 4. In this case the entire CE marking provided by DEIF A/S,
including to EN 61000-3-2, is valid.
The protective earth (PE) of the DCP2 must be connected to the protective earth
of the switchboard.
Illustration:
Grid connection.
DCP2-XX05, DCP2-XX10, -XX10/115V DCP2-2420 and DCP2-2440
and DCP2-2420

Installation instructions, DCP2
4189320008D
(
UK
)
Appendix
Type Dimensions
DCP2-1205
DCP2-1210
DCP2-2405
DCP2-2410
and
-2410/115V
105
123
147
86
86
105
123
205
105
123
147
86
86
105
123
205

Pa
g
e 8 of 8 Tel.:
(
+45
)
9614 9614 •Fax:
(
+45
)
9614 9615 •E-mail: deif
@
deif.com
Type Dimensions
DCP2-2420
DCP2-2440
86
240
130
153
264
292
130 176
185
This manual suits for next models
7