
Freeze protection (when required)
4
WARNING
Only propylene glycol may be used in this
hydronic heating system, to prevent freezing.
It is recommended to add a maximum of 50%
of propylene glycol mixture to ensure proper
operation.
Do not use automotive anti-freeze, ethylene
glycol or any undiluted anti-freeze.
If the above recommendations are not
followed, severe personal injury, death or
substantial property damage can result.
All installations must include the following items:
a. 1 pressure regulator, adjusted to 12 psi, must be installed
between the boiler and the main water supply in the building;
b. 1 expansion tank, pre-pressurized to 12 psi and of appropriate
size;
c. 1 or more automatic air purge valves;
d. 1 or more circulating pumps of appropriate capacity.
CAUTION
To avoid water damage and/or scalding due to relief
valve operation, a discharge line must be connected to
the valve outlet and run to a drainage area. The
discharge line shall be installed in such a way that it
will allow for the complete drainage of the valve and
the discharge line.
1.7) INSTALLATION OF THE BOILER
At the time of installation, the following steps should be followed.
Refer to Figure 1 and 2.
1. Choose an appropriate location. Mount the boiler securely on
the wall, with the help of the mounting plate. Ensure that it is
level and that the minimum clearances are observed;
2. Install the drain valve and the safety valve as indicated in
Figure 1;
3. An air vent can be installed on the unit. In such case, use the
½’’ NPT to ⅛’’ NPT reducer, which is provided;
4. Install the water supply and return piping with the 1” NPT fitting;
5. The heating supply line must include:
a. 1 circulator along with 2 maintenance valves;
b. 1 automatic pressure reducing valve adjusted to 12 psi,
with a shut-off valve on the return water line;
c. 1 expansion tank;
d. 1 automatic vent.
6. The flow of water through the system must be sufficient to
continuously discharge the energy generated by the boiler. If
not, the High Limit protector will disconnect all the electric
elements and a more or less frequent cycling mode will be
established by the Safety Control (see the Technical
Specifications Table);
7. In order to ensure satisfactory water flow, the friction in the
piping system must not exceed the capacity of the circulator;
8. After having completed all piping connections, run water
through the system and purge the air. The automatic vent
should be in operation.
Note: Remove the panel on the right side of the unit and check
to see if the elements are watertight.
1.8) ELECTRIC POWER SUPPLY
All electrical wiring must conform to the standards and regulations in
force and the Canadian Electrical Code CSA C22.1.
Electrical power to the boiler must come from a 120/240V 60 Hz,
single phase, 3-wire, grounded circuit, protected by an appropriately
sized breaker, based on the total rating of the boiler. Refer to the
boiler nameplate and the technical specifications in this manual to
select the proper breaker and wire size.
WARNING
Risk of fire.
The conductor sizing must conform to the last
edition of the local or national codes.
Failure to follow this rule can result in death,
bodily injury and/or property damage.
Power supply to the unit can be made using copper or aluminum
wires. The wire size must be decided in accordance to unit power
consumption, the over current protection type and capacity, the wire
type and length, and the environment where the unit is installed. If
an aluminum wire is used, other precautions (such as the use of a
DE-OX inhibitor) must be taken to insure the conformity of the
installation. In all cases, all the factors affecting the wire gauge
must be considered and the installation codes followed.
The exterior of the unit must have an uninterrupted ground to
minimize the risk of bodily harm. A ground terminal is supplied with
the control box for that purpose.
In the event that wires inside the unit require replacement, these
must be as same type as originals. (Copper wiring only)
1.8.1) CONNECTING THE CIRCULATING PUMP
The electronic circuit is designed such a way that the circulator
functions, based only on demand by the thermostat.
1.8.2) CONNECTING THE THERMOSTAT
Note: All wiring outside the control panel is 24V.
Single heating zone
Connect the low voltage thermostat to TH terminals located outside
the control panel on the left side of the unit.
Multiple heating zones
Connect the contacts of the motorized valves or pump controls to
TH terminals outside the control panel on the left side of the unit.
The anticipator inside the thermostat must be adjusted according to
the electrical load connected to the thermostat.
1.8.3) CONNECTING THE OUTDOOR SENSOR
Mount the sensor on an outside wall, protected from direct sunlight,
so that it will accurately measure the outside temperature. Install 2
only #20 wires between the outdoor sensor and the terminals
identified as S1and S2on the side of the boiler.