7
CAUTION
Please note that HGRC boilers and water
heaters require water circulation whenever the
burners are on. The factory mounted pump
relay is installed for this purpose.
Failure to circulate water through the
exchanger when the burners are operating
voids the warranty.
The unit is equipped with a 120/24 VAC step down
tranformer for all internal needs. All 24 VAC connections
are built-in at the factory. A supplementary 120/24 Vac
step down transformer shall be planned for if external
equipment needs 24 VAC voltage (zone valves, etc.).
On all units the external terminals “W” and “R” are for
the connection of a room thermostat or an operating
control (aquastat, indoor-outdoor control, etc.). Simply
putting a jumper on “W” and “R” and having the
appliance run on its high Limit Control is inefficient and
not recommended.
CAUTION
If any of the original wires, as supplied with the
appliance must be replaced, they must be
replaced with 16 gauge TEW (105°C) wire or
equivalent.
8) WATER PIPING
8.1) Overview
A pressure regulator must be installed on the water feed
line to the unit and adjusted to a pressure lower than the
unit’s safety valve setting. The system must be
equipped with a circulating pump, expansion tank, air
vents and maintenance valves as indicated in Figure 5.
Also, we strongly recommend the installation of a flow-
switch. The installation of a by-pass between the return
and supply pipes is good plumbing practice and
ensures good return temperature in the heat exchanger.
8.2) Variable volume water system
Heating systems incorporating zone valves, zone
circulators or three way mixing valves operate with
reduced water circulation through the unit. The
installation must be planned by considering that a
minimum water flow must circulate through the unit. A
water flow lower than the minimum threshold could
result in a significant water temperature elevation,
provoking a knocking noise, vibrations and short cycling
operation. All these conditions are unstable and
damaging to the appliance. Always size your circulating
pump so that the minimum flow of water never falls
below the minimum flow recommended in Tables 5 and
6. If short cycling operation persist, the use of a
modulating gas valve should be considered.
CAUTION
For proper operation and to prevent
condensation on the external surfaces of the
heat exchanger, the return temperature of
your HGRC unit must always exceed 38°C
(100°F). A transition period below that
temperature is acceptable, but a permanent
return temperature below 38°C (100°F) voids
your warranty.
9) DRAFT HOOD
The draft hood delivered with your HGRC unit must be
installed without any modifications and fastened to the
collar of the appliance by way of metal screws.
10) VENTING
10.1) Chimney
CAUTION
An inadequate chimney can result in the
improper operation of the unit.