DMP Electronics Ether-Com XR Assembly instructions

INSTALLATION SHEET
Ether-Com XR
Description
The Ether-Com XR™Single Port Router allows a DMP XR200, XR200-485, or XR2400F Command Processor™ panel to
communicate with a DMP SCS-1 Receiver over an existing Ethernet network. Operating as an interface between the
panel and the network, the Ether-Com XR™ mounts inside the panel enclosure and is powered by the panel. The panel
communicates to the Ether-Com XR through a 462N Network Interface Card as shown in Figure 1. This product is for
use with a UL listed alarm control from DMP. This unit may only be connected to a ULlimited power supply.
What is included
The Ether-Com XR includes the following:
• Ether-Com XR™ Single Port Router
• Powercable
• Model 356-2 serial cable
What is needed
Additional equipment needed to install and program the Ether-Com XR:
• 386 or better PC
• Windows™with a communication software package such as Hyperterminal™
• DMP Model 396 programming cable
• 10BaseT Ethernet cable
• DMP XR200, XR200-485, XR2400F and a 462N Network Interface Card
Hardware installation
1. Installation may only be performed by installation personnel.
2. Install the Ether-Com XR into the 3-hole pattern of the panel enclosure as shown in Figure 1.
3. Connect a 10BaseT Ethernet cable from your network to the network connector (J4) of the Ether-Com XR.
4. Connect the Model 356-2 serial cable from the Ether-Com XR’s serial connector (J3) to the 462N Network
Interface Card’s network cable connector (J7), as shown in Figure 1. Refer to LT-0209 Installation Sheet
for instructions to install and setup the 462N Network Interface Card.
Note: To program the Ether-Com XR, you must use a 396 programming cable. Refer to Programming on
pages 2-4 of this guide for further instruction.
5. Plug the power cable connector into the J1 connector of the Ether-Com XR.
6. Connect the red wire of the power cable to screw terminal 7 on the processor panel. The power
requirement for the router is 200mA @ 9-14 VDC.
7. Connect the black wire of the power cable to screw terminal 10 on the processor panel.
Note: If you are extending the power cable, crimp connectors must be used.
B
ETHER-COM
XR200 Panel
J6
Expansion
Connector
462N
Network
Connector
Power
Connector
Model 356-2
Serial Cable
J7
350 Enclosure
Ether-Com XR
Figure 1: Ether-Com XR Installation
RXD = NO
TXD = NO
Baud Rate = 9600
J3 = FORCE
J6 = HST
462N jumper settings
EXT
9600
4800
2400
1200
300
FORCE CTS
J3
J2 J5
RXD TXD
YES NO
J1 YES NO J4
DNET
J6
HST

Ether-Com XR™ Installation Sheet Digital Monitoring Products
2
LED Indicators
PWR: The steady ON green LED indicates power is okay.
GOOD LNK: The steady ON green LED indicates the communication link to the network is okay.
SER STA: The yellow flashing LED indicates activity between the panel and the Ether-Com XR.
ERR: The red flashing LED indicates a communication error has occurred or programming from the PC is
in progress.
Programming
Once the equipment is installed you will need to program the Ether-Com XR using a DMP Model 396 programming
cable and a computer. Network Administrators only: For remote programming,Telnet to port 9999.
Before beginning Programming, disconnect the 356-2 serial cable from J3 of the Ether-Com XR. Connect a Model 396
programming cable from the serial port (J3) of the Ether-Com XR to any unused COM port on your computer. Then
follow the steps below the program the Ether-Com XR.
1. Open the HyperTerminal™communication program on your computer.
2. Communication settings are 9600 Baud, 8 bits, No Parity, and No Handshaking.
IMPORTANT!! Step 3 must be completed in the exact order and time frame described. Timing is critical!
3. Once the computer is ready and the 396 programming cable is connected, disconnect and then reconnect the
power cable to the Ether-Com XR. Wait approximately 1.5 seconds for the red ERR LED on the Ether-Com XR to
begin flashing. After the second flash, immediately type lower case "xxx" and do not press "ENTER". Wait 1-2
seconds and then press "ENTER" to display the Setup Mode screen. If the Setup Mode screen does not appear,
disconnect the power cable and repeat procedure.
Setup Mode
From the Setup Mode screen enter "0" and press "ENTER" for the basic setup.
Setup Mode Screen
Figure 2: Ether-Com XR™PCB
PWR ERR SER GOOD
SERIAL
NETWORK
STA LNK
J3
J4
J1
* * * Basic Parameters * * *
Hardware: Ethernet TP1
IPAddr 194.039.078.254, no Gateway set, Netmask 255.255.255.255
* * * * * * * Channel 1 * * * * * * *
Baud rate 09600, I/F Mode 4C
Port (00000)
Panel Mode, Target IPAddress is 123.123.123.121
Change Setup (0 Basic, 1 or 2 for Channel, 8 to Exit, 9 to Save and Exit)?

Digital Monitoring Products Ether-Com XR™ Installation Sheet
3
Ethernet Configuration
Ethernet interface AUI (N) _
Enter "N".
IP Address Configuration
IP Address: (123) _
Enter IP address for the Ether-Com XR number and press "ENTER". See your network administrator for
number.
Example: Press "039.017.010.002" "ENTER". (123) 039.(123) 017. (123) 010. (123) 002 is displayed.
Gateway Address Configuration
Set Gateway IPAddress (N) _
Enter "Y".
Gateway IPAddress: (000) _
Enter number and press "ENTER". See your network administrator for
number.
Example: Press "039.017.010.001" "ENTER". (000) 039.(000) 017.
(000) 010. (000) 001 is displayed.
Netmask Configuration
Netmask: Number of bits for host port (0 = Default) (08) _
Enter number and press "ENTER". See your network administrator for
number.
Example: Press "08" "ENTER". 08 is displayed.
Telnet Configuration Password
Change Telnet config password (N) _
Enter "N".
Setup Mode Screen
Enter "1" and press "ENTER".
Figure 3: Netmask Table
rebmuNksamteNstiBtsoH#
252.552.552.5522
842.552.552.5523
042.552.552.5524
422.552.552.5525
291.552.552.5526
821.552.552.5527
000.552.552.5528
000.452.552.5529
000.252.552.55201
000.842.552.55211
......
000.000.552.55261
......
000.000.821.55232
000.000.000.55242
* * * Basic Parameters * * *
Hardware: Ethernet TP1
IP Addr 039.017.010.002, Gateway 039.017.010.001, Netmask 255.255.255.000
* * * * * * * Channel 1 * * * * * * *
Baud rate 09600, I/F Mode 4C
Port (00000)
Panel Mode, Target IPAddress is 123.123.123.121
Change Setup (0 Basic, 1 or 2 for Channel, 8 to Exit, 9 to Save and Exit)?

INTRUSION • FIRE • ACCESS • NETWORKS
2500 North Partnership Boulevard
800-641-4282
www.dmp.com
Made in the USA Springfield, Missouri 65803-8877
LT-0397 (9/02) © 2002 Digital Monitoring Products, Inc.
Channel Configuration
Baud Rate (09600) _
Press "ENTER" to continue 9600.
I/F Mode (4C) ? _
Press "ENTER" to continue 4C.
Port No. (00000) ? _
Enter "02001" and press "ENTER".
Panel side (Y) _
Enter "Y".
Target IP Address: (123) _
Enter number of the SCS-1 Receiver IPAddress and press "ENTER". See your network administrator for
number.
Example: Press "123.123.123.121" "ENTER". (123) 123.(123) 123. (123) 123. (121) 121 is
displayed.
Setup Mode Screen
Press "9" to Save and Exit Setup Mode.
Ether-Com XR programming is now complete. Exit Windows™ communication program. Then, disconnect the Model 396
programming cable from the Ether-Com XR serial connector (J3). Reconnect the Model 356-2 serial cable to the Ether-
Com XR serial connector (J3).
* * * Basic Parameters * * *
Hardware: Ethernet TP1
IPAddr 039.017.010.002, Gateway 039.017.010.001,Netmask 255.255.255.000
* * * * * * * Channel 1 * * * * * * *
Baud rate 09600, I/F Mode 4C
Port (02001)
Panel Mode, Target IPAddress is 123.123.123.121
Change Setup (0 Basic, 1 or 2 for Channel, 8 to Exit, 9 to Save and Exit)?
Specifications
Primary Power: 9 - 14 VDC
Current Draw: 200mA at 12 VDC
Dimensions: 5” H x 3” W x 0.75” D
Panel Compatibility
The Ether-Com XR is compatible with DMP Model XR200,
XR200-485, and XR2400F.