Doepke Dupline DRT 1 User manual

3931226/2009.06/C
Doepke
Dupline
Raumthermostat DRT 1
DRT 1 Room Thermostat
Bedienungsanleitung
Operating Instructions
Inhaltsverzeichnis
1. Allgemeines....................................2
2. Wichtige Hinweise vorab................2
3. Kodierung.......................................2
4. Inbetriebnahme ..............................2
5. Anzeigen ........................................3
6. Garantie..........................................3
7. Technische Daten ..........................4
15. Anschlussbeisp. / Conn. Example..8
Table of Contents
8. General Information ....................... 5
9. Important Notes in Advance........... 5
10. Coding............................................ 5
11. Putting into Service........................ 5
12. Indicators ....................................... 6
13. Guarantee...................................... 6
14. Technical Data............................... 7
15. Anschlussbeisp. / Conn. Example . 8

23931226/2009.06/C - Technische Änderungen vorbehalten!
Doepke
Deutsch
1- Inhaltsverzeichnis
Bedienungsanleitung
Raumthermostat DRT 1
1. Allgemeines
Der Raumthermostat DRT 1 ist eine Komponente des Dupline Installationssystems und
erzeugt einen Schaltkanal für die Auswertung über den Dupline-Bus, z.B. zum Schalten
von Heizkörperstellventilen.
Der Thermostat generiert den Schaltkanal in Abhängigkeit der, am Handrad eingestell-
ten, Soll-Temperatur und der Raumtemperatur: liegt die Raumtemperatur unter der ein-
gestellten, aktiviert der DRT 1 den Dupline-Kanal, andernfalls deaktiviert er ihn. Über
einen zusätzlichen Dupline-Kanal kann am DRT 1 zudem eine Nachtabsenkung von 4°C
vorgegeben werden. Die Dupline-Adresse des Schaltkanals ist frei konfigurierbar zwi-
schen A1 und P8, die Nachtabsenkung kann auf einer Adresse innerhalb der B-Gruppe
vorgegeben werden.
Der DRT 1 benötigt keine externe Spannungsversorgung, da er aus den Dupline-Signal-
leitern versorgt wird. Durch seine Bauform passt er in handelsübliche Unterputz-Dosen,
kann jedoch bei Verwendung des mitgelieferten Gehäuses auch aufputz montiert wer-
den.
2. Wichtige Hinweise vorab
Zum Schutz von Leben und Komponenten, beachten Sie bitte folgende Sicherheitshin-
weise:
• Die Installation darf nur von einer autorisierten Fachkraft vorgenommen werden.
• Die Dupline-Signalversorgung muss aus Quellen erfolgen, die den Anforderungen
für Schutzkleinspannung entsprechen, ebenso, wie die Installation diesen Anforde-
rungen genügen muss (siehe hierzu die VDE 0100, Teil 410 sowie die EN 50090-1-
1). Andere Spannungen an den Signaleingängen können, trotz umfangreicher
Schutzmaßnahmen im Gerät, zur Zerstörung des Gerätes und Gefährdung von
Menschen führen. Weitere Hinweise finden Sie in der Dupline Planungshilfe.
3. Kodierung
Die Kodierung erfolgt beim DRT 1 über Drehschalter - die Lage der Drehschalter ist
Kapitel 15 “Anschlussbeisp. / Conn. Example” auf Seite 8 dargestellt.
Die Adresse des Schaltkanals wird über die zwei nebeneinander liegenden Drehschalter
(A) zwischen A1 und P8 eingestellt.
Die Adresse des Nachtabsenkungsbefehls ist auf die Gruppe B fest kodiert; die Kanal-
nummer 1..8 lässt sich jedoch am dritten Drehschalter (B) wählen. Wird keine Nachtab-
senkung benötigt, muss der am Drehschalter eingestellte Kanal der B-Gruppe in der
Konfigurationssoftware ProLine unbelegt bleiben.
4. Inbetriebnahme
Der DRT eignet sich zur direkten Aufputzmontage an Wänden oder zum Einbau in einer
UP-Dose. Beim Anschluss ist das Schema auf Seite 8 zu beachten.

3931226/2009.06/C - Technische Änderungen vorbehalten! 3
Doepke
Deutsch
Alle anzuschließenden Leitungen müssen spannungsfrei sein. Verbindungen zwischen
dem Dupline-Signal und dem Erdpotenzial führen zu Störungen und sind nicht zulässig.
Auf die richtige Polarität des Dupline-Signals ist zu achten. Folgende Tabelle zeigt die
Anschlussbelegung:
5. Anzeigen
6. Garantie
Für fachgerecht montierte, unveränderte Geräte gewähren wir ab Kauf durch den End-
verbraucher die gesetzliche Gewährleistungsfrist. Die Garantie bezieht sich nicht auf
Transportschäden sowie Schäden, die durch Kurzschluss oder Überlastung entstanden
sind. Bei Fertigungs- und Materialfehlern, die innerhalb der Gewährleistungsfrist erkannt
werden, leistet unser Werk kostenlosen Ersatz.
Klemme Beschreibung Klemme Beschreibung
1 Dupline Signalleiter + (Dupline+) 2 Dupline Signalleiter - (Dupline-)
Anzeige Beschreibung
Rote LED Schaltkanal (Heizbefehl):
Aus: Temperatur überschritten / An: Temperatur unterschritten

43931226/2009.06/C - Technische Änderungen vorbehalten!
Doepke
Deutsch
7. Technische Daten Min. Typ. Max.
Dupline Stromaufnahme 2,5 mA
Eingangskanäle 1 Schaltkanal für z.B. Stellventile
Ausgangskanäle 1 Steuerkanal für Nachtabsenkung
Temperatursteuerung
Messbereich +14°C +28°C
Hysterese -0,25°C +0,25°C
Nachtabsenkung -4°C (auf Adressgruppe B)
Betriebsspannung
Nennbetriebsspannung nicht erforderlich (aus Dupline-Signalleiter)
Anschlüsse Art Bügelklemme
Klemmbereich 0,4 mm 2,5 mm²
Gehäuse Art Gehäuse für AP- und UP-Montage
Maße 84 x 84 x 34 (B x H x T in mm)
Material ABS, weiß
Allg. technische Daten
Betriebstemperatur -30°C +60°C
Schutzart / Normen IP20
Bestellnummer, -bezeichnung 09 501 171, DRT 1
Sollten Sie Fragen zu diesem Produkt oder zum Dupline-System haben, wenden Sie
sich bitte an:
Doepke
Schaltgeräte GmbH & Co. KG
Stellmacherstraße 11
D-26506 Norden, Germany
Tel.: +49 (0) 4931/1806-0
Fax: +49 (0) 4931/1806-101
E-mail:
Internet: info@doepke.de
http://www.doepke.de

3931226/2009.06/C - The right to make technical changes reserved! 5
Doepke
English
1- Table of Contents
Operating Instructions
DRT 1 Room Thermostat
8. General Information
The DRT 1 room thermostat is a component of the Dupline installation system and gen-
erates a switching channel for evaluation via the Dupline bus, e.g. for regulating radiator
control valves.
The thermostat generates the switching channel according to the desired temperature
set at the valve and the actual room temperature. If the room temperature is below the
set value, the DRT 1 will activate the Dupline channel or, conversely, deactivate it. Via an
additional Dupline channel the DRT 1 can also be preprogrammed for a 4ºC lowering at
night-time. The Dupline address is freely selectable between A1 and P8, the night-time
reduction can be preset at an address within the B-group.
The DRT 1 requires no external power source as it is supplied by the Dupline signal. Al-
though its compact design makes it suitable for installation in flush-mounted socket box-
es, it may also be surface-mounted by using the housing supplied.
9. Important Notes in Advance
In order to protect both life and components, please observe the following safety in-
structions:
• Installation may only be carried out by authorised, trained technicians.
• The Dupline signal supply has to be delivered by sources, which have to be installed
in accordance with theregulations governing protective low-voltage (see VDE 0100,
Part 410, or EN 50090-9-1) as well as the installation has to comply with these re-
quirements. Even if extensive protective measures have been implemented in the
device, other voltages at the signal inputs could result not only in the destruction of
the device, but also endanger people. For further information please refer to the Du-
pline Planning Aid.
10. Coding
For DRT 1, the coding is carried out by means of rotary switches - the position of the ro-
tary switches is illustrated in Chapter 15 “Anschlussbeisp. / Conn. Example” on page 8.
The address of the switching channel can be set between A1 and P8 via the two adjacent
rotary switches (A).
The address for the night-time reduction command is permanently encoded in the B-
group; the channel number 1...8 may, however, only be selected with the third rotary
switch (B). If no night-time reduction is required, the channel ofthe B-group set at the ro-
tary switch must remain unassigned in the ProLine configuration software.
11. Putting into Service
The DRT is suitable for direct surface mounting on walls or for installation in flush-moun-
ted socket boxes. Follow the connection diagram on page 8 when installing.
All lines to be connected must be dead. Connections between the Dupline signal and

63931226/2009.06/C - The right to make technical changes reserved!
Doepke
English
earth potential will causemalfunctions and are not permissible. Check that the polarityof
the Dupline signal is correct.
The following table illustrates the connection configuration:
12. Indicators
13. Guarantee
All professionally installed, unaltered devices are covered by warranty during the statu-
tory guarantee period from the day of purchase by the end user. The guarantee is not ap-
plicable to damage incurred during transport or caused by short-circuit or overloading. In
the event of defects in workmanship or material, which are discovered within the guar-
antee period, the company will provide a replacement free of charge.
Pin Description Pin Description
1 Dupline signal conductor+
(Dupline+) 2 Dupline signal conductor-
(Dupline-)
Indicator Description
Red LED Switching channel (heating command):
Off - Temperature exceeded / On - Temperature too low

3931226/2009.06/C - The right to make technical changes reserved! 7
Doepke
English
14. Technical Data Min. Typ. Max.
Dupline Current input 2.5 mA
Input channels 1 switching channel for e.g. control valves
Output channels 1 control channel for night-time reduction
Temperature sensor
Measuring range +14°C +28°C
Hysteresis -0.25°C +0.25°C
Night-time reduction -4°C (at address group „B“)
Operating Voltage
Rated operating voltage Not required (supplied by Dupline signal line)
Terminals Type Clevis terminal
Contact area 0.4 mm 2.5 mm²
Housing Type Housing for flush- and surface-mounting
Dimensions 84 x 84 x 34 (W x H x D in mm)
Material ABS, white
General technical data
Ambient temperature -30°C +60°C
Encl. protection type /
standards IP20
Order number, description 09 501 171, DRT 1
In case of queries concerning this product or the Dupline system please contact:
Doepke
Schaltgeräte GmbH & Co. KG
Stellmacherstraße 11
D-26506 Norden, Germany
Tel.: +49 (0) 4931/1806-0
Fax: +49 (0) 4931/1806-101
E-mail:
Internet: [email protected]
http://www.doepke.de

83931226/2009.06/C - The right to make technical changes reserved!
Doepke
Zeichnungen / Drawings
15. Anschlussbeisp. / Conn. Example
Dupline +
Dupline -
12
3931226_1A
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
1
.
2
.
3
.
4
.
5
.
6
.
7
.
8
1
.
2
.
3
.
4
.
5
.
6
.
7
.
8
Adresseinstellung Nachtabsenkung (B)
84,0
84,0
3931226_2A
46,0
55,8
4,6
55,8
18,0
Einbautiefe
19,0
Aufputz-Rahmen
84,0
14
16
18
20 22
24
26
28
Adresseinstellung Schaltkanal (A)
Address setting night time reduction (B)
Address setting switching channel (A)
Table of contents
Languages:
Other Doepke Thermostat manuals
Popular Thermostat manuals by other brands

Honeywell
Honeywell TB7200 Series Integration manual

Crestron
Crestron infiNET EX CHV-TSTATEX-FCU quick start guide

Hunter
Hunter 44127 owner's manual

Lennox
Lennox PCUS user manual

Carrier
Carrier PROGRAMMABLE THERMOSTAT Homeowner's guide

White Rodgers
White Rodgers 7904 Installation and operation instructions