DOSPEL luna 200 User manual

snapchat: dospel.com
www.dospel.com
twitter.com/dospel_com
facebook.com/Dospel.Wentylacja
Below documentation shall be kept by user!
In case of not following the conditions of this document, the warranty expires.
MAINTENANCE MANUAL
WARRANTY CARD
AIR HANDLING UNIT
luna 200
rew. 2.02.2018
EN

1. GENERAL INFORMATION......................................
1.1. Purpose......................................................
1.2. Technical specification....................................
2. ASSEMBLY.......................................................
2.1. Required exploitation conditions.........................
2.2. Assembly of siphon out condensate.....................
2.3. Connecting to power grid.................................
3. STARTING THE UNIT..........................................
3.1. General remarks............................................
3.2. Starting the unit............................................
3.3. Summer mode.............................................
3.4. Exploitation recommendation..........................
3.5. Controller maintenance manual........................
4.WARRANTY.....................................................
3
3
3
5
5
6
7
9
9
9
10
11
12
12
luna 200
EN

1. BASIC INFORMATION
1.1 Purpose
Luna 200 air handling unit is designed to assure air exchange in residential buildings.
The unit's puprose it to supply fresh air from the outside and dispose used air from
the rooms with simultaneous recovery of thermal energy. As standard, the unit
is equipped with with bypass which can be switched on without opening the casing.
1.2 Technical data
Chart 1. Technical specification
148 [mm]
1108 [mm] x 564 [mm] x 494 [mm]
Dimension
Connection diameter
Air flow (100Pa)
Disposal compression
Max. power consumption
Heat recovery efficiency
Power supply voltage
Power / Motor supply voltage
Motor rotational speed
Type of motor's bearing Roller
Acoustic pressure
Insulation class
International Protection Rating
Weight
LUNA 200
3
200 [m /h]
0-350 [Pa]
maks. 140 [W]
do 95%
230 VAC/50Hz
2x68[W] / 230 [VAC]
2400 [obr./min]
51 [dB]
II
IP44
20 [kg]
luna 200
EN

WARNING!
Luna 200 should be lifted by holding the casing. It is forbidden to lift
by holding the connectors. It may result in leakage and damage to the
device.
Fig.1. Nominal dimensions LUNA 200
1108
564
459,8
171,4
Ø148
494
450
870
Fig. 2. Flow efficiency characteristics LUNA 200
3
Airlfow [m /h]
Pressure [Pa]
50
0
100
150
250
200
300
350
400
0 100 200 300 400 500
luna 200
EN

2. Assembly
2.1. Required exploitation conditions
The unit and ducts should be assembled in rooms with temperature above 5°C and heat-
separated form surroundings.
Not following above conditions will cause liquefaction of condensate and cumulate
it inside and outside of the unit which may cause dampness in the room or damage
to the unit.
WARNING!
1. Ventilation installation and other belonging elements must be in accordance with
Polish Norms referring to ventilation in residential buildings.
2. The unit is not destined for drying the unseasoned houses.
3. In case of damage to elements arising from not following the above instructions,
they will be not repaired under warranty.
4. Due to design reasons there is a possibility of mixing the air inside the unit with
amount not exceeding 2%.
luna 200
EN

2. Assembly of condensation dreinage system
Steam condensation can be observed during unit's work. It is completely normal
and it does not mean abnormality in working. In order to siphon out condensate the unit
is equipped with stub pipe placed on the right side. It is essential to properly connect
the pipe siphoning out the condensate.
Exemplary way of conneting the pipe is shown below. The pipe should have adequate
diameter to the stub-pipe (16 mm). It shoud be bent into letter "U" and suffused
with water until stabilizing its level. Shipon should be palced around 120 mm from the
unit and radius should not be less than R=30 mm. Given measures should be taken
as minimal. Unit is sold with siphon and pipe,
Fig.3. Connection of ventilation ducts
To launcher
From air inlet
From rooms
To rooms
luna 200
EN

2.5. Conneting to power grid
Unit should be connected directly to one phase outlet 230V/50Hz in the most accessible place.
2 2
Unit comes with 2 m power cord and connection box to which 5x1mm or 5x1,5mm power cord
and 3-gear controller shoud be connected. Power cord should be properly led
to connection box with (in accordance with schemes). Such installation should be secured with
proper fuse (overcurrent braker, etc.). All electrical matter should be perfomed by authorized
person.
WARNING!
Prior to maintenance work or repairs, unit should be disconnected from the power outlet
by pulling the plug out.
In case of damaging the wire, replacement can only be performed by authorized person.
rev: 22.01.18
Fig. 4. Connection boxFig. 4. Place of pipe
Siphon
luna 200
EN

Manner of connecting 3 gear controller
Power cord
2
3x1,5mm
Control - power supplying cord
2
5x1mm
Switchboard
supplying the building
Main power supply
230V AC 50Hz
Luna 200
5x0,5
5x0,5
5x1
OFF
HI LO
MED
DOSPEL
L
L
LL
LL
LL
LL
N
N
N
N
PE
PE
PE
PE
C
C
LM
LM
LM
LM
LH
LH
LH
LH
NPE
LO M H
OFF
M
exhaust
~230,
max. 70W
M
intake
~230,
max. 70W
3 gear controller
WARNING!!!
Supply voltage VAC, 50Hz
(the current protection should be selected based on the device's power)
3 gear controller
connection box
connection
box
luna 200
EN

3. STARTING THE UNIT
3.1. General remarks
1.Prior to starting the unit read the manual.
2.Check if there is no objects present in the ducts which may damage the unit
or endanger health.
3.It is recommended to test the working mode of the unit prior to connecting
it to ventilation.
WARNING!
While testing the installation follow the safety rules in order to avoid improper
direction of airflow, i.e. open chimney duct or other devices with open fire towards
room.
3.2. Starting the unit
1.Read the manual
2.See if there is no damage
3.Place unit in wanted place
4.Connect 3 gear controller
5.Connect connection cord to connection box (in accordance with schemes) then
to 3 gear controller
6.With 3x1,5 mm2 (secured by fuse) 230v/50Hz connect to 3 gear controller.
7.Turn on the unit switching to wanted gear (LO, MED, HI)
8.Turn off the unit (OFF)
Once all above is performed, the unit can be used.
Usage and maintenance
When proprely installed, unit does not require special maintanance work during use. It is
recommended to control filters at least once per quarter and change filters. It is
essential for keeping unit's high efficiency. When high intake air purity of is required, it is
recommended to use external duct filter.
rev: 22.01.18
luna 200
EN

In order to replace filters, remove securing screws, take off one part of casing, remove
used filters and replace with new ones. After replacing filters timer needs to be reset.
WARNING!!!
Unit should not work without filters. It is only recommended for testing,
but no longer than 10 minutes.
3.3. Summer mode
Luna 200 is equipped with baypass which is activated by lever placed on the casing.
The moment when bypass is opened, heat exchange does not take place. To open bypass
turn lever by 90 degree counterclockwise. Bypass helps to cool ventilated rooms with
use of i.e GWC.
Fig.5. Manner of replacing filters
Exchanger Filters
Casing
luna 200
EN

3.4. Exploitation recommendation
Necessity of filter replacement is signaled by countdown timer via visual warning. The
filter cartridge made of polyester fabrics cannot be cleaned and must be replaced with a
new one if necessary. New filters should be ordered from the device supplier.
The time indicator of contamination of the filter counts down the time remaining until
the next filter change.
To start the countdown for the first time, press and hold the RESET button for 3 seconds.
The need to replace the filter is signaled by audible and visual signals - after the
countdown is over, the digits 00 00 00 are displayed on the screen.
The signal must be reset by pressing the RESET button.
The device is equipped with a magnet and CR1130 battery.
Fan check-up
Despite of required maintenance work (cleaninf/filer exchange) dust and grase can
be slowly embed inside the fan, which can decrese its effecitivity. Fan can be cleand with
cloth or soft brush. Keep caution while cleaning not to damage fan's impeller.
Do not clean with water, do not put in water! Solid dirt can be cleaned with denaturated
alcohol. Prior to placing back - dry well.
Control of condensate's stub-pipe
Stub-pipe can become dirty overtime by fixed particles brought by air.
It is recommended to periodically check (by flushing with water) stub-pipe patency.
Clean if needed.
Cleaning intake and exhaust
Unit is a part of a whole system. the system supplies fresh air and launches used air
through ducts and intake/exhaust diffusers. Air diffusers are installed in ceilings, walls,
bathrooms and rooms. They should be periodically cleaned with warm water and soap,
if needed. If they were dismounted for cleaning they should be put in the same places -
they cannot be changed.
Air inlet and launcher check-up
Pollution as leafs, insects, dust, etc.) can clog air inlet which causes air flow throttling.
Check and clean air inlet at least twice a year.
Duct check-up (every 5 years)
Dust and grease particles will pile up in duct despite of recommended maintenance
which can decrease effectivity of installation. Due to that fact, ducts should
be cleaned/exchanged when needed.
rev: 22.01.18
Fig.6. Summer bypass opened Fig.7. Summer bypass closed
luna 200
EN

Technical parameters
Nominal power supply voltage [V] 1~230 AC
2
3
86x86x40
40
IP 40
Nominal current [A]
Number of gears
Dimensions [mm]
Dimensions
860 90
860
56x47x19
Maximum surrounding
temp. [°C]
International Protection Rating
Symbol
OFF
LO
MED
HI
OFF
FIRST GEAR
SECOND GEAR
THIRD GEAR
3.5. Controller maintenance manual
Controller to one phase 3 gear motors
Possibility to connect random quantity of devices under
conditions of not exceeding maximum nominal current
for the controller (2A). Controller made out of white (RAL
9002) ABS. International Protection Rating: IP40.
Use
Used to turn on/off and switching fan's speed.
Construction
Controller is made out of ABS. Winder allows immediate
possibility of switching fan's speed.
Assembly
It can be assemblied in walls in installation box.
WARRANTY TERMS AND CONDITIONS
Territory
Dospel guarantees efficient work of the unit in accordance with maintenance conditions attached to this warranty. This warranty is valid only in territory
of Poland.
Warranty
Dospel guarantees repairs witin 2 years from date of purchase. Claims resulting from warranty are brought up with the day of purchase.
They expire with the end of warranty of a given product, counted from the day of purchase. Warranty obliges Dospel to remove failures caused
by manufacturer. Repairs are performed by qualified installation companies.
Exclusions
Warranty is not valid when one of the below is detected:
1. mechanical forces
2. pollution
3. alternations
4. changes in construction
5. activities linked with maintenance and cleaning the unit
6. accidents
7. natural disasters
8. actions of chemical agents
9. action of atmospheric agent (discoloration, etc)
10. improper storage
11. unauthorized repairs
12. transport company
13. improper installation of unit
14. improper exploitation of unit
15. faults resulting from using exploitation materials other than Dospel's
16. faults resulting from using sub-assemblies other than Dospel's
luna 200
EN

rev: 22.01.18
luna 200
Warranty excludes
1. Exploitation materials which become used over time (filters, gaskets, fuses, etc.)
2. Activities performed in accordance with guidelines from Maintenance Manual in terms of check-ups and normal exploitation
3. Losses caused by repair waiting period. It also refers to estate losses, i.e. direct and indirect losses
4. Installation of unit, etc.
Warranty also excludes all claims arisen from parameter selection by buyer or sub-contractor.
Warranty covers
1. Repair or free of charge exchange of components claimed by Dospel as faulty
2. Remove other faults of the unit
Term "repair" does not cover activities described in manuals (starting and exploitation) to which user is obliged to.
Warranty car is valid when
1. Was filled out correctly (stamp, signature and purchase date)
2. Is shown with invoice
Claim should be filled via phone or in written form to a company which performed installation. In other cases claim can be filled directly to distributor
or Dospel.
Claim must feature
1. Precise place when unit was used
2. Serial number
3. Type of fault, if possible symptoms of improper work
In case of filing a claim directly to Service Department, it has to state who performed first startup.
In case warranty card is lost, duplicates will not be outlayed.
Claimed prodct should
1. Be transported to specialistic, authorized service preffered by Dospel
2. Sent directly to Dospel main office
Replecement under warranty
1. Only when removing the fault is impossible or when removing the fauld is too expensive after Dospel evaluation
2. When product is repaired for the fourth time during warranty period due to the same production fault.
When specific unit is unavailable, a new one with similar parameters can be dispensed in exchange. After replecement the warranty period
is not extended! Warranty is not also exteneded during repair work on the unit.
Warranty costs:
1. Buyer bears transport costs to Dospel main office
2. Dospel bears repair costs
3. When claim is rejected, buyer bears diagnostic costs
Dospel provides warranty and after-warranty service. The manner of removing faults is decided by Dospel. In terms of warranty, Dospel decision
is the final one. In case of any disputable matters, they will be settled by court suitable to warrantor. Dospel may refrain from keeping the repair stage
when the processes occurring at Dospel will be disturbed by e.g, natural disasters with social unrest or other factors that may affect the time frame
of complaints or if the defect's availability within the warranty period cannot be removed. Dospel does not bear any liability resulting from possible
printing errors that may appear in this Warranty Card/Maintenance Manual. Dospel reserves the right to introduce changes considered to be useful
in relation to the manufactured products, without changing its basic characteristics in a significant way.
Wishing you satisfaction from expliotation
Dospel
Serial number
Date yr/mm/dd
Issued by
Installed by
EN

ABS w kolorze białym (RAL 9002). Stopień ochrony: IP40.
Jest stosowany w celu włączania/wyłączania oraz przełączania
prędkości wentylatorów, opierających się na wielobiegowych
przełączaniem prędkości wentylatora oraz wyłączeniem.
regulator wewnątrz ściany w puszce instalacyjnej.
200
85
F
A+
012-1480 Luna 200
Luna 200
-30
-67
-6
B
Dospel Sp. z o.o.
[dB(A)] 51
[ ]
3
m /h
[ ]W 90
%
Unit
[W/( ]
3
m /h)
Unitt
www.dospel.com
45
20
609
87
%
1
%
3
[m /s] 0,04
[Pa] 50
0,45
Luna 200
Cuperative heat
exchanger
RVU BVU
3-gear controller
Supplier
Device indentifier
Specific energy consumtion (SEC)
- average climate
Specific energy consumtion (SEC)
- cold climate
Specific energy consumtion (SEC)
- warm climate
SEC range
- average climate
SEC range
- cold climate
SEC range
- warm climate
Device type
Type of drive
Heat recovery system
Thermal efficiency
of heat recovery
Maximum flow rate
Power consumption
of fan drive
Sound power level (L )
wa
Internal leakage rate
Filter change warning signal
Website
Annual electricity consumption
2
per 100 m
Control factor (CTRL)
The annual heating saved
(cold climate)
The annual heating saved
(average climate)
Internal leakage rate
The annual heating saved
(warm climate)
Flow rate
Pressure difference rate
Specific power input (SPI)
[kWh primary
energy
/year]
[kWh primary
energy
/year]
[kWh primary
energy
/year]
[kWh/year]
Not more than 2
Not more than 2
Visual filter
change warning
signal
Product information according to Commission Regulation no 1253/2014 and Commission Regulation no 1254/2014
luna 200
EN

DOSPEL Sp. z o.o.
ul. Główna 188
42-280 Częstochowa
tel. +48 34 365 98 43
fax +48 34 360 97 00
e-mail: [email protected]
www.dospel.com
Dospel reserves the right to introduce any changes regarding its products
resulting from ongoing technical development. Dospel shall not be liable
for printing errors.
Table of contents
Other DOSPEL Air Handler manuals
Popular Air Handler manuals by other brands

ActronAir
ActronAir CAY500T Installation and commissioning guide

Dettson
Dettson Atmos MHD-18 owner's manual

Vents
Vents DVUT 500 HB user manual

Komfovent
Komfovent DOMEKT series installation manual

Ingersoll-Rand
Ingersoll-Rand TAMGB0A24V21DA Installer's guide

York International
York International N Series installation manual

Exhausto
Exhausto VEX300 Series Original instructions

ActronAir
ActronAir PCG153U Series Installation and commissioning guide

Vents
Vents VUT 800 WH user manual

Swegon
Swegon SILVER Series MANUAL FOR INSTALLATION, OPERATION AND MAINTENANCE

MrCool
MrCool U-match MDUI18060 owner's manual

Daikin
Daikin Altherma 3 H HT ECH2O Series Service manual