2.4 Target group
Only qualified and trained service engineers shall in-
stall the control.
Only qualified and trained electricians shall connect
and carry out the electrical maintenance.
Qualified and trained professionals have knowledge of
the general and specific safety and accident preven-
tion regulations, of the relevant regulations and stand-
ards, training in the use and maintenance of adequate
safety equipment, as well as the ability to recognize
hazards associated with their work.
2.5 Key to symbols
1. CONTENTS
1. Contents ................................................... 2
2. General instructions ................................. 2
3. Safety related regulations ........................ 3
4. Safety instructions .................................... 3
5. Initial Operation ........................................ 4
6. LED Codes ............................................. 14
7. Run mode / error codes ......................... 15
8. Electronic counter and last 10 errors ..... 17
9. PCB-overview ........................................ 18
10. Connections ........................................... 19
11. Technical Data ....................................... 22
12. Declaration of conformity ....................... 23
2 GENERAL INSTRUCTIONS
2.1 Original operating instructions
• Copyright protection: any reproduction is permitted
only with permission of Tornado Antriebstechnik
GmbH.
• Changes in the interest of technical progress are
reserved.
• All dimensions are in millimetres, drawings are not
necessarily to scale.
2.2 Using the equipment for its intended purpose
The control V7E is designed only for controlling gates
and doors with mechanical or digital end position sys-
tems.
For other applications, the controller must be consult-
ed with the manufacturer.
2.3 Warranty
The function and safety of the equipment is only guar-
anteed if the warning and safety instructions included
in these operating instructions are adhered to.
The manufacturer is not liable for any personal injury
or damage to property that occurs as a result of the
warning and safety instructions being disregarded.
The CE declaration and warranty is voided by chang-
es such as unauthorized attachments, modifications or
rewiring goes out. Only original spare parts shall be
used.
These parts serve to maintain the quality and safety of
the machine. Changes are only permitted after consul-
tation with the manufacturer.
DANGER !
Safety notice indicating a danger that will directly result
in death or severe injury.
WARNING !
Safety notice indicating a danger that could result in
death or severe injury.
CAUTION !
Safety notice indicating a danger that could result in
slight or moderate injuries.
NOTICE !
Safety notice indicating a danger that could result in
damage to property or in irreparable damage to the
product
INFORMATION !
Reference to a check that needs to be carried out or to
separate documents that must be observed.

04/2022
-
Version 1 DoorTec Deutschland | www.doortec.online
3
Änderungen vorbehalten | Subject to Modifications
3. SAFETY-RELATED REGULATIONS
For connecting, programming and servicing, the fol-
lowing regulations must be observed (the list is not
exhaustive).
• EN 12453 (Safety in use of power operated doors -
Requirements)
• EN 12445 (Safety in use of power operated doors -
Test methods)
• EN 12978 ((Industrial commercial and garage doors
and gates - safety devices for power operated doors
- Requirements and test methods)
References to additional, additionally accepted stand-
ards must also be observed, such as:
• EN 60204-1 (Safety of machinery, electrical equip-
ment of machines, part 1: general requirements)
• EN 12100-1 (Safety of machinery, basic concepts,
general principles for design. Basic terminology,
methodology)
• EN 60335-1 (Household and similar electrical appli-
ances - Safety)
• EN 60335-2-103 (Particular requirements for drives
for gates, doors and windows)
• Committee for Workplaces (ASTA)
• Workplace regulation ASR A1.7 (“Doors and gates“)
4. SAFETY INSTRUCTIONS
DANGER !
Failure to comply with the documentation could result in
life-threatening danger!
Be sure to follow all the safety instructions in this docu-
ment.
DANGER !
Life-threatening danger due to electric shock!
• It is vital that you disconnect the operator system
from the power supply before commencing cabling
work. Take measures to ensure that the power sup-
ply remains disconnected for the duration of the
work.
NOTICE !
For a three-phase current, a clockwise rotating field is
required.
WARNING !
• Ensure that children can not play with the door con-
trols or the hand transmitter.
• Before setting the door in motion, make sure that no
persons or objects are within the danger zone of the
door.
• Check all the existing emergency command devices.
• Pay attention to potential crushing and shearing
zones in the door system.
• Never touch a running door, the guide rail or any
moving parts.
INFORMATION !
For a permanent connection, an all-pole main switch
must be used.
WARNING !
• The control and the drive must be installed with its
intended covers and guards. It is important to en-
sure the correct fit of any seals and couplings are
tightened correctly.
• The mains voltage must correspond to the voltage
stated on the type plate.
• The mains voltage must be the same as the voltage
of the drive.
• For a three-phase connection, only 3-way automatic
circuit breakers (10A) may be used.
• Before switching on the controls for the first time, a
check must be carried out after completing the wir-
ing to ensure that all the motor connections at the
motor and at the controls are securely fixed.
• SAFETY RELAYS:
• If the control unit is a version without three safety
relays, the door manufacturer/installer is responsi-
ble of preventing any dangerous situation if one of
the contactors is welded.

4
DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
1. Select programming mode
To enter programming mode: Change DIL switch 1
(S4) to ON position.
Back to normal mode: Change DIL switch 1 (S4) to
OFF position.
2. Navigating the table
STOP push-button is used to navigate between pa-
rameter number and parameter value.
OPEN and CLOSE push-buttons is used to select pa-
rameter number or change parameter value.
Active digits will be flashing.
Some of the parameters have an extra step when
pressing the stop push-button. For example when the
door needs to run in programming stage. Display will
show ”RUN”.
3. Parameter explanation
5. INITIAL OPERATION
Before initial operation and at regular intervals of no
more than one year, power-operated windows, doors
and gates must be inspected by a qualified person
(whereby written inspection records must be kept).
After setting the system in operation, the operator of
the door system, or the operator’s representatives,
must be instructed in the operation of the system.
Make sure before installation that the direction of rota-
tion of the gear motor is correct and that all protective
devices are functioning.
5.1 Electrical installation
5.2 HOW TO program
The door will always run in hold-to-run mode when
programming. Program the control by opening the en-
closure. Find OPEN - CLOSE - STOP push-buttons
and a 4 pole DIL switch on the PCB (S4).
NOTICE !
To avoid damaging the device, the following must be
ensured:
• The cable types and cross-sections are to be chosen
according to the regulations.
• The rated currents and the connection type must
match those on the motor type plate.
• The on site fuse must comply with the specifications.
DANGER !
Life-threatening danger due to electric shock!
It is vital that you disconnect the operator system from
the power supply before commencing cabling work.
Take measures to ensure that the power supply re-
mains disconnected for the duration of the work.
NOTICE !
• The main power supply must be in the range of max.
+/- 10% of the control unit’s mains supply.
• Be sure not to overload the gear motor in accord-
ance with the electrical data on the type plate.
• Temperature control is necessary when using the
control outside the temperature range -10 - + 50°C.
• The control unit must not be used in environments
with risk of condensation.
Parameter value.
Parameter number.

04/2022
-
Version 1
DoorTec Deutschland | www.doortec.online
5
Änderungen vorbehalten | Subject to Modifications
5.3 Parameter
Parameter overview
Parameter Description Page
Operation mode 7
Reaction – Failure on photo or Safety edge 7
Selection of limits 7
Learning - Electronic Limit Open 8
Fine Tuning of electronic Limit Open 8
Learning - Electronic limit CLOSE 8
Fine tuning of electronic limit CLOSE 9
½ Open settings 9
Auto close ½ open 10
Safety edge selection 10
After run 10
Extra safety edge 10
Wire tightening 11
Photo settings 11

6
DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
Parameter Description Page
Auto close 11
Car wash function 11
Forced closing 12
GO function (Step) 12
Interlock function ON/OFF 12
Run time control 12
Reverse time safety edge 12
Reserve time photo 13
Service counter setup 13
Service count reaction 13
Delay time indication of missing encoder position 13
Option relay K3 13

04/2022
-
Version 1
DoorTec Deutschland | www.doortec.online
7
Änderungen vorbehalten | Subject to Modifications
The factory setting is shown in bold letters.
Parameter Value
Operation mode
01 = Hold to run OPEN
Hold to run CLOSE (bridge in terminal X3 / 23-24 when there is
no safety edge)
02 = Impulse OPEN
Hold to run CLOSE (bridge in terminal X3 / 23-24 when there is
no safety edge)
03 = Impulse OPEN
Impulse CLOSE
04 = Impulse OPEN
Impulse CLOSE
0,5 sec reverse by stop on force control in opening direction.
Notice: The door will always run in hold-to-run mode when programming.
Reaction – Failure on photo or
Safety edge
00 = Hold to run operation not possible when failure on photo or safety
edge.
The door cannot close when there is an error on photo or safety edge.
By a special code the door can close one time in hold to run mode.
Press and hold STOP when pressing 222111
(2 = DOWN push button and 1 = OP push button).
01 = Hold to run possible when failure on photo or safety edge.
Selection of Limits
00 = Mechanical Limits
01 = Dalmatic right turning
02 = Dalmatic left turning
03 = Feig TST PD right turning
04 = Feig TST PD left turning
05 = Kostal– right turning
06 = Kostal– left turning
Arrow = door opening
After changing to Kostal encoder a new power up is needed to start communi-
cation.

8
DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
Parameter Value
Learning - Electronic
limit OPEN
Press STOP 2 times - Display shows ‚run‘.
Run the door to open position. (By pressing OPEN or DOWN).
Press the STOP push-button to confirm open limit.
(The display will show open limit symbol about 2 sec. and the display will auto-
matic switch back to active parameter number).
Notice:
• ½ OPEN limit cannot be active during programming (parameter 16).
• Photo in the door frame (parameter 31) cannot be active during learning of
limits.
• When relearning limits parameter 41(force control) and 51(run time) will be
reset to factory setting.
Fine tuning of electronic
limit OPEN
Press STOP push-button until the display parameter value is active.
Fine tune OPEN limit 6-9 more open, 1-4 less open. Press OPEN or CLOSE
push-button to change value.
If the value is changed:
Press STOP push-button (Display shows ”RUN”)
Test the fine tuning by running the door up and down.
Press the STOP push-button to save and return to parameter value.
(adjustment range is maximum +/- 0.8% of the door run range)
Pressing STOP without a value change = return to parameter number.
Learning - Electronic limit
CLOSE
Press STOP 2 times - Display shows ‚run‘.
Run the door to close position (by pressing OPEN or DOWN). Normally 3-5 cm
from the floor.
Press the STOP push-button to confirm close limit.
(The display will show close limit symbol about 2 sec. and the display will auto-
matic switch back to active parameter number)
Notice:
• ½ OPEN limit cannot be active during programming (parameter 16).
• Photo in the door frame (parameter 31) cannot be active during learning of
limits.
• When relearning limits parameter 41 (force control) and 51 (run time) will be
reset to factory setting.
• The safety edge is not active during programming.

04/2022
-
Version 1
DoorTec Deutschland | www.doortec.online
9
Änderungen vorbehalten | Subject to Modifications
Parameter Value
Fine tuning of electronic
limit CLOSE
Press STOP push-button until the display parameter value is active.
Fine tune OPEN limit 6-9 more open, 1-4 less open. Press OPEN or CLOSE
push-button to change value.
If the value is changed:
Press STOP push-button (Display shows ”RUN”)
Test the fine tuning by running the door up and down.
Press the STOP push-button to save and return to parameter value
(adjustment range is maximum +/- 0.8% of the door run range)
Pressing STOP without a value change = return to parameter number
½ Open settings
00 = No ½ open active.
Mechanical limit switches: (Value 00 in parameter 11)
01 = ½ open stop active.
Position controlled by mechanical micro switch (NC type)
in terminal 15 + 16.
Short-circuit terminal 15+16 parallel connected by mechanical
switch to ON/OFF this function.
Electronic limits: (Value > 00 selected in parameter 11)
ON/OFF controlled by switch in terminal X3,15+16
02 ½ open stop active. Electronic limit on 50 % open position.
03 ½ open stop active. Electronic limit on 55 % open position.
04 ½ open stop active. Electronic limit on 60 % open position.
05 ½ open stop active. Electronic limit on 65 % open position.
06 ½ open stop active. Electronic limit on 70 % open position.
07 ½ open stop active. Electronic limit on 75 % open position
½ OPEN command by a push button NO in terminal X3,15 + 16
08 ½ open stop active. Electronic limit on 50 % open position.
09 ½ open stop active. Electronic limit on 55 % open position.
10 ½ open stop active. Electronic limit on 60 % open position.
11 ½ open stop active. Electronic limit on 65 % open position.
12 ½ open stop active. Electronic limit on 70 % open position.
13 ½ open stop active. Electronic limit on 75 % open position

10 D DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
Parameter Value
Auto close ½ open
00 =
No auto close from ½ open limit
01 =
Auto close from ½ open limit
Notice:
Auto close must be activated in parameter 32.
Safety edge selection
Note that actual edge must be connected but not activated before this setup. If
the controller has observed a wrong edge select, the display will show ERR.
Please note that nothing must be connected to X3 terminal 23-24 when param-
eter value 03 have been chosen.
01 = NCC edge or DW switch AU contact
02 = 8k2 electrical edge
03 = optical edge (Type FRABA)
04 = DW switch (AG contact)
05 = Wireless safety edge with test function (X20)
After run
00 = No after run
> 00 After run active (after run time 0.01 – 0.50 sec.).
Monitoring of PNE/DW air switch safety edge is automatically selected when
after run is active. When the door reaches the close limit switch, the door will
continue to close until PNE/DW air switch activate or until the after run time
exceeds.
Notice:
Can be used to prevent that the door reverses when it reaches the floor before
the close limit gets activated – for instance if there is dirt in the door opening or
if the wires are getting longer.
Extra safety edge
(X20 – terminal 3-4)
00 = No extra safety edge
01 = Extra safety edge works parallel with primary safety edge
02 = Extra safety edge stops door in opening direction
03 = Stop and short reversal in opening direction
05 = Slack rope switch
06 = Slack rope switch (NC)

04/2022
-
Version 1 DoorTec Deutschland | www.doortec.online
11
Änderungen vorbehalten | Subject to Modifications
Parameter Value
Wire tightening
00 = No wire tighten function
01 = Wire tighten 5 ms
02 = Wire tighten 10 ms
03 = Wire tighten 20 ms
04 = Wire tighten 30 ms
Used to prevent that the wire is getting loose when the door is closed. Works
as a small pull back time when the door stops on close limit.
Photo settings
Photo 1: Plug in photo module mounted in X12
Photo 2: External photo mounted in screw terminals X3
00 = No Photo safety connected
01 = Photo 1 connected
02 = Photo 2 connected
03 = Photo 1 and 2 connected
Parameter 31:04 – 31:07 (only possible with electronic limits)
04 = Photo 1 connected and mounted in the door frame (*)
05 = Photo 2 connected and mounted in the door frame
06 = Photo 1 und 2 connected and Photo 1 mounted in the door frame (*)
07 = Photo 1 und 2 connected and Photo 2 mounted in the door frame (*)
(*) After selecting the right parameter value run mode is available by pressing
stop. Location of photo will now be learned by running from close to open posi-
tion. The door will stop when the photo is no longer blocked and the control
unit will change back to parameter number automatically.
Auto close
Note that impulse close must be selected in parameter 1!
00 = No auto closing
xx = Seconds 1 – 990 (after 99 the changing will be in x10 of seconds and
the value is flashing quickly - e.g. 18 is 180 seconds)
Interlock:
If stop or emergency stop is activated more than 5 sec. with door in open posi-
tion. The auto close is interlocked to prevent closing. Reset of interlock by
CLOSE push-button or ”GO FUNCTION” close.
It is only possible to use automatic closing after selecting photo settings in pa-
rameter 31, which activates additional security provided by the light-sensitive
sensors. Automatic closing without additional safety by light-sensitive sensors:
bypass terminals 20-22 on terminal strip X3 and select parameter 31:02.
Car wash function
(Only available if auto close select is on)
00 = No car wash function
xx = Photo active time in 0.1 sec. Units (e. g. 15 = 1.5 sec.)
(Adjustable 1 – 30 units = 0.1 sec. to 3.0 sec)
Count down of auto closing time starts, only if photo has been activated more
than ”photo active time”. Door shall be complete closed before start of a new
cycle.

12
DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
Parameter Value
Forced closing
Only when car wash function is selected (parameter 33), closing even though
photo has not been activated
00 =
No forced closing
01 =
Forced closing after 2 min.
02 =
Forced closing after 5 min.
03 =
Forced closing after 10 min.
04 =
Forced closing after 20 min.
GO function (Step)
Only when photo is selected (parameter 31), Impulse function used for step-by-
step operation
00 Normal go function (Closing is only possible from open limit)
01 Special go function (stop command possible in opening direction)
Automatic closing is normally only allowed if additional photo safety is used
(parameter 31). Auto close without additional photo safety requires a connect-
ing bridge between X3, 20-22 (parameter 31:02).
Interlock function
Only when auto close is selected (parameter 32)
00 = Interlock function OFF
01 = Interlock function ON
Run time control
00 = No run time control
01 = run time 20 sec.
02 = run time 40 sec.
03 = Automatic run time.
”RUN” position is now available by pressing STOP.
Run the door from closed to open position without any stop
(keep press OPEN).
When run time is learned (by open limit) the ”RUN” will stop flashing
and the display will automatic switch back to active parameter number).
Run time is learned time + 12.5%. Below 10 seconds learned time,
fixed 1 second is added.
Notice: Both limits must be set before selecting automatic run time.
Reverse time safety edge
xx = Reverse time of safety edge in 1/100 seconds.
01 = 0,01 Sec
Range: 0.00 – 0.99 sec
(when using a single phase motor the parameter is to be set to 50 to avoid
problems with too fast reversing time)
(If 00 is selected the reverse time is set to minimum 0.004 sec.)

04/2022
-
Version 1
DoorTec Deutschland | www.doortec.online
13
Änderungen vorbehalten | Subject to Modifications
Remember to switch DIL switch 4 back to OFF posi-
tion
5.4 Reset to factory settings
Reset to factory settings by changing DIP switch 4
(S4) to ON position and push STOP and OPEN at the
same time within 2 seconds. The display will flash with
”FAC” and program version number will be shown.
Parameter Value
Reverse time photo
xx = Reverse time of Photo in 1/100 seconds.
30 = 0.30 seconds
Range 0.05 – 0.99 sec.
This reverse time is also used as force reversing time.
(when using a single phase motor the parameter is to be set to 50 to avoid
problems with too fast reversing time)
Service counter setup
00 = No Service countdown
01 = 15 open cycles before service (for test only)
02 = 5000 open cycles before service
03 = 10000 open cycles before service
04 = 20000 open cycles before service
Reset for new countdown or selecting value:
• Press STOP to select parameter value.
• Press OPEN or CLOSE to select value.
• Press STOP again minimum 2 sec.
• CLR is shown 2 sec. in display to confirm new countdown.
Service count reaction
00 = Display shows E:04
01 = Switch to hold-to-run control and display shows E:04
If LED pad is mounted: Service LED will light when service countdown reach 0.
Delay time indication of miss-
ing encoder position
00 = 1 Sec.
01 = 2 Sec.
02 = 4 Sec.
Display shows E:09 after pre-set operation time without change of encoder
position. Failure can be reset by hold-to-run steps to find both end limits or re-
learning of limits.
03 = 4 Sec.
(After operation without change of encoder position the door will stop
and error code E:09 will be automatically reset)
Notice: No limit monitoring by selecting value 03.
Option relays K3
00 = K3 active when door is running
01 = K3 active when the door is closed
02 = K3 active when the door is open
Mechanical relay and terminals X17 needs to be mounted on the PCB on posi-
tion K3.

14
DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
6. LED CODES (D15)
Used when electronic limits is selected :
Flashes on error
LED Error Explanation Solving error
1No answer from encoder Check connections.
Maybe RS485 A and B are interchanged.
2Limits not learned Learn limits.
3Motor running unintended
Service needed. Fatal error. Move the door man-
ual to middle position without power. Change
from normal mode to programming mode on DIL
switch no. 1. This will clear the SER error. If the
door is running again in 1 sec. without command
when power is on then the PCB is defect.
4Calculation error
Check that parameter 11 value is correct select-
ed. (Left/right turning select).
Possible user error – both limits are the same.
Encoder error.
5Not in use
6Not in use
7Kostal encoder –wrong selection of left/
right turning
Re-learn limits.
Check that parameter 11 value is correct select-
ed (Left/right turning select) or re-learn limits.
8Kostal encoder – Failure operating
voltage
Check connection and supply voltage.
Change encoder.
9EEPROM failure on IC4 by power up Try factory clear or change controller.

04/2022
-
Version 1
DoorTec Deutschland | www.doortec.online
15
Änderungen vorbehalten | Subject to Modifications
7. RUN MODE
The display will in run mode show status of limits, some inputs or error codes if they occurs.
When power up the software version is showed shortly.
Display Description Remark
Nothing active
4 chairs symbol Door is stopped between limits and no errors are found.
Open limit active Normal symbol as an aid in programming and troubleshooting.
Close limit active Normal symbol as an aid in programming and troubleshooting.
1/2 open limit active Normal symbol as an aid in programming and troubleshooting.
STOP active Normal symbol as an aid in programming and troubleshooting.
OPEN push-button
active
Normal symbol as an aid in programming and troubleshooting.
Activation of loop detector will also show this symbol.
CLOSE push-button
active Normal symbol as an aid in programming and troubleshooting.
GO function active
Normal symbol as an aid in programming and troubleshooting.
(Note that GO function is only possible to use when photo is
installed)
Photo 1 active Normal symbol as an aid in programming and troubleshooting.
Photo 1 is internal photo amplifier mounted in X12.
Photo 2 active Normal symbol as an aid in programming and troubleshooting.
Photo 2 is external photo cells mounted in the screw terminals.
Safety Edge active Normal symbol as an aid in programming and troubleshooting.
Door running up Normal symbol as an aid in programming and troubleshooting.
Door running down Normal symbol as an aid in programming and troubleshooting.

16
DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
7.1 Error Codes
Display Description Remark
Edge monitoring Monitoring failure of safety edge if this function is activated. Check
or adjust safety edge.
Run time Door is stopped on run time control.
Service Service counter decremented to 0.
Reset for new countdown.
Photo Failure in photo circuit.
(Test cycle after last stop failed, Press stop to start new test)
Safety edge Failure in edge circuit.
(Test cycle after last stop failed, Press stop to start new test)
Encoder
Door started, but the position is not changing.
Door is stopped after delay time and E:09 failure is shown about 1
sec (see parameter 81).
Both limits shall be founded again by hold-to-run steps or both limits
must be relearned.
EEPROM EEPROM failure of powerup.
Try factory clear or change processor.

04/2022
-
Version 1
DoorTec Deutschland | www.doortec.online
17
Änderungen vorbehalten | Subject to Modifications
8. ELECTRONIC COUNTER AND LAST 10 ERRORS
To select counter or error history – Close the door and switch DIL switch 2 to ON.
The door cannot be moved when display status is active!
Electronic Counter
The display is flashing between and the most significant digits (1000 to
999000) and the least significant digits (000 – 999).
Example shown is (362 and 086) = 362086 door openings
Press STOP to see last 10 errors or exit by switching DIL switch 2 to off.
Last 10 Errors
Press OPEN (up) to select newer error.
Press CLOSE (down) to select older error.
If there is no errors the display will show:
By the end of the registered 10 errors the display will show::
Upper end
Lower end
Switch DIL switch 2 to OFF to get out of ”display status”.
Reset of last 10 errors by pressing OPEN at least 10 sec. when “upper end”
symbol is shown.
Exit by switching DIL switch 2 to off.

18
DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
9. PCB OVERVIEW
S1 STOP button X1 Mains supply X17 Relay K3
S2 OPEN button X2 Motor X19 Auto. Close (ON/OFF)
S3 CLOSE button X3 Control and safety devices X20 Secondary safety edge
D7 LED Power X5 Key pad X24 Power supply selection
D10 LED Stop X6 Antenna radio receiver K1 Contactor OPEN
D12 LED limit CLOSE X7 Plug in module: radio receiver K2 Contactor CLOSE
D13 LED push button OPEN X8 Plug in module: traffic lights K3 Relay, potential-free
D14 LED limit OPEN X12 Plug in module: Photo 1 RT1 Polyfuse
D15 LED Limit Error X13 Digital limit switch RT2 Polyfuse
D16 LED push button CLOSE X14 Plug in module: LED Panel TR1 Transformer

04/2022
-
Version 1
DoorTec Deutschland | www.doortec.online
19
Änderungen vorbehalten | Subject to Modifications
10.5 Safety device - Pneumatic safety edge
Parameter 21:04)
10.6 Additional safety edge
10.7 Photo Beam one way - Photo 2
(Testing required)
The supply voltage of the transmitter is switched off to
test the photocell. Without testing, the sensor can not
be used.
10. CONNECTIONS X3
10.1 Command devices / 6 wire connection
The LED light when a button is actuated or when inter-
rupting the STOP circuit.
10.2 Command devices / 4 wire connection
10.3 Safety device - Electrical safety edge
(Parameter 21:02)
10.4 Safety device - Optical safety edge
(Parameter 21:03)
Safety edge

20 DoorTec Deutschland | www.doortec.online
04/2022
-
Version 1
Änderungen vorbehalten | Subject to Modifications
10.11 Limit switch - Mechanical limit switch
Parameter 11:00)
10.12 Limit Switch - Kostal Encoder
(Parameter 11:05, 11:06)
10.8 Photo Beam Reflex - Photo 2
(Testing required)
Colour code photo beam RAY-RT:
18: +24 V = brown
19: 0V = blue
20: Test = grey
21: Input = black
22: Input = white
10.9 Additional photo beam - Photo 1 / X12
(Parameter 31:01)
10.10 Potential Free Contact K3 (OPTION)
INFORMATION !
The polarity of the test signal must be considered. The
signal is switched to low (0V) while testing.
X12 Self contain pho-
to cell
Photocell with re-
lay output
4+ Supply to re-
ceiver
+ Supply
3+ Signal from re-
ceiver
Relay output
2- common ground - common ground
1+ Supply to trans-
mitter
Relay output
INFORMATION !
LED D12 / D 14 are activated when the respective end
position is reached.
not in use
Chain
Table of contents
Other dtec Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Dwyer Instruments
Dwyer Instruments DFMT Series Installation and operating instructions

Korg
Korg TM-70T quick start guide

Xylem
Xylem WTW OxiTop-i operating manual

Physio Control
Physio Control TrueCPR 80596-000001 Instructions for use

Mitchell Instrument
Mitchell Instrument WENS 900C user manual

Reed Instruments
Reed Instruments R9230 instruction manual