stage thermostat or other fuel saving devices or
techniques without first contacting the factory.
11. Install Gar-Ber filter as provided rather than a
standard filter between burner and oil storage tank.
12. Before making control adjustments, verify that
all fuel, water, and electrical connections have been
made in accordance with the regulations of the
National Fire Prevention Association, the National
Electrical Code, and/or local regulations.
13. STARTUPANDADJUSTMENT: Start and adjust
burner according to manufacturer's instructions
contained in burner carton or included with boiler
and pay special attention to the following:
a. As the name suggests, this boiler is designed
to produce the ultimate in usable heat from a
gallon of fuel oil.
b. With chamber fully warmed up, find the
highest CO 2 level at which zero Smoke can be
maintained. Then add extra air until CO 2falls off
1%. Final setting should be at least 11% CO 2. If
unable to obtain that reading, check for internal
oil leaks, incorrect flame retention head, or faulty
or incorrect nozzle.
14. POST PURGE TIMING: With through-the-wall
venting there is no overfire draft present after the
burner shuts down. Therefore a post purge must be
used to prevent the hot chamber from overheating
the nozzle.
The post purge timer is part of the Honeywell
intermittent primary control, which is located on the
Beckett oil burner. The post purge time has been
preset to 4 minutes but may be adjusted to 0, 2,
4, or 6 minutes by adjusting the switches on the
side of the intermittent primary control. With a stack
thermometer in place, the boiler fully warmed up
(200°F or more), and the boiler running, turn the
high limit control on the aquastat all the way down.
The burner motor should then be running with the
flame off (i.e., in post purge). Measure the time it
takes from the flame off until the stack temperature
falls to the same temperature as the boiler water.
Adjust the post purge timer to nearest time interval,
always rounding up if possible. For example, if the
time measured is 3 minutes and 20 seconds, then
set the post purge timer at 4 minutes.
Whenever the nozzle is removed for service, check
for varnish forming on the outside of the nozzle. If
carbon and varnish do not wipe off easily, increase
the post purge time.
15. LIMITED RECYCLEAND LIMITED RESET: The
Honeywell R7184P1031 interrupted-duty primary
control utilizes two safety features to protect the
boiler from being saturated with oil. Limited recycle
will allow the burner 3 attempts to ignite, if ignition
is unproven the control locks out. The control's
reset button can then be pressed. The limited reset
feature will allow the burner to be reset 3 times
before it locks out. To unlock the control requires
the reset button to be held for 30 seconds.
16. ELECTRICAL WIRING: Wiring should conform
with the latest edition of the National Electrical Code
ANSI/NFPA No. 70 in the United States and the CSA
C22.1 Canadian Electrical Code in Canada and/or
the local authority having jurisdiction. A separate
electrical circuit should be run from the entry box
with a fused disconnect switch in this circuit. Refer
to wiring diagrams for suggested circuitry and
field wiring. Wiring for zone valve installations are
furnished with zone valve packages.
_omplete installation must be made in"_
accordance with the requirements of the local I
authorities and the National Fire Protection J
k,,Association. J
With all high efficiency boilers, care must be taken
to minimize condensation. Therefore, cold standby
is not recommended and may be used only with a
piping bypass as shown in Figure 6. This requires
a change in control wiring. Please contact factory
prior to making that change. When cold standby is
not utilized, the homeowner might possibly object to
the burner starting when space heat is not required.
To avoid this, an optional outside thermostat may
be used to shut down the system totally when
outside temperature is above a specific limit set by
the homeowner.