7
• All electrical and electronic controls are supported on the control panel located at the top of the
boiler.
• The cleaning of the installation is of utmost importance for the transformation projects from
boilers with solid fuel or liquid fuel to boilers with gas fuel. The installation shall be washed, any
leaks shall be detected and repaired and a plate type heat exchanger shall be used.
• Boilers shall be installed in a place with no risk of frost. When the boiler is not operated, the water
remaining in the radiators shall be drained to prevent freezing.
• Boilers shall not be installed in a location that contains moisture, vapor or dust. Otherwise the boiler
shall not operate correctly and efficiently.
• The floor of the installation location of the boiler shall be stable, firm and wide, and it shall be
positioned high above the ground in order not to be affected by floods.
• The supply of fresh air shall be free of halogen hydrocarbons (sprays, paints and some chemicals),
otherwise these shall cause corrosion and erosion of the boiler and flue.
• Flammable materials shall not be placed on or near the boiler.
• Fresh air intake shall comply with the instructions of the local gas supplier and the instructions for
gas connection, otherwise there is a risk of poisoning.
• Condensate and flue connections shall be made in accordance with the rules and standards.
• Before starting to work on the boiler, always disconnect the main power line and turn off the main
gas valve.
• If you smell gas, turn off the main gas valve and call the emergency number for gas leaks in your
neighbourhood. If you smell flue gas, turn off the boiler and call the authorized service immediately
Combustibility (flammability) levels of construction materials and products
Granite, sandstone, concrete, brick, ceramic, fireproof plasters
B- Very Difficult to Burn
acumin, isumin, heraclith, lignose, fiberglass components
Products made of beech or oak, hobrex plates, werzalit, umuakart
C2- Medium Combustibility
Wet wood, black pine, cork and tree crumbs, rubber sole
Asphalt Components, Fiber components, cellulose materials, polyurethane, polystyrene, PVC, polyethylene
Keep the boilers at least 200 mm away from flammable materials with B, C1, C2 burning classes as
specified in the table during their installation and operation.
• For materials that burn rapidly and by themselves after any spark, that are easily ignitable with a
burning class of C3, increase the safety distance to at least 400 mm.
The boiler is set for natural gas H/E (G20, 20 mbar) in the factory.
• The boiler shall only be installed in a room that meets proper ventilation requirements and that is
separated from living areas. Otherwise there is a risk of suffocation or poisoning.
• To prevent incorrect circulation, control valves shall be used in conjunction with the circulation
pump system. A strainer (filter) shall be used in the return water lines of the new/old buildings and
new/old installation systems.