DVG ITVC Series User manual

Intelligent Total
Valve Controller
Document Number Prepared
Approved Date Release
IOM-ITVC-LB AA GR 10/02/2016 04
Annex B:
Line Break
Line Break-differential
ITVC Series
Gas Over Oil actuator
with ITVC Line Break


ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A.WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 3 DI 28
DVGITVCSeries–“IntelligentTotalValveController”
ANNEXB:LineBreakandLineBreak-differential
1 Introduction..........................................................................................................................................5
2 Line Break protection system................................................................................................................6
3 Line Break (LB)......................................................................................................................................6
3.1 Operating mode........................................................................................................................... 7
3.2 Enable/Disable Valve Control........................................................................................................ 8
3.3 Working parameters..................................................................................................................... 8
3.4 Acquisition + ValveControl operating mode................................................................................. 9
3.5 Remote signalling......................................................................................................................... 9
3.6 Local signalling............................................................................................................................10
3.7 Analogue inputs architecture.......................................................................................................10
3.8 Output to drive the SOV ..............................................................................................................10
3.9 CPU redundancy..........................................................................................................................10
3.10 Diagnostics..................................................................................................................................11
3.10.1 CPU diagnostics...................................................................................................................11
3.10.2 Analogue inputs diagnostics.................................................................................................11
3.11 LBmenu in the ITVC HMI.............................................................................................................13
3.11.1 Enable / Disable ValveControl.............................................................................................14
3.11.2 LBparameters .....................................................................................................................15
3.11.3 LBSensor option..................................................................................................................17
3.11.4 LBoptions in the MEASUREMENTmenu of ITVC HMI...........................................................18
4 Line Break differential (LB-d)...............................................................................................................19
4.1 Operating mode..........................................................................................................................19
4.2 CPU redundancy..........................................................................................................................20
4.3 Output to drive the SOV..............................................................................................................20
4.4 Diagnostic ...................................................................................................................................20
4.5 LB-d menu in the ITVC HMI..........................................................................................................21
4.6 LB-dSensoroption ......................................................................................................................21

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 4 DI 28
4.7 LB-d Enable / Disable...................................................................................................................22
4.8 LB-dparameters..........................................................................................................................23
5 Battery option.....................................................................................................................................24
5.1 Setting options in the ADMINISTRATOR menu.............................................................................25
6 Troubleshooting..................................................................................................................................26
7 Start-up...............................................................................................................................................27
7.1 LB start-up...................................................................................................................................27
7.2 LB-dstart-up................................................................................................................................27
8 InstallationandMaintenance..............................................................................................................27
WARRANTY................................................................................................................................................28
Trade Marks:..............................................................................................................................................28

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 5 DI 28
1Introduction
This document, ITVC Annex B contains the information to set and use the Line Break function of the ITVC
Intelligent Total valve Controller. It is supplied to the user together with the manual IOM-ITVC-Basic if the ITVC has
the option “Line Break function”.
The “Annex B: Line Break function” should be considered an integral part of the document IOM-ITVC-Basic
for actuator with Line Break function.
Refer to document “IOM-ITVC-Basic” for the complete Installation, Operation and Maintenance instructions of
the ITVC
The “Annex B: Line Break function”, together with the “IOM-ITVC-Basic” is an integral part of the apparatus
and must be carefully read, understood and consulted before use and must be retained for future reference
WARNING!
Do not install, operate, or maintain an ITVC without first being fully trained and qualified in valve,
actuator and accessory installation, operation and maintenance, and carefully reading and
understanding the contents of this manual, including all safety cautions and warnings. For any
questions regarding these instructions, contact the factory before proceeding.
With reference to the manual IOM-ITVC-Basic, chapter ITVC HMI, paragraph HOME page, the Line Break function
is available only if the ITVC display shows the icon or .
The icon signals that the Line Break function is available and working according to the settings, but the output to
drive the actuator in safe position is disabled. No action is done by the ITVC to execute the safe action.
The icon signals that the execution of the safe action is enabled. If one of conditions described in the next
paragraphs occurs, the ITVC will drive actuator and process valve in safe position.
The Line Break pages in the HMI menu allow setting the working parameters.
In general the ITVC with Line Break function is fitted with an optional backup battery pack of rechargeable lithium-ion
batteries. The icon signals the charge level of the batteries. By the battery, the ITVC can work properly even if the
main electrical power fails (see Battery option paragraph)
The below figures show the HOME page, standard, HPU and HIPPS types of the ITVC HMI. Refer to IOM-ITVC-
Basic, ITVC HMI chapter, to view the HOME pages features. Refer to the above IOM to find the instructions relevant
to MENU chart and menu operations.
The procedures described in this document use HOME page standard type.
The procedures to navigate in the menu are the same if the HOME page is HPU and HIPPS type. Only the HOME
page changes.
LB icon LB icon LB icon
Battery icon Battery icon Battery icon
The icon
changes in if
the Line Break
function is enabled
to carry out the
safe action
HOME page standard type
HOME page HPU
type
HOME page HIPPS
type
ITVC
equipped
with
battery pack
Standard or extended endurance battery pack
(Rechargeable lithium-ion batteries)

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 6 DI 28
2Line Break protection system
It is a system to be installed at a pipeline site to monitor the pipeline integrity and prevent dangerous conditions due to
abnormal pressures or pressure changes. Basically it is made of pressure transmitters, actuator, process valve and ITVC
logic solver. According to the system configuration the ITVC logic solver can be set to work as
Line Break: If the ITVC detects an abnormal pressure drop rate or a dangerous pressure in the pipeline drives the
actuator to close the process valve
or alternatively
Line Break-differential: If the ITVC detects a differential pressure outside the permissible limits, across the
process valve, drives the valve in safe position. Three options are available: stayput, close, open
In this manual, Line Break function will be abbreviated by LB, and Line Break-differential by LB-d
3Line Break (LB)
This function protects the pipeline in three ways:
Pressure drop rate higher than a configurable limit
Pressure higher than a configurable limit
Pressure less than a configurable limit
If the ITVC detects one of the above condition drives actuator and valve in closure.
Its features include logic solver function with redundancy of CPU’s and voting mechanism, acquisition and record of
pipeline pressure trends, local and remote control to open/close the process valve, suitability for gas and liquids
applications.
It can be set to work in 1oo1, 1oo2, 1oo3 and 2oo3 configuration. The below figures show the 1oo1 and 2oo3
configurations
Process Valve
Actuator
Pressure sensor
Pipeline
1oo1 configuration
Pt1
Solenoid
Valve
ITVC
SOV1
Gas and
liquids
Process Valve/s
Actuator
/s
Pressure sensors
Pipeline
2oo3 configuration
Pt1
Pt2
Pt3
SOV1
SOV2
ITVC
Solenoid
Valves
Gas and
liquids
The options in
Line Break menu
page of ITVC HMI allows:
To set the type of Line Break function (LB or LB-d)
To Disable/Enable the safe action execution (if the condition
to do it occurs)
To set the sensor architecture and working setpoints

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 7 DI 28
3.1 Operating mode
Three operating modes are available:
Acquisition : the ITVC Line Break does not carry out any action to stroke the process valve, the Valve
Control is off and forced to “Disable”. The icon in the HOME page of display is . Acquisition of
analogue pressure channels is continuously done and the values are visible as instantaneous measures and 24h
graphs in the ITVC local display (see IOM-ITVC Basic, Visualization of pressures, Instantaneous measures
and Historical data sub-menus paragraphs). The ITVC monitors two pressure data, “Pressure increase / hour”
and “Pressure decrease / hour”. If one the above measures exceeds the parameters “Max pressure increase”
and “Max pressure decrease”, the ITVC raises a Warning, the LED of the pushbutton lights-up,
fuchsia colour, and the display shows the icon . After few minutes, and if the pressure remains stable, the
warning is cleared but the type of warning with date and time is memorized in the ITVC permanent memory
and is visible in the “Line Break warning” option of the Measurement menu. The measured “maximum
increase and decrease / hour” are visible in the operating mode “Monitor”. The action of parameters “Max
pressure increase” and “Max pressure decrease” can be inhibited by the option “Available/Not available” in the
setting operations. If the setting is “Not available”, no warning is raised. Open/Close, ESD actuator controls
are available.
Acquisition + Valve Control : in this mode all features of Acquisition mode are actives, in addition, if the
Valve Control is set “Enable” and if one of the “Pressure events” listed below occurs and persists for a
configurable time (Delay action), the ITVC carries out the Valve Control, that is “to energize the SOV to
stroke actuator and process valve in close position”. An alarm is generated, the LED of the pushbutton
lights-up, red colour, and the icon appears on the display. In the option “Line Break events” of the
Measurement menu is available the event history with date, time and 24 hours graph.
oPressure events:
the pipeline pressure exceeds the configured maximum pressure (reaction time 400ms)
the pipeline pressure is less than the configured minimum pressure (reaction time 400ms)
the pipeline pressure drop / minute exceeds the configured pressure drop rate (reaction time 400ms)
If the “Pressure event” disappears in the “Delay action” time, no action is done.
Once the Valve Control ends, Open/Close actuator control are inhibited (in the paragraph “Acquisition +
Valve Control mode is described the procedure to restart the operation and clear the alarm).
In general, the “safe position” is “valve closed”, but it is configurable by the procedure described in the
paragraph ESD shutdown, chapter “Setup, Administrator menu” of manual IOM-ITVC-Basic.
Monitor : all acquisition features of “Acquisition” mode are available,
Valve Control is off and forced to “Disable”, check of “Pressure increase / hour”
and “Pressure decrease / hour” is done as in Acquisition mode, but if the test
fails, the ITVC does not raise any warning. The measured “maximum pressure
increase / hour” and “maximum pressure decrease / hour” are visible in the local
display of the HMI and can be cleared by the configuration options of the menu.
The read values can be used to set the working parameters of Line Break function.
The icon in the HOME page of display is . Open/Close ESD actuator controls are available.
A

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 8 DI 28
3.2 Enable/Disable Valve Control
If the operating mode is “Acquisition + Valve Control”, the option “Enable” = ON = “ “ in the Line Break menu
page, enables the ITVC to perform the Valve Control (if a Pressure event occurs). The icon in the HOME page
of display changes in .
On the contrary, the option “Disable” = ON = “ “ inhibits the Valve Control even
if a pressure event occurs . The icon in the HOME page of display changes from
to .
In the operating modes “Acquisition” and “Monitor” the icon
in the HOME page of display is and the “Enable” option
in the LB page is forced to OFF = .
The paragraph “Enable/Disable VC” shows the procedure to set the Enable/ Disable.
3.3 Working parameters
The paragraph LB parameters shows the procedure to set the working
parameters of the Line Break function by the ITVC HMI.
The figure “LB parameters” shows the list of parameters to set.
Max pressure: the parameter sets the pipeline maximum working pressure.
If the measured pressure exceeds the “Max pressure” for the time “Delay action”,
a “Pressure event” occurs. If the operating mode is “Acquisition + Valve
Control, “Enable” is “ =ON “, the ITVC Line Break energizes the SOV to close
actuator and process valve.
Min pressure: the parameter sets the pipeline minimum working pressure.
If the measured pressure is less than “Min pressure” for the time “Delay action”, a “Pressure event” occurs. If the
operating mode is “Acquisition + Valve Control” and Enable” is “ =ON “, the ITVC Line Break energizes the SOV
to close actuator and process valve.
Pressure drop in ACQVC mode: the parameter sets the allowable max pipeline pressure drop /minute. The action of
the parameter can be inhibited by the option “Not Available/ Available” in the setting procedure.
If the setting is “available” and the measured pipeline pressure drop / minute exceeds the above parameter for the time
“Delay action”, a “Pressure event” occurs. If the operating mode is “Acquisition + Valve Control” and Enable” is “
=ON “, the ITVC Line Break energizes the SOV to close actuator and process valve. If the setting is “not available”, the
ITVC Line Break does not carry out any action in case of pipeline pressure drop.
Delay action: it is the time between the detection of the “Pressure events” described in the “Operating mode”
paragraph and the start of the action to close the process valve. If the pressure event disappears during the time “Delay
action”, the ITVC Line Break does not carry out any action to move the process valve.
Operating mode: it allows setting the Line Break operating mode, as described in the previous paragraph “Operating
mode”. Three operating modes are available: Acquisition, Acquisition + Valve Control, Monitor
Maximum pressure increase: it sets the allowable maximum increase in pressure / hour. The parameter can be
inhibited by the option “available/not available” in the setting procedure. If the measured “pressure increase / hour”
exceeds the above parameter, the parameters is set “available”, and the operating mode is “Acquisition” or “Acquisition
+ Valve Control”, the ITVC Line Break raises a Warning, but the SOV is not energized and no action is carried out
to close the process valve. In “Monitor” operating mode, no warning is generated and the measured maximum pressure
increase can be viewed in the Monitor page of the menu.
LB
parameters
LB page
= ON
= OFF

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 9 DI 28
Maximum pressure decrease: it sets the allowable maximum decrease in pressure / hour. The parameter can be
inhibited by the option “available/not available” in the setting procedure. If the measured “pressure decrease / hour”
exceeds the above parameter and the parameter is set “available”, the ITVC Line Break raises a Warning, but the SOV
is not energized and no action is carried out to close the process valve. In “Monitor” operating mode, no warning is
generated and the measured maximum pressure decrease can be viewed in the Monitor page of the menu.
3.4 Acquisition + Valve Control operating mode
To start the LB operation
The Line Break carries out the Valve Control if the operating mode is “Acquisition + Valve Control” and only if
“Enable is = ”. The paragraphs “Enable/Disable VC” shows the procedures to Enable the Valve Control. The icon
in the HOME page of the display switches from to . The local and remote Open/Close and ESD commands
are available. The ITVC Line Break continuously acquires and measures the pipeline pressure. If one of the “Pressure
events” described in the previous paragraph “Operating mode”occurs and persists for the time “Delay action”, the
ITVC Line Break carries out the “Valve Control”, that means: to energize the SOV and stroke the actuator and the
process valve in closure (safe position). After having closed the process valve the Valve Control switches in “Disable”
and any open/close command is inhibited. The data of the “pressure event” (date, type of event, 24h pressure graph)
are memorized in the ITVC permanent memory and can be viewed in the Measurement menu of the ITVC HMI. The
icon in the HOME page of the display switches from to . ITVC signals Alarm and any Open and Close
command is off.
If the Pressure event disappears within the time “Delay action”, no action is done.
To restart LB operation after a Valve Control:
restore the correct pressure in the pipeline
set “Enable = ” in the Line Break parameters
re-open the actuator by the local or remote open command
To re-open the valve without restoring the correct pressure in the pipeline:
set Acquisition or Monitor control mode. The Alarm disappears, exit from MENU mode.
move the valve by the local or remote open/close commands
set the Acquisition + Valve Control mode
when the pipeline pressure is correct, set the Line Break option “Enable = ”
To set in OFF the Valve Control function
set Acquisition or Monitor operating mode. In the above modes the Valve Control is OFF, the option “Disable
is = “ and “Enable is = “ .
3.5 Remote signalling
In Acquisition + Valve Control mode and Enable = , the Monitor Relay switches over when ITVC carries out the
Valve Control.
The auxiliary output relays R1,…,R4 can be individually set to signal: Max pressure increase, Max pressure decrease,
LB on=Enable, High LB pressure, Low LB pressure, Max pressure drop. The paragraphs “Output signalling relays” and
“Output relays” in the IOM-ITVC-Basic give the procedure to set the above relays.

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 10 DI 28
3.6 Local signalling
In “Acquisition” and “Monitor” operating modes, the HOME page of the display shows the icon .
In “Acquisition + Valve Control” mode and Disable = , the HOME page of the display shows the icon .
In “Acquisition + Valve Control” mode and Enable = , the HOME page of the display shows the icon . If Valve
Control is performed, the ITVC signals Alarm by the red LED of the pushbutton , and the display of the HOME
page shows the icon . The Alarm page shows the message
“High press limit or Low press limit or Press drop”, “Linebreak action”, Safety action LB, and Micro 2 alarm
(see the paragraph Visualization of Alarms and Warnings in the document IOM-ITVC-Basic).
In “Acquisition” and in “Acquisition + Valve Control” modes, the conditions “Pressure increase and decrease / hour >
Max pressure increase/decrease” are signalled by Warning. The LED of the pushbutton is on, fuchsia colour, and
the display shows the icon . The Warning page of the display shows the message “Max pressure increase” or “Max
pressure decrease”. In Monitor operating mode the measured “Max pressure increase and decrease / hour” can be
viewed. The clear option in the above page resets the displayed values.
The option “Line Break Events” in the Measurement menu shows the list of the “Pressure events” with date and
time and the 24 hours graphs.
The option “Line Break Warnings” in the Measurement menu shows the list of the warnings with date and time. No
graph is available.
3.7 Analogue inputs architecture
The option “Sensor” in the Line Break menu page allows setting the architecture
of the analogue inputs connected to the pipeline pressure transmitters .
3 modes are available: 1oo1, 1oo2, 2oo3 and 1oo3.
1oo1 mode: one only pressure transmitter, only Sensor 1 or 2 or 3 = = ON,
no voting mechanism, one only analogue input channel
1oo2 mode: two pressure transmitters, Sensor 1-2 or 1-3 or 2-3 = = ON,
voting mechanism, two analogue input channels
2oo3 mode: three pressure transmitters, Sensor 1-2-3 = = ON,
voting mechanism, three analogue input channels
1oo3 mode: three pressure transmitters, Sensor 1-2-3 = = ON,
voting mechanism, three analogue input channels,
“1oo3 operating mode” = = ON
The analogue input channels should be previously enabled/disabled by the
Setup, Administrator, Analog inputs menu (see document IOM-ITVC-Basic).
The next paragraph “Diagnostics” describes the behaviour in case of failure.
3.8 Output to drive the SOV
According to the user request, the ITVC can be configured to control one or two SOV’s. ITVC functions include the
test of electrical continuity and absence of short-circuit of coil of SOV’s. It is described in the IOM-ITVC-Basic,
paragraph “Test of coil of Solenoid Operated Valves” and in the procedures “Coil test” and “Test coil absorption”,
Setup chapter, Administrator menu. Any fault must be detected three consecutive times, before confirmation.
3.9 CPU redundancy
Line Break and emergency safety functions are managed by two independent CPU’s working in parallel, in particular
they manage input reading, logic processing and output enabling.
A
LB
page
LB sensor
= ON
= OFF

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 11 DI 28
3.10 Diagnostics
3.10.1 CPU diagnostics
Diagnostics processed by each CPU includes: Diagnostics of comparison between the two CPUs, Software flow
diagnostics, Watchdog, System clock monitor and Detection of a fault not imputable to an identified channel:
oPower supply diagnostics
oTemperature diagnostics
oComparison diagnostics of redundant channels (1oo2 architecture)
oCPUs Comparison diagnostic
In case of the above mentioned instances, system switches to safe state.
3.10.2 Analogue inputs diagnostics
The range-ability of the analogue input circuits is from 3 to 21 mA.
CPU’s 1 and 2 perform the following diagnostics:
Under-range and Over-range
Both CPU’s assumes that if signal is <3mA or >21mA the transmitter or the acquisition stage is damaged
Action performed:
o1oo1 architecture:
Valve Control (SOV energization and closure of actuator)
Local alarm and display of type of fault
Switch-over of Monitor relay
o1oo2 architecture:
Local “MRT timer” alarm and display of type of fault
Switch-over of Monitor relay
Exclusion of damaged channel
Operation in 1oo1 architecture for a maximum time equal to MRT. Correct system must be
restored (repair or replace the device) or Valve Control will be carried out at the end of MRT
time. The menu option MRT, in the Measurement menu, displays the remaining time before
than MRT time ends
Valve Control will be carried out if the surviving analogue channel fails in the MRT time
o1oo3 architecture:
Local “MRT timer” alarm and display of type of fault
Switch-over of Monitor relay
Exclusion of damaged channel
Operation in 1oo2 architecture for a maximum time equal to MRT. Correct system must be
restored (repair or replace the device) or Valve Control will be carried out at the end of MRT
time. The menu option MRT, in the Measurement menu, displays the remaining time before
than MRT time ends
In the MRT time, operation in 1oo1 architecture if a further analogue channel fails (due to
over-under range) and Valve Control if also the surviving analogue channel fails
In the MRT time, Valve Control if comparison between the two channels fails
o2oo3 architecture:
Local alarm and display of type of fault
Switch-over of Monitor relay
Exclusion of damaged channel
Operation in 1oo2 architecture for a maximum time equal to MRT. Correct system must be
restored (repair or replace the device) or Valve Control will be carried out at the end of MRT
time. The menu option MRT, in the Measurement menu, displays the remaining time before
than MRT time ends
- In the MRT time, Valve Control will be carried out if the remaining analogue channels
fail (due to over/under range or out of comparison)

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 12 DI 28
Continuous comparison and voting for 1oo2, 1oo3 and 2oo3 architectures
After A/D conversion, if a single signal deviation is more than 5% compared to the reading of each remaining
signal, both CPU’s assume that:
Analog inputs in 1oo2 architecture: one of two signals is not reliable, but it is not possible to identify
which one
Analog inputs in 2oo3 architecture: channel with the signal out of deviation range is considered damaged
Action performed:
o1oo2 architecture:
Valve Control (SOV energization and closure of actuator)
Local alarm and display of type of fault
Switch-over of Monitor relay
o1003 architecture:
Local “MRT timer” alarm and display of type of fault
Switch-over of Monitor relay
Exclusion of damaged channel
Operation in 1oo2 architecture for a maximum time equal to MRT. Correct system must be
restored (repair or replace the device) or Valve Control will be carried out at the end of MRT
time. The menu option MRT, in the Measurement menu, displays the remaining time before
than MRT time ends
- in the MRT time, Valve Control will be carried out if the analogue channels comparison
fails or in case of under/over range in one channel
o2oo3 architecture:
Local alarm and display of type of fault
Switch-over of Monitor relay
Exclusion of damaged channel
Operation in 1oo2 architecture for a maximum time equal to MRT. Correct system must be
restored (repair or replace the device) or Valve Control will be carried out at the end of MRT
time. The menu option MRT, in the Measurement menu, displays the remaining time before
than MRT time ends
- In the MRT time, Valve Control will be carried out if the remaining analogue channels
fail (due to over/under range or out of comparison)
Restart operations:
check/repair transmitter, restore pressure
clear MRT alarms in the Measurement menu, MRT sub-menu
clear Alarms and Warnings
restore Line Break operation and open the actuator if Valve Control was done
Any fault must be detected three consecutive times, before confirmation.
If one sensor fails the ITVC signals alarm, but if the LB is set “Disable” the open/close and ESD commands
are available

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 13 DI 28
3.11 LB menu in the ITVC HMI
The procedures to view the instantaneous values of the pressure transmitters, the historical data and the alarms are
described in the paragraphs “Visualization of pressures”, “Instantaneous measures sub-menu”, “Historical data
sub-menu” and “Visualization of Alarms and Warnings” of the document “IOM-ITVC-Basic”. Refer to ITVC
HMI chapter of the above IOM to find the instructions relevant to HOME page, navigation in the MENU and MENU
chart.
Here below are described only the procedures to set the LB parameters, to enable/disable the Valve Control, to set the
operating mode and sensor architecture. Access to LB menu is allowed only by password “ADMINISTRATOR”.
To enter in the LB menu, by and position the cursor on the icon or and then press . Enter the
password Administrator (“default 00001”). The ITVC display shows the Line Break menu page.
To switch back from Line Break page to HOME page press simultaneously or by and position the cursor
on and press
The above figure refers to the “Standard type”of HOME page (see IOM-ITVC-BASIC, paragraph HOME page). The
procedure to navigate in the LB menu is the same in case of HOME pages “HPU type” and “HIPPS type”.
The Line Break menu has the following options: Enable, Disable, Linebreak, Linebreak differen and Sensor. In the
next paragraphs is the description of each option relevant to LB. The chapter 4 describes the LB-d

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 14 DI 28
3.11.1 Enable / Disable Valve Control
Enable: if a “Pressure event” occurs and lasts for the time “Delay action”, the ITVC energizes the SOV to
move the actuator in safe position (closure). The “Enable” option is available only if the parameter “Operating
mode” is “Acquisition + Valve Control”. The icon of the HOME page is .
Disable: even if a “Pressure event” occurs and lasts for the time “Delay action”, the ITVC does not move the
valve. The icon of the HOME page is .
ON = , OFF = .
Enable Valve Control procedure:
Disable Valve Control procedure:

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 15 DI 28
3.11.2 LB parameters
The below figures shows the procedure to set the values of the LB Parameters “Max pressure, Min pressure,
Operating mode, Delay action, Max pressure diff.”,described in the previous paragraph “Line Break working
parameters”.
In the operating mode “MONITOR”, the option YES, in the Reset page, clears the measured Max increase / hour and
Max decrease / hour in the “Monitor page” of display

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 16 DI 28
The below figures show the procedure to set values of the LB Parameters “Max pressure increase, Max pressure
decrease and Pressure drop ACQVC (ACQuisition + Valve Control)”, described in the previous paragraph “Line
Break working parameters”.

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 17 DI 28
3.11.3 LB Sensor option
The procedure described below allows setting the analogue input architecture.
Sensor 1: it corresponds to “L1 Pressure sensor” in the Measurement and Setup menu
Sensor 2: it corresponds to “L2 Pressure sensor” in the Measurement and Setup menu
Sensor 3: it corresponds to “S3 Pressure sensor” in the Measurement and Setup menu
The character “ “ indicates presence of transmitter, the character “ “ indicates absence.
To avoid alarms, it is important that the configuration of the LB sensor page in the Line Break menu is according to the
setting of the Analog inputs page in the Administrator, Setup menu. If a sensor is “not available” ( ) in the Analog
input page it must be set “absent” ( ) also in the LB sensor page. Vice-versa, if a sensor is set “available” ( ) in
the Analog inputs page in the Administrator, Setup menu, it should be set “present” in the LB sensor page and Line
Break function works according to description in the paragraph “Analogue input architecture”. It is mandatory that the
above settings is according to the pressure transmitters really connected to the analogue input channels of the ITVC.
The “1oo3 operating mode” sets the analogue input channels architecture to work in 1oo3 mode, see “Diagnostics”
paragraph.
Note: A sensor set “available” in the Analog inputs page in the Administrator, Setup menu, and “absent” in the LB
sensor page, is not used by the Line Break function, but if it fails, it generates an Alarm (even if not used). The figure
below shows an example of setting in case of 1oo1 analogue input architecture.
Analog input page
LB sensor page
This settings is not correct
.
T
he working pressure
transmitter is Sensor 2, connected to analogue channel
2, Press sens L2 in the Analogue input page of
Administrator, Setup menu. Even if not used by the
Line Break function, the pressure sensors connected to
analogue channels 1 and 5, Press sens L1 and Press
sens S3 generates alarms in case of failures (or if they
are not connected to ITVC), since they are set as
“available”. They must be configured “not available”
Correct settings
.
T
he working pressure transmitter is
Sensor 2, connected to analogue channel 2, Press sens
L2 in the Analogue input page of Administrator, Setup
menu. Press sens L1 and S3 are “not available”.
Analog input page
LB sensor page

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 18 DI 28
3.11.4 LB options in the MEASUREMENT menu of ITVC HMI
The below procedure allows viewing the “Pressure events” history and graphs and the Line Break warning list and
date. In the Line Break Events page, D stays for Pressure Drop rate, Hstays for High pressure, Lstays for Low pressure
In the Line Break warnings page the character “M” stays for “Max pressure increase” and “m” stays for “Max pressure
decrease”. The procedure to move in the Measurement menu are described in the manual IOM-ITVC-Basic.
In the manual IOM-ITVC-Basic, Measurement menu, Historical data sub-menu are described the procedures to view
the instantaneous pressure measures and the L1, L2, S3, S4 pressure history and graph. History and graph are available
only if they are marked with the symbol “ “.

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 19 DI 28
4Line Break differential (LB-d)
The ITVC monitors the pressure across the process valve and carries out the safe action if the differential pressure is
outside the limit. The following LB-d options can be set:
Safe action:
ostayput, open, close
Condition to start:
odifferential pressure higher than a configurable limit
odifferential pressure less than a configurable limit
Differential pressure limit:
oconfigurable pressure value to compare with the read pressure and decide if the safe action should start
Enable/Disable:
oby this parameter the LB-d safe action is enabled/disabled
Only 1oo2 configuration of analogue inputs is available. The reaction time is 200ms
4.1 Operating mode
If the setting is “Enable” the icon of the HOME page is : the local and remote open/close and ESD commands
are available. If the configured “condition to start” is true, the ITVC drives actuator and valve to the safe position
(stay in position or open or close). The icon of the HOME page becomes and LB-d switches to “Disable” status.
The ITVC signals alarm by the icon and by the LED of the pushbutton that lights-up red colour. The Monitor
relay switches over. The alarm visualization page of the ITVC HMI shows: “Linebreak action”, “Press out of limit”,
“Micro 2 alarm” and “Safety action”. The alarm is recorded also in the “Alarm history” register (Measurement
menu). The local and remote open/close commands to move actuator and valve are inhibited, but the ESD command
is still available since it has the highest priority.
Even if the “condition to start” becomes false the LB-d remains in “Disable” status, the ITVC maintains the alarms and
the open/close commands are off.
In case of ESD command sent after the “condition to start” occurs, the ITVC drives actuator and valve to the safe
position set in the ESD parameters (ESD safety position). When the ESD command disappears, since the LB-d status is
“Disable”, the actuator remains in the last position.
Vice-versa if the ESD command was sent before the “condition to start” occurs, the LB-d remains in “Enable” status.
Due to ESD command, actuator and valve move to the ESD safety position, but if the ESD command is removed and
the “condition to start” is true, actuator and valve perform the LB-d safe action
To restore LB-d operation it is necessary
to check that the differential pressure is in the acceptable limit
to set the parameter “Enable” = ON in the ITVC HMI.
The alarm is cleared and the local and remote open/close commands are available.
If the setting is “Disable” the icon of the HOME page is . The ITVC works according to IOM-ITVC-basic. The
differential pressure is continuously measured and visible by the ITVC HMI, but the safe action is inhibited e no alarm
is generated even if the “condition to start” is true.
Process Valve
Actuator
PT1 and PT2
Differential
Pressure sensors
Pipeline
1oo2
configuration
Pt1
Solenoid
Valve
ITVC
SOV
Gas and
liquids
Pt2
A

ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
FullyPaid In Capital: Euro 1.000.000,00= ISO 9001, ISO 14001, OHSAS 18001 CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECTTO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. WITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
www.dvgautomation.it SHEET 20 DI 28
4.2 CPU redundancy
Line Break-differential is safety function managed by two independent CPU’s working in parallel, in particular they
manage input reading, logic processing and output enabling.
4.3 Output to drive the SOV
ITVC functions include the test of electrical continuity and absence of short-circuit of coil of SOV. It is described in the
IOM-ITVC-Basic, paragraph “Test of coil of Solenoid Operated Valves” and in the procedures “Coil test” and “Test
coil absorption”, Setup chapter, Administrator menu. Any fault must be detected three consecutive times, before
confirmation.
4.4 Diagnostic
Analogue input diagnostic
The range-ability of the analogue input circuits is from 3 to 21 mA.
CPU’s 1 and 2 perform the following diagnostics:
Under-range and Over-range
Both CPU’s assumes that if signal is <3mA or >21mA the transmitter or the acquisition stage is damaged
Action performed:
oLocal “MRT timer” alarm and display of type of fault
oSwitch-over of Monitor relay
oExclusion of damaged channel
oOperation in 1oo1 architecture for a maximum time equal to MRT. Correct system must be restored
(repair or replace the device) or the configured LB-d safe action will be carried out at the end of
MRT time. The menu option MRT, in the Measurement menu, displays the remaining time before
than MRT time ends
LB-d safe action will be carried out if the surviving analogue channel fails in the MRT time
Continuous comparison and voting
After A/D conversion, if a single signal deviation is more than 5% compared to the reading of each remaining
signal, both CPU’s assume that:
One of two signals is not reliable, but it is not possible to identify which one
Action performed:
oLB-d safe action
oLocal alarm and display of type of fault
oSwitch-over of Monitor relay
CPU’s diagnostic
Diagnostics processed by each CPU includes: Diagnostics of comparison between the two CPUs, Software flow
diagnostics, Watchdog, System clock monitor and Detection of a fault not imputable to an identified channel:
oPower supply diagnostics
oTemperature diagnostics
oComparison diagnostics of redundant channels (1oo2 architecture)
oCPUs Comparison diagnostic
In case of the above mentioned instances, system switches to safe state.