Dynisco MDT 420 User manual

From lab to production,
providing a window into the process
-1-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
MDA / LDA / TDA Series
Pressure transducers for high temperatures and high
pressures
Operang Manual

From lab to production,
providing a window into the process
-2-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
Table of Contents
Content Chapter Page Icon
General
Notes on safety
Technical data
Funcon
Transport/delivery
Installaon
Commissioning
Maintenance
Accessories
Troubleshoong
- Declaraon
of conformity
1
2
3
4
5
6
7
8
9
10
11
3
5
6
13
14
16
24
26
28
29
30

From lab to production,
providing a window into the process
-3-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
1. General
1.1 Important informaon
1.2 Copyright
1.3 Explanaon of icons
1.4 Abbreviaons
1.5 Correct use
1.6 User’s obligaons
1.1 Important information
This manual applies to the MDT 420/460/435/467 and PT 420/460, TDA 432/463 and
LDA 415 series only. It must be kept near the equipment in a readily and immediately
accessible locaon at all mes.
The content of this manual must be read, understood and
followed in all points by all relevant people. This applies in parcular to the notes on
safety. Following the safety instrucons will help to prevent accidents, defects and
malfuncons.
DYNISCO will not be held liable for any injury, loss or damage resulng from failure to
follow the instrucons in this manual.
If malfuncons occur in spite of having followed the operang instrucons, please
contact the DYNISCO customer service department (see chapter 8,
Maintenance).
This applies in parcular during the warranty period.

From lab to production,
providing a window into the process
-4-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
1.2 Copyright
Copyright law requires that this manual be used for inhouse purposes only.
All reproducon, even parally and for in-house purposes, requires the approval of
DYNISCO. This manual may not be forwarded to third pares.
1.3 Explanation of icons
The manual uses icons to indicate informaon pertaining to safety:
Risk of destrucon or damage to equipment, machines or installaons
General danger to life or limb
Specic danger to life or limb
You MUST do this
The safety instrucons are provided again in the individual chapters of the manual.
1.4 Abbreviations
The following abbreviaons are used:
OM Operang manual
PT pressure transmier
f.s. of full scale

From lab to production,
providing a window into the process
-5-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
1.5 Correct use
The purpose of the pressure transducer is to measure pressure in plasc melt as part
of a larger overall system. The PT can be used in media temperatures up to 400°C.
If the PT is used in other applicaons, the safety and accident prevenon regulaons
specic to that applicaon must be followed.
When using the PT as a safety component in accordance with the EC Machine
Direcve, Annex IIc, the equipment manufacturer must take any necessary
precauons to ensure that malfuncons of the PT cannot cause damage or injury.
1.6 User’s obligations
The operator or owner of the larger overall system, e.g. a machine, is responsible for
following the safety and accident prevenon regulaons that apply to the specic
applicaon.
2. Notes on safety
The operator or owner of the larger overall system is responsible for
following the safety and accident prevenon regulaons that apply
to the specic applicaon.
Toxic hazard!
The PT contains a small amount (7 mm³) of mercury (Hg) as its transmis-
sion medium. If the diaphragm is damaged, mercury may escape.
Never transport or store the PT without the protecve shell bolted in
place. Remove the shell shortly before installaon.
If mercury is inhaled or swallowed, seek medical aenon immediately!
Mercury is hazardous waste and must be disposed of in accordance with
applicable laws. DYNISCO will accept defecve PTs. If mercury escapes,
use airght packaging!

From lab to production,
providing a window into the process
-6-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
When planning machinery and using the PT, follow the safety and
accident prevenon regulaons that apply to your applicaon,
e.g.:
● EN 60204, Electrical equipment in
machines.
● EN 292, Machine safety, general design
guidelines.
● DIN 57 100 Part 410, Protecon against
electric shock.
Mounng and electrical connecon of the PT must be done by specialists
with EMC training, following all applicable regulaons, and in
pressureless, voltage-free condion with the machine switched o.
The machine must be secured against being switched back on!
Burn hazard!
The PT must be removed with the melt in molten condion. The PT can
be very hot when removed.
Wear protecve gloves!
3. Technical Data
3.1 Ordering guide
3.2 Ordering example
3.3 Performance characteriscs
3.3.1 Accuracy
3.3.2 Repeatability
3.3.3 Resoluon
3.4 Mechanical conguraons
3.5 Pressure side connecon

From lab to production,
providing a window into the process
-7-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
3.6 Pressure ranges
3.6.1 Pressure ranges in bar
3.6.2 Max. Overload
3.6.3 Burst pressure
3.6.4 Limit frequency
3.7 Rigid stem/exible stem
3.8 Electrical Data
3.9 Temperature inuence
3.10 EMC requirements
3.11 Materials
3.12 Mounng torque
3.13 Environmental Protecon
3.14 Weight
3.15 Dimensions
3.1 Ordering guide
3.2 Ordering example
xDT4xx x- xx - xxx - x - Opon
Rigid stem/exible stem
Pressure range
Pressure side connecon
Amplier
Perf. characteriscs
Mechanical conguraon
The exact meanings of the leer/digit combinaons are given in the corresponding
secons of chapter 3.
MDT462 F - ½ - 5C - 15/46
Melt PT
Perf. char. ± 1,0 % full scale
Amplier: 2-wire 4-20mA
Thread: ½ = ½" - 20 UNF
Pressure range: 0 - 500 bar
Stem length:15 = 152 mm
Flex. stem:46 = 457 mm

From lab to production,
providing a window into the process
-8-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
3.3 Performance characteristics (xDT4Xx x-xx-xxx-xx)
3.3.1 Accuracy
(Linearity and hysteresis at T = constant)
xDT42x x ± 0,5 % of full scale
(35 bar and 50 bar ± 1 % of full scale)
xDT46x x ± 1 % of full scale
3.3.2 Repeatability
xDT42x x ± 0,1 % of full scale
(35 bar and 50 bar ± 0,2 % of full scale)
xDT46x x ± 0,2 % of full scale
3.3.3 Resolution innite
3.4 Mechanical configurations (XDT4xX x-xx-xxx-xx)
MDT4x0, LDA 415 stem version
MDT4x2 rigid stem and exible stem
TDT432/463 combined pressure and
temperature measurement
MDT435/467 transducer for limited
installaon space
3.5 Pressure side connection (xDT4xx x-XX-xxx-xx)
½ = ½” 20 UNF 2A
M18 = M18 x 1,5
3.6 Pressure ranges (xDT4xx x-xx-XXX-xx)

From lab to production,
providing a window into the process
-9-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
3.6.1 Pressure ranges in bar
Model number Permitted pressure range in bar
xDT4xx x-xx-17-xx 0 - 17 series 42x/43x x only
xDT4xx x-xx-35-xx 0 - 35 series 42x/43x x only
xDT4xx x-xx-50-xx 0 - 50 series 42x/43x x only
xDT4xx x-xx-1C-xx 0 - 100
xDT4xx x-xx-2C-xx 0 - 200
xDT4xx x-xx-3,5C-xx 0 - 350
xDT4xx x-xx-5C-xx 0 - 500
xDT4xx x-xx-7C-xx 0 - 700
xDT4xx x-xx-1M-xx 0 - 1000
xDT4xx x-xx-1,4M-xx 0 - 1400
xDT4xx x-xx-2M-xx 0 - 2000
Other pressure ranges on request
3.6.2 Max. Overload (without influencing operating data)
2 x full scale pressure up to 700 bar (for 1000 bar and 1400 bar range: max. 1750 bar,
and 2450 bar for the 2000 bar range)
3.6.3 Burst pressure 6 x nominal value,
max. 3000 bar
3.6.4 Limit frequency 50 Hz [-3db]
3.7 Rigid stem/flexible stem (xDT4xx x-xx-xxx-XX)
15 = 152 mm standard length for rigid version
15/46 = 152 mm stem length / 457 mm exible stem
Other lengths on request

From lab to production,
providing a window into the process
-10-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
3.8 Electrical data (xDT4xx X-xx-xxx-xx)
Conguraon 4-arm Wheatstone bridge
strain gauge with int. amplier
Output signal 3,33 mV/V ± 2 %
Supply voltage 10 VDC (recommended)
min.6 VDC, max.12 VDC
Calibraon funcon 80 % ± 0,5 % of full scale
(room temperature) output by externally connecng contacts E and F
Leakage resistance > 1000 MΩ at 50 V
3.9 Temperature influence
Housing
Max. housing temperature ± 120 °C
Zero shi due to temperature change on the housing
xDA420 series ±0,2% full scale /10°C typ.
xDA460 series ±1,0% full scale /10°C typ.
Sensivity shi due to temperature change on the housing
xDA420 series < 0,1 % f. s. / 10 °C typ.
(35 and 50 bar < 0,2 % f. s. / 10 °C) typ.
xDA460 series < 0,4 % f. s. / 10 °C typ.
Diaphragm (in contact with media)
Maximum temperature at the diaphragm
400 °C
Zero shi due to temperature change on the diaphragm
xDT 420 series <0,2 bar / 10 °C typ.
xDT 460 series < 0,4 bar / 10 °C typ.

From lab to production,
providing a window into the process
-11-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
3.10 EMC requirements
Conforming to in accordance with EMC direcve.
Emied interference DIN EN 50081-1
(residenal area)
Immunity DIN EN 50082-2
(industrial area)
3.11 Materials
Diaphragm 15-5PH Mat.No. 1.4545
Armoloy coated
Stem 15-5PH Mat.No. 1.4545
3.12 Mounting torque max. 50 Nm (500 inch-lbs.)
min. 12 Nm (100 inch-lbs.)
3.13 Environmental protection to IEC 529
PT housing IP54 (without connector)
Standard connector
PT06A-10-6S(SR) IP40
Connector PT06W-10-6S IP64
3.14 Weight 0,6 kg
3.15 Dimensions

From lab to production,
providing a window into the process
-12-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a

From lab to production,
providing a window into the process
-13-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
4. Function
4.1 Construcon
4.2 Descripon of funcons
4.3 PT series
4.1 Construction
The PTs of series MDT 420 x/460 x are industry standard.
The main advantages are:
- manufactured under ISO 9002
- thermal stability
- resistance to aggressive media
- insensivity to electromagnec radiaon (EMC)
- liquid-lled transmission system (mercury)
- pressure measurements in plasc melt up to a temperature of 400°C (750°F)
- maximum pressure 2000 bar
4.2 Description of functions
Through a closed, liquid-lled pressure transmission system, the PT furnishes
an electrical signal that is proporonal to the pressure of the melt.
The pressure applied by the medium is forwarded to the measuring diaphragm via the
separang diaphragm and the transmission medium (standard conguraon:
mercury) in the capillary. The deecon of the measuring diaphragm changes the
resistance of the strain gauge bonded to the measuring diaphragm. The strain gauge
is a Wheatstone bridge.
An electric signal proporonal to the pressure is generated via the supply voltage.

From lab to production,
providing a window into the process
-14-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
Fig. 05: Funconing
principle of the PT
of the MDT 420/460
series
4.3 PT series
The MDA/LDA/TDA series PTs are also
available as PT series. The PT types
correspond to the MDA models, and the
TPT types correspond to the TDA models;
the number codes are idencal. The PT
series diers from the MDA series in that
all specicaons are given in US American
units of measure.
E.g.: 1 bar = 14,5 PSI
(PSI value is rounded)
2,54 cm= 1" (inch)
All other specicaons are the same as in
the MDT series.
5. Transport / delivery
5.1 Transport / packing /
transport damage
5.2 Storage
5.3 Scope of delivery

From lab to production,
providing a window into the process
-15-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
Toxic hazard!
The PT contains a very small amount of mercury (Hg) as its
transmission medium. If the diaphragm is damaged, mercury
may escape. Non-toxic NaK is being used in the LDA series. NaK is
also available as an opon for other pressure transducers. Never
transport or store the PT without the protecve shell bolted in
place. Remove the shell shortly before installaon.
If mercury is inhaled or swallowed, seek medical aenon
immediately.
Mercury is hazardous waste and must be disposed of in
accordance with applicable laws. DYNISCO will accept defecve
PTs.
If mercury escapes, use airght packaging!
Alternave, non-toxic transmission media (Oil or NaK) available
on request.
ESD sensive component. Electrostac discharge may damage
the PT. Take ESD precauons.
5.1 Transport/packing/transport damage
- Do not let the PT be damaged by other items during transit.
- Use only the original packaging.
- Report transport damage to DYNISCO immediately in wring.
5.2 Storage
- Store the PT in original packaging only.
- Protect against dust and moisture.
5.3 Scope of delivery
- PT with diaphragm protecon cap
- Cable socket
- Fastening clip (transmier with exible stem only)
- Calibraon sheet
- Operang manual

From lab to production,
providing a window into the process
-16-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
6. Installation
6.1 Mounng hole
6.2 Checking the mounng hole
6.3 Mounng the Pressure Transmier
6.4 Mounng PTs with exible stem
6.5 Electrical connecon
6.5.1 EMC / compliant connecon
6.6 Connecon assignments
6.7 Wiring
6.8 Connecon thermocouple /RTD element
Am bient temperature for the electronics housing max.
+120°C. Higher temperatures can result in damage and
malfuncons. Mount the PT only in locaons where
these temperatures are not exceeded.
6.1 Mounting hole
To produce the mounng hole, use only DYNISCO
machining tool kit.
- Drill the mounng hole as shown in gure 06/07.

From lab to production,
providing a window into the process
-17-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
Fig. 06: Mounng hole for transmier
MDT 420, 460, 422, 462, 432, 463
Fig. 07: Mounng hole for transmier MDT467 x

From lab to production,
providing a window into the process
-18-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
When reworking the mounng hole, pay parcular aenon to the
centricity of:
- the hole,
- the thread and
- the sealing surface.
Pressure sealing takes place on the 45° beveled sealing surface and on the front
cylindrical secon of the PT (see gures 06 and 07).
The sealing surface must be:
- correctly machined
- free from marks and rough edges
- free from solidied plasc residue.
6.2 Checking the mounting hole
- Paint the test bolt DYNISCO on the marked area
(gure 08, item 1) with marking ink up to the
thread.
Fig. 08: test bolt with marking ink
- Insert the test bolt in the mounng hole
- Twist it in by hand unl the two sealing surfaces make contact.
- Remove and examine the test bolt.
The only acceptable abrasion of marking ink is at the sealing edge (45°), evenly (!)
over the enre circumference.
If the ink has been rubbed o in other places too:
- rework the mounng hole.

From lab to production,
providing a window into the process
-19-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
6.3 Mounting the Pressure Transmitter
Mounng and electrical connecon of the PT must be
done by specialists with EMC training, following all applicable
regulaons, and in pressureless, voltage-free condion with the
machine switched o.
The machine must be secured against being switched back on!
Toxic hazard!
(Only when using standard models with mercury)
The PT contains a small amount (7 mm³) of mercury (Hg) as its
transmission medium. If the diaphragm is damaged, mercury may
escape.
Never transport or store the PT without the protecve shell bolted
in place. Remove the shell shortly before installaon.
If mercury is inhaled or swallowed, seek medical aenon
immediately!
Alternave, non-toxic transmission media (Oil or NaK) available on
request.
ESD sensive component. Electrostac discharge may damage the
PT. Take ESD precauons.
Before mounng the PT, check the mounng hole carefully. The PT
must only be mounted in holes that sasfy the requirements
spulated in chapter 6.1. A hole that does not sasfy these
requirements can damage the PT.
Before mounng the PT, ensure that the mounng hole is free
from plasc residue. Remove plasc residue with the DYNISCO
cleaning tool kit. A test bolt is included with this cleaning set.
To prevent the PT from scking permanently in the mounng hole,
coat the thread secon of the transmier with high temperature
resistant grease or a suitable parng agent.
- Check the mounng hole with the test bolt, and clean with cleaning set if necessary.
- Coat the thread secon of the transmier with high temperature resistant grease or
a suitable parng agent.

From lab to production,
providing a window into the process
-20-
www.dynisco.com
Rev: 1117P/N: n/a ECO: n/a
Always use a spanner applied to the designated hexagon
collar when screwing the PT in and out. Do not apply the
tool to the housing or housing/sensor connecon!
Maximum mounng torque 50 Nm. If the mounng torque is too
high, the PT may be damaged or its zero point may shi.
- screw the PT into the mounng hole and ghten.
6.4 Mounting PTs with flexible stem
Mounng a PT with a exible stem to the pressure sensor is done analogously to the
procedure in 6.3.
Avoid kinking or crushing the exible stem.
Minimum bending radius
- 25 mm for protected capillary
- 2 mm for unprotected capillary
(MDT 435 / 467)
The connector must be easily accessible.
- Mount the electronics housing of the PT with the fastening clip DYNISCO P/N 200982
(included). See mounng example in gure 09.
- Addionally secure the exible stem between the electronics housing with a
standard cable clip.
Fig. 09: Mounng example for Pressure Transmier with exible stem
This manual suits for next models
8
Table of contents
Other Dynisco Transducer manuals
Popular Transducer manuals by other brands

S+S Regeltechnik
S+S Regeltechnik PREMASGARD 1110 Operating Instructions, Mounting & Installation

Airmar
Airmar M260 Owner's guide & installation instructions

HBM
HBM PAD4001A quick start guide

HPS
HPS mks 999 Quattro Series Operation and maintenance manual

HBM
HBM SK12 Mounting instructions

Milltronics
Milltronics XLS Series instruction manual

Balluff
Balluff BTL6-V5 V-M PF-S115 Series user guide

novotechnik
novotechnik TM1 Series user manual

Simrad
Simrad 50-200 COMBI C - REV D installation manual

Thyracont
Thyracont VCP63MV operating instructions

Simrad
Simrad ES38DD - REV E installation manual

HyQuest Solutions
HyQuest Solutions WL3100 user manual