
EARTHSTONE OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS 9
COMMERCIAL DIRECT VENTING
EXISTING ROOFEXISTING ROOF
EXISTING CEILINGEXISTING CEILING
FAN ADAPTER PLATEFAN ADAPTER PLATE
SELKIRK METALBESTOS IPS C1 OR
METAL-FAB MODEL IPIC-1
UL LISTED GREASE DUCT/BUILDING
HEATING APPLIANCE CHIMNEY
A FIELD BUILT DUCT, CONSTRUCTED
AND INSTALLED TO THE SPECIFICATIONS
OF A GREASE DUCT PER NFPA 96 OR
THE IMC MAY ALSO BE USED.
SELKIRK METALBESTOS IPS C1 OR
METAL-FAB MODEL IPIC-1
UL LISTED GREASE DUCT/BUILDING
HEATING APPLIANCE CHIMNEY
A FIELD BUILT DUCT, CONSTRUCTED
AND INSTALLED TO THE SPECIFICATIONS
OF A GREASE DUCT PER NFPA 96 OR
THE IMC MAY ALSO BE USED.
3" MIN. CLEARANCE3" MIN. CLEARANCE
EXHAUST FANAND CURB POWER
VENTILATOR FOR RESTAURANT EXHAUST
APPLIANCES. RATED FOR 500F DEG.
MODELS: ENERVEX GSV SERIES. CALL
EARTHSTONE FOR DETAILS
800-840-4915 - 818-553-1134
EXHAUST FANAND CURB POWER
VENTILATOR FOR RESTAURANT EXHAUST
APPLIANCES. RATED FOR 500F DEG.
MODELS: ENERVEX GSV SERIES. CALL
EARTHSTONE FOR DETAILS
800-840-4915 - 818-553-1134
IF ACEILING OR WALL DOES NOT
HAVE A FIRE RESISTANCE RATING
AND IS PENETRATED BY AMODEL
PS GREASE DUCT INSTALLED AT THE
CORRECT MINIMUM CLEARANCE FOR
UNENCLOSED DUCT, THEN AN
ENCLOSURE MAY NOT BE REQUIRED
AROUND THE DUCT SHAFT.
IF ACEILING OR WALL DOES NOT
HAVE A FIRE RESISTANCE RATING
AND IS PENETRATED BY AMODEL
PS GREASE DUCT INSTALLED AT THE
CORRECT MINIMUM CLEARANCE FOR
UNENCLOSED DUCT, THEN AN
ENCLOSURE MAY NOT BE REQUIRED
AROUND THE DUCT SHAFT.
3" MIN CLEARANCE TO COMBUSTIBLES
REQUIRED FOR SELKIRK
METALBESTOS
MODEL IPS C1
3" MIN CLEARANCE TO COMBUSTIBLES
REQUIRED FOR SELKIRK
METALBESTOS
MODEL IPS C1
REFER TO LOCAL JURISDICTION
AUTHORITIES.
REFER TO LOCAL JURISDICTION
AUTHORITIES.
FIGURE 18
GREASE DUCT HEATINGAPPLIANCE CHIMNEY ATTACHED TO PRIMARY HOOD
THIS DIAGRAM GENERALLY DEPICTSTHE INSTALLATION REQUIRED TO MAINTAIN THE U.L. LISTING OF THE OVEN
FOR THIS TYPE OF VENTING APPLICATION.
FOR SPECIFIC INSTALLATION REQUIREMENTS REFER TO SELKIRK METALBESTOS MODEL IPS GREASE DUCT
INSTALLATION 8. MODEL PS AND IPS GREASE DUCTCOMPLIES WITH NFPA, SBCCI, ICBOAND BOCA WHEN
PROPERLY INSTALLED PER ITS INSTALLATION INSTRUCTIONS.
CONTACT LOCALAUTHORITY HAVING JURISDICTION REGARDING FIRE RATED DUCT SHAFT.
NOTE: OTHER U.L. LISTED SYSTEMS MAY BE SUBSTITUTED FORTHE METALBESTOS SYSTEM DEPICTED
IN THIS DIAGRAM. TO MAINTAIN THE U.L. LISTING OF THE OVEN THE SYSTEM MUST BEA U.L. LISTED
GREASE DUCT WHICH IS ALSOA U.L. LISTED BUILDING HEATING APPLIANCE CHIMNEY INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER'S GREASE DUCT INSTALLATION INSTRUCTIONS.
30” min.
80.000
FOR ORDERING PARTS MENTIONED ON THIS PAGE CONTACT EARTHSTONE ORYOUR
SUPPLIER. Tel: 800-840-4915- 818-553-1134
6 INCH DIAMETER GREASE DUCT - Models - 90, Café, 110, 110-Due (Dual opening)
8 INCH DIAMETER GREASE DUCT - Models 90-Due, 120, 130, 160, 110-Due (Single opening), 130-Due (Dual opening)
10 INCH DIAMETER GREASE DUCT - Model 130-Due (Single opening)